Rockwell Automation 150-F201NCR

Selling Points

  • 11. Efficient Motor Control: Handles motor currents between 116 and 348 A, making it suitable for a wide range of applications.;
  • 22. Robust Performance: Designed for robust performance with a three-phase input line voltage range of 200 to 575V AC, supporting both 50 and 60 Hz line frequencies.;
  • 33. Versatile Control Voltage: Offers a versatile control voltage of 24V AC/DC, ensuring compatibility with various systems.;
  • 44. Advanced Fault Detection: Reliably detects and alerts over various faults including phase reversal and voltage imbalance, ensuring safe operation.;
  • 55. User-Friendly Interface: Features a backlit LCD display and keypad interface, making it easy to configure and monitor motor operations.
Product Details
150-F201NCR
Rockwell Automation

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Dimension Unit
CM
Weight Unit
KG
Stock Status
NON_STOCKED
Dimension Length
64.389
Dimension Width
31.09
Lead Time
10
Dimension Height
33.604
Quick Turnaround
false
Preferred Availability
false
Repairable
REPAIRABLE
Metal parts construction
Plated brass, copper or painted steel
Control modules construction
Thermoset and thermoplastic moldings
Enclosure
Open type
Number of poles
3
Line/load side power terminals
Two M10 x 1.5 diam holes per power pole
Control terminals
ClAing yoke connection, M3 screw clA
Power terminal markings
NEMA, CENELEC EN50 012
Function
Single direction
Internal bypass
Yes
Break
360VA for auxiliary contacts
Make
3600VA for auxiliary contacts
Vibration
Opsal: 1.0 G peak, 0.15 mm (0.006 in) displacement
Power pole construction
Heatsink hockey puck thyristor modular design
Height
560 mm (22.05 in)
Depth
253.8 mm (9.99 in)
Width
225 mm (8.86 in)
Shock
Opsal: 5.5 G
Weight
30.264
Pollution degree
2
Altitude
2000 m
EMC immunity levels
Surge transient: per EN/IEC 60947-4-2
EMC emission levels
Radiated emission: Class A
Protection against electrical shock
IP2X (with terminal covers) per IEC for power circuit
Operating temperature
Open: -5 to 50 °C (23 to 122 °F)
Humidity
5...95% (noncondensing)
Storage and transportation temperature
-20
Steady state heat dissipation with control and fan power
180 W
Contact type
Auxiliary contacts 19/20 (Aux #1), 29/30 (Aux #2), 31/32 (Aux #3) and 33/34 (Aux #4)
Input ON-state current
20mA @ 120V AC/40mA @ 240V AC, 7.6mA @ 24V AC/DC for control circuit
Rated operational current
3A @ 120V AC, 1.5A @ 240V AC for auxiliary contacts
Input ON-state voltage, min
85V AC @ 19.2V DC/20.4V AC for control circuit
Input OFF-state voltage, max
50V AC @ 10V DC/12V AC for control circuit
Reset resistance
1600 ? ± 100 ? for PTC input ratings
Response resistance
3400 ? ± 150 ? for PTC input ratings
Short circuit trip resistance
25 ? ± 10 ? for PTC input ratings
Allen bradley power supply control module, min
1606-XLP50E @ 24V DC (-15%, +10%)
Tachometer input
0...5V DC @ 4.5V DC = 100% Speed
Cold resistance of PTC sensor chain, max
1500 ? for PTC input ratings
Transient time control module
500 ms @ 24V DC (-15%, +10%)
Inrush time control module
250 ms @ 24V DC (-15%, +10%)
Response time
800 ms for PTC input ratings
Voltage at PTC terminals (RPTC = 4 kΩ), max
<7.5 for PTC input ratings
Steady state watts control module
24 W @ 24V DC (-15%, +10%)
Transient watts control module
60 W @ 24V DC (-15%, +10%)
Voltage at PTC terminals (RPTC = open), max
30V for PTC input ratings
Inrush current control module
5A @ 24V DC (-15%, +10%)
Number of sensors, max
6 for PTC input ratings
Short circuit protection device performance (SCPD) type
Type 1
Integrated motor overload protection
Yes
Rated control supply voltage at DC
24 V
Optional controller feature
SMB smart motor braking control: provides motor braking without additional equipment for applications that require the motor to stop quickly, braking current is adjustable from 0...400% of the motor’s full-load current rating
Standard available fault current, max
70kA @ 690V for maximum FLC
Standard controller feature
Status indication: stopped, starting, stopping, at speed, alarm and fault
Utilization category
MG 1 per UL/CSA/NEMA for power circuit
Type of contacts
Progmable NO/NC for auxiliary contacts
Type of control circuit
Electromagnetic relay for auxiliary contacts
Conventional thermal current (Ith)
AC/DC: 5 A for auxiliary contacts
Type of current
AC for auxiliary contacts
High capacity available fault current, max
70kA @ 600V, maximum current 600 A time delay Class J or Class L fuse for inside delta connected motors
Number of contacts
1 for auxiliary contacts
Short-circuit protection device list
Standard fuse, circuit breaker and high capacity time delay class CC/J/L
Input OFF-state current
<10 mA AC, <3 mA DC for control circuit @ input OFF-state voltage
Rated operational voltage
200...600V AC (-15%, +10%) per UL/CSA/NEMA for power circuit
Insulation voltage
Rated 500V per IEC for power circuit
Transient protection
Metal oxide varistors: 220 J (optional) for power circuit
Ampere tested north american style, max
A070URD33xxx700 @ 690V for maximum FLC
Ampere tested european style, max
6,9 gRB 73xxx630 6,6URD33xxx700 @ 690V for maximum FLC
Delta connected motor current
116...348A @ 500/575V AC, 3-phase
Line connected motor current
67...201 A @ 600/Y/690V AC, 3-phase
Dielectric withstand
2500V per IEC for power circuit
Rated impulse voltage
6000V per IEC for power circuit
Delta connected motor power, max
350Hp @ 575V AC, 60 Hz, 3-phase
Line connected motor power, max
75Hp @ 230V AC, 60 Hz, 3-phase
Operating frequency
50/60 Hz for power circuit
Repetitive peak inverse voltage rating
1600V per UL/CSA/NEMA for power circuit
DV/DT protection
RC snubber network for power circuit
Heatsink fan rating
40VA @ 110/120V AC or 220/240V AC
Transformer control module
75VA @ 100...240V AC (-15%, +10%)
Trip current rating
117% of motor FLC
Trip classes
10, 15, 20 and 30
Control options
None
Controller type
Soft starter
Overload current for delta connected devices
116 A
Overload current for line connected devices
67 A
Rated control supply voltage at AC 60 Hz
24 V
Rated control supply voltage at AC 50 Hz
24 V
Rated operating voltage Ue
200
Voltage type for actuating
AC/DC
With display
Yes
Product Family
SMC Flex
Controller Rating
201 A 75-150Hp @ 460V AC
Control Voltage
24V AC/DC

Specifications may be subject to change without notice