Product Model
150-F5NCDD

Selling Points
- 11. Versatile Motor Control: The Allen Bradley 150-F5NCDD supports a wide range of motor sizes from 0.5 to 3.0 HP, making it suitable for various industrial applications.;
- 22. Advanced Safety Features: Equipped with IP20 protection, this controller ensures safe operation in harsh environments, reducing the risk of electrical shock.;
- 33. Efficient Braking Control: The controller includes an SMB smart motor braking control feature, which allows for quick motor braking without additional equipment, enhancing application reliability.;
- 44. Precise Control and Monitoring: With a display and status indication for stopped, starting, stopping, at speed, alarm, and fault conditions, the 150-F5NCDD provides real-time monitoring and control.;
- 55. Reliable Power Handling: Designed with a heatsink thyristor modular design, this controller can handle high peak currents and repetitive inverse voltages up to 1600V, ensuring reliable operation in demanding power circuits.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Dimension Unit | CM | Weight Unit | KG |
Stock Status | NON_STOCKED | Dimension Length | 29.489 |
Dimension Width | 18.11 | Lead Time | 38 |
Dimension Height | 40.589 | Quick Turnaround | false |
Preferred Availability | false | Repairable | REPAIRABLE |
Metal parts construction | Plated brass, copper or painted steel | Control modules construction | Thermoset and thermoplastic moldings |
Enclosure | Open type | Number of poles | 3 |
Wire strip length | 18...20 mm (0.22...0.34 in) for power terminals | Control terminals | ClAing yoke connection, M3 screw clA |
Power terminal markings | NEMA, CENELEC EN50 012 | Function | Single direction |
Internal bypass | Yes | Tightening torque | 14.7 Nm (130 in-lb) for power terminals |
Break | 360VA for auxiliary contacts | Make | 3600VA for auxiliary contacts |
Vibration | Opsal: 1.0 G peak, 0.15 mm (0.006 in) displacement | Power pole construction | Heatsink thyristor modular design |
Height | 321 mm (12.60 in) | Depth | 203 mm (8 in) |
Width | 150 mm (5.90 in) | Shock | Opsal: 15 G |
Weight | 6.554 | Pollution degree | 2 |
Altitude | 2000 m | EMC immunity levels | Surge transient: per EN/IEC 60947-4-2 |
EMC emission levels | Radiated emission: Class A | Protection against electrical shock | IP20 per IEC for power circuit |
Operating temperature | Open: -5 to 50 °C (23 to 122 °F) | Humidity | 5...95% (noncondensing) |
Storage and transportation temperature | -20 | Steady state heat dissipation with control and fan power | 70 |
Contact type | Auxiliary contacts 19/20 (Aux #1), 29/30 (Aux #2), 31/32 (Aux #3) and 33/34 (Aux #4) | Input ON-state current | 20mA @ 120V AC/40mA @ 240V AC, 7.6mA @ 24V AC/DC for control circuit |
Rated operational current | 3A @ 120V AC, 1.5A @ 240V AC for auxiliary contacts | Upper line side cable size | 2.5...95 mm2 (14...3 AWG) for line power terminals |
Upper load side cable size | 2.5...50 mm2 (14...1 AWG) for load power terminals | Lower load side cable size | 0.8...2.5 mm2 (18...14 AWG) for power terminals |
Lower line side cable size | 0.8...2.5 mm2 (18...14 AWG) for power terminals | Input ON-state voltage, min | 85V AC @ 19.2V DC/20.4V AC for control circuit |
Input OFF-state voltage, max | 50V AC @ 10V DC/12V AC for control circuit | Reset resistance | 1600 ? ± 100 ? for PTC input ratings |
Response resistance | 3400 ? ± 150 ? for PTC input ratings | Short circuit trip resistance | 25 ? ± 10 ? for PTC input ratings |
Allen bradley power supply control module, min | 1606-XLP50E @ 24V DC (-15%, +10%) | Tachometer input | 0...5V DC @ 4.5V DC = 100% Speed |
Cold resistance of PTC sensor chain, max | 1500 ? for PTC input ratings | Transient time control module | 500 ms @ 24V DC (-15%, +10%) |
Inrush time control module | 250 ms @ 24V DC (-15%, +10%) | Response time | 800 ms for PTC input ratings |
Voltage at PTC terminals (RPTC = 4 kΩ), max | <7.5 for PTC input ratings | Steady state watts control module | 24 W @ 24V DC (-15%, +10%) |
Transient watts control module | 60 W @ 24V DC (-15%, +10%) | Voltage at PTC terminals (RPTC = open), max | 30V for PTC input ratings |
Inrush current control module | 5A @ 24V DC (-15%, +10%) | Number of sensors, max | 6 for PTC input ratings |
Short circuit protection device performance (SCPD) type | Type 1 | Integrated motor overload protection | Yes |
Optional controller feature | SMB smart motor braking control: provides motor braking without additional equipment for applications that require the motor to stop quickly, braking current is adjustable from 0...400% of the motorâs full-load current rating | Standard available fault current, max | 5kA @ 200...600V, maximum standard fuse 35 A for delta device opsal current rating |
Standard controller feature | Status indication: stopped, starting, stopping, at speed, alarm and fault | Utilization category | MG 1 per UL/CSA/NEMA for power circuit |
Type of contacts | Progmable NO/NC for auxiliary contacts | Type of control circuit | Electromagnetic relay for auxiliary contacts |
Conventional thermal current (Ith) | AC/DC: 5 A for auxiliary contacts | Type of current | AC for auxiliary contacts |
High capacity available fault current, max | 70kA @ 600V, maximum current 17.5 A time delay Class J or Class L fuse for inside delta connected motors | Number of contacts | 1 for auxiliary contacts |
Short-circuit protection device list | Standard fuse, circuit breaker and high capacity time delay class CC/J/L | Input OFF-state current | <10 mA AC, <3 mA DC for control circuit @ input OFF-state voltage |
Rated operational voltage | 200...600V AC (-15%, +10%) per UL/CSA/NEMA for power circuit | Insulation voltage | Rated 500V per IEC for power circuit |
Transient protection | Metal oxide varistors: 220 J (optional) for power circuit | Delta connected motor current | 1.7...8.7A @ 500/575V AC, 3-phase |
Line connected motor current | 1...5A @ 500/575V AC, 3-phase | Dielectric withstand | 2500V per IEC for power circuit |
Rated impulse voltage | 6000V per IEC for power circuit | Delta connected motor power, max | 7.5Hp @ 575V AC, 60 Hz, 3-phase |
Line connected motor power, max | 3Hp @ 575V AC, 60 Hz, 3-phase | Operating frequency | 50/60 Hz for power circuit |
Repetitive peak inverse voltage rating | 1600V per UL/CSA/NEMA for power circuit | DV/DT protection | RC snubber network for power circuit |
Heatsink fan rating | 20VA @ 110/120V AC or 220/240V AC | Transformer control module | 75VA @ 100...240V AC (-15%, +10%) |
Trip current rating | 117% of motor FLC | Trip classes | 10, 15, 20 and 30 |
Control options | Brake control | Controller type | Soft starter |
Overload current for delta connected devices | 1.7 A | Overload current for line connected devices | 1 A |
Rated control supply voltage at AC 60 Hz | 100 | Rated control supply voltage at AC 50 Hz | 100 |
Rated operating voltage Ue | 200 | Voltage type for actuating | AC |
With display | Yes | Product Family | SMC Flex |
Controller Rating | 5 A 0.5-3.0Hp @ 460V AC | Control Voltage | 100...240V AC |
Specifications may be subject to change without notice