Rockwell Automation 140G-K6F3-D30-CJ-MU

Selling Points

  • 11. High Interrupt Rating: The Allen Bradley 140G-K6F3-D30 boasts a 65kA interrupt rating at 480V AC, ensuring it can handle high short-circuit currents effectively, making it ideal for demanding industrial applications.;
  • 22. Thermal/Magnetic Trip: This circuit breaker features a thermal/magnetic trip mechanism, providing adjustable thermal and magnetic settings for customizable protection. This ensures that the device can be tailored to specific application requirements.;
  • 33. Reliable Protection: With a rated current of 300A (80% of MCCB), the 140G-K6F3-D30 offers reliable protection against overcurrents, ensuring the safety of electrical systems and equipment.;
  • 44. Versatile Mounting Options: Although not designed for DIN rail mounting, the device's front-side screw connection for the main current circuit provides flexibility in installation, making it suitable for various mounting configurations.;
  • 55. Durable Construction: Built with a robust K frame design, this circuit breaker is constructed to withstand harsh industrial environments. It has a mechanical life of 20,000 operations and can operate in temperatures up to 104°F (40°C) without derating.
Product Details
140G-K6F3-D30-CJ-MU
Rockwell Automation

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Dimension Unit
CM
Weight Unit
KG
Stock Status
NON_STOCKED
Dimension Length
38.1
Dimension Width
38.1
Lead Time
15
Dimension Height
27.94
Quick Turnaround
false
Preferred Availability
false
Repairable
NOT_REPAIRABLE
Ambient temperature without derating
104 °F
Rated uninterrupted current (Iu)
98% of current rating @ 3000 m (9840 ft) altitude
Operational voltage (Ue)
90% of voltage rating @ 3000 m (9840 ft) altitude
Wire temperature rating
Al or Cu 75°C
Storage temperature
-40 °F
Depth
108.5 mm
Width
140 mm
Device construction
Built-in device fixed built-in technique
Height
205 mm
Factory option
Standard busbar mount, universal
Shock
Peak acceleration: 150 m/s2 peak, pulse duration 11 ms
Vibration
2...13.2 Hz ±1 mm, 13.2...100 Hz ±0.7 G
Mechanical life operations
20000 /h
Weight
8.305
Degree of protection (IP)
IP40
DIN rail (top hat rail) mounting optional
False
Suitable for DIN rail (top hat rail) mounting
False
Type of electrical connection of main circuit
Screw connection
Position of connection for main current circuit
Front side
Motor drive optional
True
With switched-off indicator
False
Motor drive integrated
False
Protection type
T/M-adjustable thermal/adjustable magnetic TMA
Rated service short-circuit breaking capacity (Ics)
IEC 60947-2: 100% Icu @ 750V DC, 3-poles in series, thermal-magnetic trip units only
Rated ultimate short-circuit breaking capacity (Icu)
IEC 60947-2: 70kA @ 400...415V AC, 50/60 Hz
Interrupting rating
65kA @ 480V AC, 50/60 Hz per NEMA, UL, CSA
Electrical life cycle
7000 (400 A)/5000 (600 A) @ 415V AC
Thermal trip rating, max
300 A @ ambient temperature 40 °C
Insulation voltage (Ui)
Rated 1000V per IEC
Watt loss
Thermal magnetic type: 40.8 W
Voltage for reverse-fed circuit breaker, max
690V AC per IEC
Magnetic trip current (Im)
1500 A
Thermal trip current (Ir)
210 A
Current range
80% MCCB
Frame size
400 A
Rated impulse withstand voltage (Uimp)
8 kV
Type of control element
Toggle
Rated permanent current Iu
300 A
Complete device with protection unit
True
Integrated earth fault protection
False
With integrated under voltage release
False
Number of auxiliary contacts as change-over contact
3
Number of poles
3

Specifications may be subject to change without notice