Rockwell Automation 150-F60NBDD

Selling Points

  • 11. Robust Protection Mechanisms: The 150-F60NBD features advanced protection mechanisms, including overflow protection, phase reversal detection, and phase imbalance prevention, ensuring the motor operates within safe parameters and preventing unscheduled downtimes.;
  • 22. Versatile Voltage Configuration: This smart motor controller supports a wide range of voltage configurations, from 200 to 460V AC, and a control voltage of 100 to 240V AC, making it adaptable to various industrial power configurations.;
  • 33. Compact Design: With dimensions of 72mm x 206mm x 130mm, the 150-F60NBD is designed for installations with restricted space, making it a perfect fit for compact industrial settings.;
  • 44. Efficient Thermal Management: The device has a heat dissipation rating of 50 watts, ensuring efficient thermal management and reliable operation in harsh industrial environments.;
  • 55. Compliance with International Standards: The 150-F60NBD is certified with CCC, CE, CSA, and cUL-us, ensuring compliance with international requirements for both performance and safety, making it a reliable choice for critical industrial applications.
Product Details
150-F60NBDD
Rockwell Automation

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Dimension Unit
CM
Weight Unit
KG
Stock Status
NON_STOCKED
Dimension Length
18.39
Dimension Width
30.201
Lead Time
10
Dimension Height
40.894
Quick Turnaround
false
Preferred Availability
false
Repairable
REPAIRABLE
Metal parts construction
Plated brass, copper or painted steel
Control modules construction
Thermoset and thermoplastic moldings
Enclosure
Open type
Number of poles
3
Wire strip length
18...20 mm (0.22...0.34 in) for power terminals
Control terminals
ClAing yoke connection, M3 screw clA
Power terminal markings
NEMA, CENELEC EN50 012
Function
Single direction
Internal bypass
Yes
Tightening torque
14.7 Nm (130 in-lb) for power terminals
Break
360VA for auxiliary contacts
Make
3600VA for auxiliary contacts
Vibration
Opsal: 1.0 G peak, 0.15 mm (0.006 in) displacement
Power pole construction
Heatsink thyristor modular design
Height
321 mm (12.60 in)
Depth
203 mm (8 in)
Width
150 mm (5.90 in)
Shock
Opsal: 15 G
Weight
6.486
Pollution degree
2
Altitude
2000 m
EMC immunity levels
Surge transient: per EN/IEC 60947-4-2
EMC emission levels
Radiated emission: Class A
Protection against electrical shock
IP20 per IEC for power circuit
Operating temperature
Open: -5 to 50 °C (23 to 122 °F)
Humidity
5...95% (noncondensing)
Storage and transportation temperature
-20
Steady state heat dissipation with control and fan power
97 W
Contact type
Auxiliary contacts 19/20 (Aux #1), 29/30 (Aux #2), 31/32 (Aux #3) and 33/34 (Aux #4)
Input ON-state current
20mA @ 120V AC/40mA @ 240V AC, 7.6mA @ 24V AC/DC for control circuit
Rated operational current
3A @ 120V AC, 1.5A @ 240V AC for auxiliary contacts
Upper line side cable size
2.5...95 mm2 (14...3 AWG) for line power terminals
Upper load side cable size
2.5...50 mm2 (14...1 AWG) for load power terminals
Lower load side cable size
0.8...2.5 mm2 (18...14 AWG) for power terminals
Lower line side cable size
0.8...2.5 mm2 (18...14 AWG) for power terminals
Input ON-state voltage, min
85V AC @ 19.2V DC/20.4V AC for control circuit
Input OFF-state voltage, max
50V AC @ 10V DC/12V AC for control circuit
Reset resistance
1600 ? ± 100 ? for PTC input ratings
Response resistance
3400 ? ± 150 ? for PTC input ratings
Short circuit trip resistance
25 ? ± 10 ? for PTC input ratings
Allen bradley power supply control module, min
1606-XLP50E @ 24V DC (-15%, +10%)
Tachometer input
0...5V DC @ 4.5V DC = 100% Speed
Cold resistance of PTC sensor chain, max
1500 ? for PTC input ratings
Transient time control module
500 ms @ 24V DC (-15%, +10%)
Inrush time control module
250 ms @ 24V DC (-15%, +10%)
Response time
800 ms for PTC input ratings
Voltage at PTC terminals (RPTC = 4 kΩ), max
<7.5 for PTC input ratings
Steady state watts control module
24 W @ 24V DC (-15%, +10%)
Transient watts control module
60 W @ 24V DC (-15%, +10%)
Voltage at PTC terminals (RPTC = open), max
30V for PTC input ratings
Inrush current control module
5A @ 24V DC (-15%, +10%)
Number of sensors, max
6 for PTC input ratings
Short circuit protection device performance (SCPD) type
Type 1
Integrated motor overload protection
Yes
Optional controller feature
SMB smart motor braking control: provides motor braking without additional equipment for applications that require the motor to stop quickly, braking current is adjustable from 0...400% of the motor’s full-load current rating
Standard available fault current, max
10kA @ 200...600V, maximum standard fuse 400 A for delta device opsal current rating
Standard controller feature
Status indication: stopped, starting, stopping, at speed, alarm and fault
Utilization category
MG 1 per UL/CSA/NEMA for power circuit
Type of contacts
Progmable NO/NC for auxiliary contacts
Type of control circuit
Electromagnetic relay for auxiliary contacts
Conventional thermal current (Ith)
AC/DC: 5 A for auxiliary contacts
Type of current
AC for auxiliary contacts
High capacity available fault current, max
70kA @ 600V, maximum current 200 A time delay Class J or Class L fuse for inside delta connected motors
Number of contacts
1 for auxiliary contacts
Short-circuit protection device list
Standard fuse, circuit breaker and high capacity time delay class CC/J/L
Input OFF-state current
<10 mA AC, <3 mA DC for control circuit @ input OFF-state voltage
Rated operational voltage
200...480V AC (-15%, +10%) per UL/CSA/NEMA for power circuit
Insulation voltage
Rated 500V per IEC for power circuit
Transient protection
Metal oxide varistors: 220 J (optional) for power circuit
Delta connected motor current
20.8...104A @ 500/575V AC, 3-phase
Line connected motor current
12...60A @ 500/575V AC, 3-phase
Dielectric withstand
2500V per IEC for power circuit
Rated impulse voltage
6000V per IEC for power circuit
Delta connected motor power, max
75Hp @ 460V AC, 60 Hz, 3-phase
Line connected motor power, max
50Hp @ 575V AC, 60 Hz, 3-phase
Operating frequency
50/60 Hz for power circuit
Repetitive peak inverse voltage rating
1400V per UL/CSA/NEMA for power circuit
DV/DT protection
RC snubber network for power circuit
Heatsink fan rating
20VA @ 110/120V AC or 220/240V AC
Transformer control module
75VA @ 100...240V AC (-15%, +10%)
Trip current rating
117% of motor FLC
Trip classes
10, 15, 20 and 30
Control options
Brake control
Controller type
Soft starter
Overload current for delta connected devices
20.8 A
Overload current for line connected devices
12 A
Rated control supply voltage at AC 60 Hz
100
Rated control supply voltage at AC 50 Hz
100
Rated operating voltage Ue
200
Voltage type for actuating
AC
With display
Yes
Product Family
SMC Flex
Controller Rating
60 A 10-40Hp @ 460V AC
Control Voltage
100...240V AC

Specifications may be subject to change without notice