Product Model
150-C43NBR

Selling Points
- 11. Enhanced Motor Protection: The Allen Bradley 150-C43NBR features strong protection against voltage spikes and transients, ensuring reliable operation under difficult conditions.;
- 22. Flexible Control Setup: With a 24V AC/DC control voltage, this smart motor controller offers flexible control setups and easy system integration.;
- 33. Compact Design: Its compact dimensions (72mm x 206mm x 130mm) make it suitable for many industrial applications, facilitating easy installation and integration into control panels and machinery.;
- 44. Thermal Management: The 150-C43NBR dissipates 34W at 14.3-43A running currents, maintaining appropriate operating temperatures and extending gadget life through smart thermal management.;
- 55. Multi-Layered Safety Features: Equipped with a 150A non-time-delay K5 fuse, a 150A thermal magnetic circuit breaker, and a 90A Class CC/J/L time-delay fuse, this controller provides multiple layers of protection against short circuits and major electrical problems.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Dimension Unit | CM | Weight Unit | KG |
Weight | 3.329 | Stock Status | STOCKED |
Dimension Length | 21.692 | Dimension Width | 29.896 |
Lead Time | 5 | Dimension Height | 14.402 |
Quick Turnaround | false | Preferred Availability | true |
Repairable | NOT_REPAIRABLE | Enclosure | Open type |
Number of poles | Equipment is designed for 3-phase only for power circuit | Pollution degree | 2 |
Altitude | 2000 m | EMC immunity levels | Surge transient: per EN/IEC 60947-4-2 per IEC |
EMC emission levels | Radiated emission: Class A per IEC | Operating temperature | Open: -5 to 50 °C (23 to 122 °F) |
Humidity | 5...95% noncondensing | Rated surrounding temperature range without derating | -5 °C |
Storage and transportation temperature | -25 °C | Selectable soft stop | Off, 100%, 200%, or 300% of the start time setting when wired |
Selectable initial torque | 15%, 25%, 35%, and 65% of locked rotor torque | Selectable kick start - 450% FLA | 0, 0.5, 1.0, or 1.5 s |
Function | Single direction | Internal bypass | Yes |
Break | TB-97, -98 (OVLD/Fault): 72VA for auxiliary contacts | Make | TB-97, -98 (OVLD/Fault): 432VA for auxiliary contacts |
Vibration | Opsal: 1.0 G peak, 0.15 mm (0.006 in) displacement | Shock | Opsal: 15 G |
Degree of protection (IP) | IP2X | Input ON-state current (IN1, IN2) | 9.8mA @ 120V AC/19.6mA @ 240V AC for control circuit, 7.3mA @ 24V AC/DC for control circuit |
Input ON-state voltage, during start (IN1, IN2) | 85V AC @ 19.2V DC/19.2V AC minimum for control circuit | Selectable current limit | 150%, 250%, 350%, and 450% of full load current |
Input OFF-state voltage (IN1, IN2), max | 40V AC @ 17V DC/12V AC for control circuit | Selectable start times | 2, 5, 10, 15, 20, 25, or 30 s |
Selectable overload trip class | Trip Class 10, 15, or 20 | Short circuit protection device performance (SCPD) type | Type 1 |
Integrated motor overload protection | Yes | Rated control supply voltage at DC | 24 V |
Standard available fault current, max | 10 kA @ maximum standard fuse 250 A for delta device opsal current rating | Standard controller feature | Soft stop |
Rated operational current, max | TB-97, -98 (OVLD/Fault): 0.6A @ 120V AC and 0.3A @ 240V AC for auxiliary contacts | Utilization category | TB-23, -24 (normal/up-to-speed), TB-33, -34 (normal/up-to-speed): C300/R150 per UL/CSA/NEMA for Side mount auxiliary contacts |
Type of contacts | TB-97, -98 (OVLD/Fault): Normally Open (N.O.) for auxiliary contacts | Type of control circuit | TB-97, -98 (OVLD/Fault): Electromagnetic relay for auxiliary contacts |
Conventional thermal current (Ith) | TB-97, -98 (OVLD/Fault): 1 A for auxiliary contacts | Type of current | TB-97, -98 (OVLD/Fault): AC/DC for auxiliary contacts |
High capacity available fault current, max | 70kA @ 600V, maximum current 90 A time delay Class J or Class L fuse for line connected motors | Number of contacts | TB-97, -98 (OVLD/Fault): 1 for auxiliary contacts |
Short-circuit protection device list | Non-time delay Thermal magnetic circuit breaker High capacity time delay class CC/J/L | Input OFF-state current | <10 mA, <12 mA @ input OFF-state voltage (IN1, IN2) for control circuit |
Rated operational voltage | 250V AC/30V DC per UL/CSA/NEMA for Side mount auxiliary contacts | Insulation voltage | Rated 600V AC per UL/CSA/NEMA for power circuit |
Dielectric withstand | 2500V AC per IEC for power circuit | Rated impulse voltage | 6 kV for power circuit |
Overvoltage category | III per IEC for side mount auxiliary contacts | Operating frequency | 50/60 Hz per UL/CSA/NEMA for power circuit |
Repetitive peak voltage | 1400V per UL/CSA/NEMA for power circuit | DV/DT protection | 1000V/μs for power circuit |
Controller type | SMC-3 | Rated control supply voltage at AC 60 Hz | 24 V |
Rated control supply voltage at AC 50 Hz | 24 V | Rated operating voltage Ue | 200 |
Voltage type for actuating | AC/DC | With display | No |
Specifications may be subject to change without notice