Product Model
150-F361NCRD

Selling Points
- 11. High Power Rating: The Allen-Bradley 150-F361NCRD features a controller rating of 361 A, making it suitable for high-power industrial applications. It supports motors up to 300 HP at 460 V AC, ensuring efficient power management.;
- 22. Versatile Frequency Management: This controller efficiently manages frequencies ranging from 50 to 60 Hz, making it versatile for various industrial power topologies. Its adaptability ensures seamless integration into current systems without disruption.;
- 33. Overload Protection: The Allen-Bradley 150-F361NCRD includes a standard electronic overload protector to safeguard motors from overcurrent. This feature ensures the motor and controller remain resilient even in harsh conditions.;
- 44. Quick Diagnosis with LED Indicators: The controller features LED indicators that signal issues such as overload, overheating, and phase mismatch. These visual alarms enable quick diagnosis and response, ensuring system reliability and minimizing downtime.;
- 55. Reliable Operation in Harsh Conditions: Designed for harsh industrial environments, the Allen-Bradley 150-F361NCRD ensures reliable motor control. Its sturdy build and cutting-edge features make it an ideal safeguard for motors running in demanding conditions, such as processing facilities and manufacturing plants.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Weight Unit | KG | Stock Status | NON_STOCKED |
Dimension Length | 0.0 | Dimension Width | 0.0 |
Lead Time | 74 | Dimension Height | 0.0 |
Quick Turnaround | false | Preferred Availability | false |
Repairable | REPAIRABLE | Metal parts construction | Plated brass, copper or painted steel |
Control modules construction | Thermoset and thermoplastic moldings | Enclosure | Open type |
Number of poles | 3 | Line/load side power terminals | Two M12 x 1.75 diam holes per power pole |
Control terminals | ClAing yoke connection, M3 screw clA | Power terminal markings | NEMA, CENELEC EN50 012 |
Function | Single direction | Internal bypass | Yes |
Break | 360VA for auxiliary contacts | Make | 3600VA for auxiliary contacts |
Vibration | Opsal: 1.0 G peak, 0.15 mm (0.006 in) displacement | Power pole construction | Heatsink hockey puck thyristor modular design |
Height | 600 mm (23.62 in) | Depth | 276.5 mm (10.89 in) |
Width | 290 mm (11.42 in) | Shock | Opsal: 5.5 G |
Weight | 34.915 | Pollution degree | 2 |
Altitude | 2000 m | EMC immunity levels | Surge transient: per EN/IEC 60947-4-2 |
EMC emission levels | Radiated emission: Class A | Protection against electrical shock | IP2X (with terminal covers) per IEC for power circuit |
Operating temperature | Open: -5 to 50 °C (23 to 122 °F) | Humidity | 5...95% (noncondensing) |
Storage and transportation temperature | -20 | Steady state heat dissipation with control and fan power | 245 W |
Contact type | Auxiliary contacts 19/20 (Aux #1), 29/30 (Aux #2), 31/32 (Aux #3) and 33/34 (Aux #4) | Input ON-state current | 20mA @ 120V AC/40mA @ 240V AC, 7.6mA @ 24V AC/DC for control circuit |
Rated operational current | 3A @ 120V AC, 1.5A @ 240V AC for auxiliary contacts | Input ON-state voltage, min | 85V AC @ 19.2V DC/20.4V AC for control circuit |
Input OFF-state voltage, max | 50V AC @ 10V DC/12V AC for control circuit | Reset resistance | 1600 ? ± 100 ? for PTC input ratings |
Response resistance | 3400 ? ± 150 ? for PTC input ratings | Short circuit trip resistance | 25 ? ± 10 ? for PTC input ratings |
Allen bradley power supply control module, min | 1606-XLP50E @ 24V DC (-15%, +10%) | Tachometer input | 0...5V DC @ 4.5V DC = 100% Speed |
Cold resistance of PTC sensor chain, max | 1500 ? for PTC input ratings | Transient time control module | 500 ms @ 24V DC (-15%, +10%) |
Inrush time control module | 250 ms @ 24V DC (-15%, +10%) | Response time | 800 ms for PTC input ratings |
Voltage at PTC terminals (RPTC = 4 kΩ), max | <7.5 for PTC input ratings | Steady state watts control module | 24 W @ 24V DC (-15%, +10%) |
Transient watts control module | 60 W @ 24V DC (-15%, +10%) | Voltage at PTC terminals (RPTC = open), max | 30V for PTC input ratings |
Inrush current control module | 5A @ 24V DC (-15%, +10%) | Number of sensors, max | 6 for PTC input ratings |
Short circuit protection device performance (SCPD) type | Type 1 | Integrated motor overload protection | Yes |
Rated control supply voltage at DC | 24 V | Optional controller feature | SMB smart motor braking control: provides motor braking without additional equipment for applications that require the motor to stop quickly, braking current is adjustable from 0...400% of the motorâs full-load current rating |
Standard available fault current, max | 70kA @ 690V for maximum FLC | Standard controller feature | Status indication: stopped, starting, stopping, at speed, alarm and fault |
Utilization category | MG 1 per UL/CSA/NEMA for power circuit | Type of contacts | Progmable NO/NC for auxiliary contacts |
Type of control circuit | Electromagnetic relay for auxiliary contacts | Conventional thermal current (Ith) | AC/DC: 5 A for auxiliary contacts |
Type of current | AC for auxiliary contacts | High capacity available fault current, max | 69kA @ 600V, maximum current 600 A time delay Class J or Class L fuse for line connected motors |
Number of contacts | 1 for auxiliary contacts | Short-circuit protection device list | Standard fuse, circuit breaker and high capacity time delay class CC/J/L |
Input OFF-state current | <10 mA AC, <3 mA DC for control circuit @ input OFF-state voltage | Rated operational voltage | 200...600V AC (-15%, +10%) per UL/CSA/NEMA for power circuit |
Insulation voltage | Rated 500V per IEC for power circuit | Transient protection | Metal oxide varistors: 220 J (optional) for power circuit |
Ampere tested north american style, max | A070URD33xxx900 @ 690V for maximum FLC | Ampere tested european style, max | 6,9 gRB 73xxx800 6,6URD33xxx900 @ 690V for maximum FLC |
Delta connected motor current | 208...625A @ 500/575V AC, 3-phase | Line connected motor current | 120...361 A @ 600/Y/690V AC, 3-phase |
Dielectric withstand | 2500V per IEC for power circuit | Rated impulse voltage | 6000V per IEC for power circuit |
Delta connected motor power, max | 600Hp @ 575V AC, 60 Hz, 3-phase | Line connected motor power, max | 450Hp @ 600V AC, 60 Hz, 3-phase |
Operating frequency | 50/60 Hz for power circuit | Repetitive peak inverse voltage rating | 1600V per UL/CSA/NEMA for power circuit |
DV/DT protection | RC snubber network for power circuit | Heatsink fan rating | 60VA @ 110/120V AC or 220/240V AC |
Transformer control module | 75VA @ 100...240V AC (-15%, +10%) | Trip current rating | 117% of motor FLC |
Trip classes | 10, 15, 20 and 30 | Control options | Brake control |
Controller type | Soft starter | Overload current for delta connected devices | 208 A |
Overload current for line connected devices | 120 A | Rated control supply voltage at AC 60 Hz | 24 V |
Rated control supply voltage at AC 50 Hz | 24 V | Rated operating voltage Ue | 200 |
Voltage type for actuating | AC/DC | With display | Yes |
Product Family | SMC Flex | Controller Rating | 361 A 150-300Hp @ 460V AC |
Control Voltage | 24V AC/DC |
Specifications may be subject to change without notice