Rockwell Automation 150-F1250NZA

Selling Points

  • 11. Efficient Motor Control: The Allen-Bradley 150-F1250NZA SMC-Flex Solid State Controller is designed with an open enclosure to provide efficient motor control, making it ideal for robust industrial applications.;
  • 22. High Power Handling: Capable of handling a controller rating of 1250A and delivering up to 1000 horsepower at 460V AC, this controller is perfect for high-power requirements.;
  • 33. Versatile Voltage Range: Operates with an input voltage ranging from 230 to 690V AC, supporting both 50 and 60 Hz frequencies, making it versatile for various industrial settings.;
  • 44. Reliable Performance: With a robust design and reliable performance, this controller ensures consistent operation in demanding industrial environments.;
  • 55. Comprehensive Compatibility: Supports a wide range of control voltages (230/240V AC) tailored for units between 625 to 1250 A, ensuring compatibility with various system configurations.
Product Details
150-F1250NZA
Rockwell Automation

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Weight Unit
KG
Stock Status
NON_STOCKED
Dimension Length
0.0
Dimension Width
0.0
Lead Time
20
Dimension Height
0.0
Quick Turnaround
false
Preferred Availability
false
Repairable
REPAIRABLE
Metal parts construction
Plated brass, copper or painted steel
Control modules construction
Thermoset and thermoplastic moldings
Enclosure
Open type
Number of poles
3
Line/load side power terminals
Two 13.5 mm (0.53 in) diam holes per power pole
Control terminals
ClAing yoke connection, M3 screw clA
Power terminal markings
NEMA, CENELEC EN50 012
Function
Single direction
Internal bypass
Yes
Break
360VA for auxiliary contacts
Make
3600VA for auxiliary contacts
Vibration
Opsal: 1.0 G peak, 0.15 mm (0.006 in) displacement
Power pole construction
Heatsink hockey puck thyristor modular design
Height
1041.1 mm (41 in)
Depth
346.2 mm (13.63 in)
Width
596.9 mm (23.50 in)
Shock
Opsal: 4 G
Weight
185.917
Pollution degree
2
Altitude
2000 m
EMC immunity levels
Surge transient: per EN/IEC 60947-4-2
EMC emission levels
Radiated emission: Class A
Protection against electrical shock
IP00 (open device) per IEC for power circuit
Operating temperature
Open: -5 to 50 °C (23 to 122 °F)
Humidity
5...95% (noncondensing)
Storage and transportation temperature
-20
Steady state heat dissipation with control and fan power
1222 W
Contact type
Auxiliary contacts 19/20 (Aux #1), 29/30 (Aux #2), 31/32 (Aux #3) and 33/34 (Aux #4)
Input ON-state current
20mA @ 120V AC/40mA @ 240V AC, 7.6mA @ 24V AC/DC for control circuit
Rated operational current
3A @ 120V AC, 1.5A @ 240V AC for auxiliary contacts
Input ON-state voltage, min
85V AC @ 19.2V DC/20.4V AC for control circuit
Input OFF-state voltage, max
50V AC @ 10V DC/12V AC for control circuit
Reset resistance
1600 ? ± 100 ? for PTC input ratings
Response resistance
3400 ? ± 150 ? for PTC input ratings
Short circuit trip resistance
25 ? ± 10 ? for PTC input ratings
Tachometer input
0...5V DC @ 4.5V DC = 100% Speed
Cold resistance of PTC sensor chain, max
1500 ? for PTC input ratings
Response time
800 ms for PTC input ratings
Transformer rating control module
751 VA (recommended 800 VA)
Voltage at PTC terminals (RPTC = 4 kΩ), max
<7.5 for PTC input ratings
Voltage at PTC terminals (RPTC = open), max
30V for PTC input ratings
Number of sensors, max
6 for PTC input ratings
Short circuit protection device performance (SCPD) type
Type 1
Integrated motor overload protection
Yes
Optional controller feature
SMB smart motor braking control: provides motor braking without additional equipment for applications that require the motor to stop quickly, braking current is adjustable from 0...400% of the motor’s full-load current rating
Standard available fault current, max
85kA @ 690V for maximum FLC
Standard controller feature
Status indication: stopped, starting, stopping, at speed, alarm and fault
Utilization category
MG 1 per UL/CSA/NEMA for power circuit
Type of contacts
Progmable NO/NC for auxiliary contacts
Type of control circuit
Electromagnetic relay for auxiliary contacts
Conventional thermal current (Ith)
AC/DC: 5 A for auxiliary contacts
Type of current
AC for auxiliary contacts
High capacity available fault current, max
85kA @ 600V, maximum current 3000 A time delay Class J or Class L fuse for line connected motors
Number of contacts
1 for auxiliary contacts
Short-circuit protection device list
Standard fuse, circuit breaker and high capacity time delay class CC/J/L
Input OFF-state current
<10 mA AC, <3 mA DC for control circuit @ input OFF-state voltage
Rated operational voltage
230...690V/Y (-15%, +10%) per IEC for power circuit
Insulation voltage
Rated 690V per IEC for power circuit
Ampere tested north american style, max
Two fuses in parallel A070URD33xxx1250 @ 690V for maximum FLC
Ampere tested european style, max
Two fuses in parallel 6,6URD33xxx1250 @ 690V for maximum FLC
Delta connected motor current
533...1600A @ 500/575V AC, 3-phase
Line connected motor current
416...1250 A @ 600/Y/690V AC, 3-phase
Dielectric withstand
2500V per IEC for power circuit
Rated impulse voltage
6000V per IEC for power circuit
Delta connected motor power, max
900 kW @ 400/415V AC @ 50Hz, 3-phase
Line connected motor power, max
900 kW @ 500V AC @ 50Hz, 3-phase
Operating frequency
50/60 Hz for power circuit
Repetitive peak inverse voltage rating
1800V per UL/CSA/NEMA for power circuit
Heatsink fan rating
150VA @ 110/120V AC or 220/240V AC
Trip current rating
117% of motor FLC
Trip classes
10, 15, 20 and 30
Control options
None
Controller type
Soft starter
Overload current for delta connected devices
533 A
Overload current for line connected devices
416 A
Rated control supply voltage at AC 60 Hz
230 V
Rated control supply voltage at AC 50 Hz
230 V
Rated operating voltage Ue
230 V
Voltage type for actuating
AC
With display
Yes
Product Family
SMC Flex
Controller Rating
1250 A 1000Hp @ 460V AC
Control Voltage
230...240V AC

Specifications may be subject to change without notice