Product Model
140G-HC0F3-D12

Selling Points
- 11. Reliable Operation: The Allen Bradley 140G-H0F3-D12 is built to withstand rigorous industrial environments, ensuring long-term performance and minimal downtime.;
- 22. Adjustable Trip Units: Equipped with adjustable thermal and magnetic trip units, this circuit breaker can be tailored to meet specific application requirements, providing enhanced safety and reliability.;
- 33. High Interrupting Rating: With an interrupting rating of 35kA at 480V AC, this circuit breaker can handle high short-circuit currents, making it suitable for demanding industrial settings.;
- 44. Robust Construction: Constructed with a durable H-frame design, the 140G-H0F3-D12 is built to last, offering a long service life and minimal maintenance needs.;
- 55. Versatile Mounting Options: Available for front-side screw connection and optional DIN rail mounting, this circuit breaker provides flexibility in installation, making it easy to integrate into various industrial setups.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Weight Unit | KG | Stock Status | NON_STOCKED |
Dimension Length | 0.0 | Dimension Width | 0.0 |
Lead Time | 13 | Dimension Height | 0.0 |
Quick Turnaround | false | Preferred Availability | false |
Repairable | NOT_REPAIRABLE | Ambient temperature without derating | 104 |
Rated uninterrupted current (Iu) | 98% of current rating @ 3000 m (9840 ft) altitude | Operational voltage (Ue) | 90% of voltage rating @ 3000 m (9840 ft) altitude |
Wire temperature rating | Cu 75 °C | Storage temperature | -40 |
Depth | 82.5 | Width | 90 |
Device construction | Built-in device fixed built-in technique | Frame size | 125 A H frame current limiting |
Height | 130 | Factory option | None |
Mechanical life operations | 25000 | Weight | 0.999 |
Degree of protection (IP) | IP40 | DIN rail (top hat rail) mounting optional | Yes |
Suitable for DIN rail (top hat rail) mounting | No | Type of electrical connection of main circuit | Screw connection |
Position of connection for main current circuit | Front side | Motor drive optional | Yes |
With switched-off indicator | No | Motor drive integrated | No |
Protection type | T/M-adjustable thermal/adjustable magnetic TMA | Rated service short-circuit breaking capacity (Ics) | IEC 60947-2: 100% lcu @ 690V AC @ 50/60Hz |
Rated ultimate short-circuit breaking capacity (Icu) | IEC 60947-2: 85kA @ 500V DC, 2 poles in series | Interrupting rating | 35kA @ 500V DC, 2 poles in series per NEMA, UL, CSA |
Interrupting rating (I2t) | 704 x 103, rated current (In) upto 125A @ 480V AC | Intermediate point (I2t) | 655 x 103, rated current (In) upto 125A @ 600V AC |
Threshold current (I2t) | 301 x 103, rated current (In) upto 125A @ 600V AC | Threshold current (Ip) | 10 kA, rated current (In) upto 125A @ 600V AC |
Interrupting rating (Ip) | 31.1 kA, rated current (In) upto 125A @ 480V AC | Intermediate point (Ip) | 21 kA, rated current (In) upto 125A @ 480V AC |
Interrupting rating (Irms) | 35 kA, rated current (In) upto 125A @ 600V AC | Threshold current (Irms) | 6 kA, rated current (In) upto 125A @ 600V AC |
Intermediate point (Irms) | 50 kA, rated current (In) upto 125A @ 480V AC | Electrical life cycle | 8000 @ 415V AC |
Insulation voltage (Ui) | Rated 1000V per IEC | Thermal trip current (Ir) | 87 to 125 A |
Magnetic trip current (Im) | 625 to 1250 A | Rated impulse withstand voltage (Uimp) | 8 |
Type of control element | Toggle | Rated permanent current Iu | 125 |
Complete device with protection unit | Yes | Integrated earth fault protection | No |
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz | 120 kA | With integrated under voltage release | No |
Number of poles | 3 |
Specifications may be subject to change without notice