Selling Points

  • 11. Efficient Motor Control: The Allen-Bradley 150-C60NCR offers precise control over motor operations, ensuring optimal performance and energy efficiency in industrial applications.;
  • 22. Reliable Design: Built with robust components, this smart motor controller provides reliable operation even in demanding environments, minimizing downtime and maintenance.;
  • 33. Versatile Applications: Suitable for a wide range of applications such as compressors, chillers, pumps, conveyors, and crushers, making it a versatile solution for various industrial needs.;
  • 44. Easy Setup: The controller features easy and secure setup using DIP switches, allowing for quick installation and configuration without requiring extensive technical expertise.;
  • 55. Advanced Protection Features: Equipped with built-in electronic motor overload protection and a hold-to-test/push-to-reset button, ensuring safe and secure operation of the motor.
Product Details
150-C60NCR
Rockwell Automation

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Dimension Unit
CM
Weight Unit
KG
Weight
3.4
Stock Status
STOCKED
Dimension Length
25.499
Dimension Width
28.001
Lead Time
93
Dimension Height
18.999
Quick Turnaround
false
Preferred Availability
false
Repairable
NOT_REPAIRABLE
Enclosure
Open type
Number of poles
Equipment is designed for 3-phase only for power circuit
Pollution degree
2
Altitude
2000 m
EMC immunity levels
Surge transient: per EN/IEC 60947-4-2 per IEC
EMC emission levels
Radiated emission: Class A per IEC
Operating temperature
Open: -5 to 50 °C (23 to 122 °F)
Humidity
5...95% noncondensing
Rated surrounding temperature range without derating
-5 °C
Storage and transportation temperature
-25 °C
Selectable soft stop
Off, 100%, 200%, or 300% of the start time setting when wired
Selectable initial torque
15%, 25%, 35%, and 65% of locked rotor torque
Selectable kick start - 450% FLA
0, 0.5, 1.0, or 1.5 s
Function
Single direction
Internal bypass
Yes
Break
TB-97, -98 (OVLD/Fault): 72VA for auxiliary contacts
Make
TB-97, -98 (OVLD/Fault): 432VA for auxiliary contacts
Vibration
Opsal: 1.0 G peak, 0.15 mm (0.006 in) displacement
Shock
Opsal: 15 G
Degree of protection (IP)
IP2X
Input ON-state current (IN1, IN2)
9.8mA @ 120V AC/19.6mA @ 240V AC for control circuit, 7.3mA @ 24V AC/DC for control circuit
Input ON-state voltage, during start (IN1, IN2)
85V AC @ 19.2V DC/19.2V AC minimum for control circuit
Selectable current limit
150%, 250%, 350%, and 450% of full load current
Input OFF-state voltage (IN1, IN2), max
40V AC @ 17V DC/12V AC for control circuit
Selectable start times
2, 5, 10, 15, 20, 25, or 30 s
Selectable overload trip class
Trip Class 10, 15, or 20
Short circuit protection device performance (SCPD) type
Type 1
Integrated motor overload protection
Yes
Rated control supply voltage at DC
24 V
Standard controller feature
Soft stop
Rated operational current, max
TB-97, -98 (OVLD/Fault): 0.6A @ 120V AC and 0.3A @ 240V AC for auxiliary contacts
Utilization category
TB-23, -24 (normal/up-to-speed), TB-33, -34 (normal/up-to-speed): C300/R150 per UL/CSA/NEMA for Side mount auxiliary contacts
Type of contacts
TB-97, -98 (OVLD/Fault): Normally Open (N.O.) for auxiliary contacts
Type of control circuit
TB-97, -98 (OVLD/Fault): Electromagnetic relay for auxiliary contacts
Conventional thermal current (Ith)
TB-97, -98 (OVLD/Fault): 1 A for auxiliary contacts
Type of current
TB-97, -98 (OVLD/Fault): AC/DC for auxiliary contacts
Number of contacts
TB-97, -98 (OVLD/Fault): 1 for auxiliary contacts
Short-circuit protection device list
Non-time delay Thermal magnetic circuit breaker High capacity time delay class CC/J/L
Input OFF-state current
<10 mA, <12 mA @ input off-state voltage (IN1, IN2) for control circuit
Rated operational voltage
250V AC/30V DC per UL/CSA/NEMA for Side mount auxiliary contacts
Insulation voltage
Rated 600V AC per UL/CSA/NEMA for power circuit
Dielectric withstand
2500V AC per IEC for power circuit
Rated impulse voltage
6 kV for power circuit
Overvoltage category
III per IEC for side mount auxiliary contacts
Operating frequency
50/60 Hz per UL/CSA/NEMA for power circuit
Repetitive peak voltage
1600V per UL/CSA/NEMA for power circuit
DV/DT protection
1000V/μs for power circuit
Controller type
SMC-3
Rated control supply voltage at AC 60 Hz
24 V
Rated control supply voltage at AC 50 Hz
24 V
Rated operating voltage Ue
200
Voltage type for actuating
AC/DC
With display
No

Specifications may be subject to change without notice