Rockwell Automation 150-C85NBD

Selling Points

  • 11. Efficient Motor Control: The Allen-Bradley 150-C85NBD soft starter ensures smooth and efficient motor operation by gradually increasing the motor speed, reducing wear and tear on the motor and its components.;
  • 22. Adjustable Start Times: With selectable start times ranging from 2 to 30 seconds, you can customize the startup process to meet the specific needs of your application, ensuring optimal performance and safety.;
  • 33. Soft Stop Functionality: The soft stop feature allows for a controlled shutdown of the motor, reducing the impact on the motor and its surroundings, and extending its lifespan.;
  • 44. Integrated Overload Protection: The 150-C85NBD comes with true motor overload protection, which automatically shuts off the motor if it exceeds the set limits, preventing damage and ensuring safe operation.;
  • 55. Versatile Power Range: Compatible with 100-240V AC, this soft starter is versatile and can be used in a variety of applications, making it a reliable choice for both new and existing installations.
Product Details
150-C85NBD
Rockwell Automation

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Dimension Unit
CM
Weight Unit
KG
Weight
3.338
Stock Status
STOCKED
Dimension Length
22.606
Dimension Width
29.972
Lead Time
92
Dimension Height
13.97
Quick Turnaround
false
Preferred Availability
true
Repairable
NOT_REPAIRABLE
Enclosure
Open type
Number of poles
Equipment is designed for 3-phase only for power circuit
Pollution degree
2
Altitude
2000 m
EMC immunity levels
Surge transient: per EN/IEC 60947-4-2 per IEC
EMC emission levels
Radiated emission: Class A per IEC
Operating temperature
Open: -5 to 50 °C (23 to 122 °F)
Humidity
5...95% noncondensing
Rated surrounding temperature range without derating
-5 °C
Storage and transportation temperature
-25 °C
Selectable soft stop
Off, 100%, 200%, or 300% of the start time setting when wired
Selectable initial torque
15%, 25%, 35%, and 65% of locked rotor torque
Selectable kick start - 450% FLA
0, 0.5, 1.0, or 1.5 s
Function
Single direction
Internal bypass
Yes
Break
TB-97, -98 (OVLD/Fault): 72VA for auxiliary contacts
Make
TB-97, -98 (OVLD/Fault): 432VA for auxiliary contacts
Vibration
Opsal: 1.0 G peak, 0.15 mm (0.006 in) displacement
Shock
Opsal: 15 G
Degree of protection (IP)
IP2X
Input ON-state current (IN1, IN2)
9.8mA @ 120V AC/19.6mA @ 240V AC for control circuit, 7.3mA @ 24V AC/DC for control circuit
Input ON-state voltage, during start (IN1, IN2)
85V AC @ 19.2V DC/19.2V AC minimum for control circuit
Selectable current limit
150%, 250%, 350%, and 450% of full load current
Input OFF-state voltage (IN1, IN2), max
40V AC @ 17V DC/12V AC for control circuit
Selectable start times
2, 5, 10, 15, 20, 25, or 30 s
Selectable overload trip class
Trip Class 10, 15, or 20
Short circuit protection device performance (SCPD) type
Type 1
Integrated motor overload protection
Yes
Standard controller feature
Soft stop
Rated operational current, max
TB-97, -98 (OVLD/Fault): 0.6A @ 120V AC and 0.3A @ 240V AC for auxiliary contacts
Utilization category
TB-23, -24 (normal/up-to-speed), TB-33, -34 (normal/up-to-speed): C300/R150 per UL/CSA/NEMA for Side mount auxiliary contacts
Type of contacts
TB-97, -98 (OVLD/Fault): Normally Open (N.O.) for auxiliary contacts
Type of control circuit
TB-97, -98 (OVLD/Fault): Electromagnetic relay for auxiliary contacts
Conventional thermal current (Ith)
TB-97, -98 (OVLD/Fault): 1 A for auxiliary contacts
Type of current
TB-97, -98 (OVLD/Fault): AC/DC for auxiliary contacts
High capacity available fault current, max
70kA @ 600V, maximum current 300 A time delay Class J or Class L fuse for inside delta connected motors
Number of contacts
TB-97, -98 (OVLD/Fault): 1 for auxiliary contacts
Short-circuit protection device list
Non-time delay Thermal magnetic circuit breaker High capacity time delay class CC/J/L
Input OFF-state current
<10 mA, <12 mA @ input OFF-state voltage (IN1, IN2) for control circuit
Rated operational voltage
250V AC/30V DC per UL/CSA/NEMA for Side mount auxiliary contacts
Insulation voltage
Rated 600V AC per UL/CSA/NEMA for power circuit
Dielectric withstand
2500V AC per IEC for power circuit
Rated impulse voltage
6 kV for power circuit
Overvoltage category
III per IEC for side mount auxiliary contacts
Operating frequency
50/60 Hz per UL/CSA/NEMA for power circuit
Repetitive peak voltage
1400V per UL/CSA/NEMA for power circuit
DV/DT protection
1000V/μs for power circuit
Controller type
SMC-3
Rated control supply voltage at AC 60 Hz
100
Rated control supply voltage at AC 50 Hz
100
Rated operating voltage Ue
200
Voltage type for actuating
AC/DC
With display
No

Specifications may be subject to change without notice