Rockwell Automation 1756-IF8I

Selling Points

  • 11. High Resolution Conversion: The 1756-IF8I boasts a superior 24-bit conversion resolution, ensuring precise measurements in various industrial applications.;
  • 22. Isolated Channels: Each of the 8 input channels is isolated, providing a safe and reliable connection to your system, reducing the risk of electrical interference or damage.;
  • 33. Versatile Signal Support: This module supports both voltage and current signals, allowing it to interface with a wide range of transmitters and sensors, making it highly versatile.;
  • 44. Internal Loop Power: In sourcing current mode, the channel provides loop power, simplifying the setup and reducing the need for external power sources.;
  • 55. Enhanced Diagnostic Capabilities: The module includes overvoltage protection, data warnings, and process alerts, ensuring that any issues are quickly detected and addressed, minimizing downtime and improving overall system reliability.
Product Details
1756-IF8I
Rockwell Automation

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Dimension Unit
CM
Weight Unit
KG
Weight
0.365
Stock Status
STOCKED
Dimension Length
23.622
Dimension Width
18.034
Lead Time
5
Dimension Height
5.588
Quick Turnaround
false
Preferred Availability
true
Repairable
REPAIRABLE
Enclosure type rating
None (open-style)
IEC temperature code
T4
Isolation voltage
250V (continuous), reinforced insulation type, inputs to backplane, 250V (continuous), basic insulation type, input to input
Input impedance
Voltage mode: 1 G? approximately (powered), Voltage mode: 7500 ? approximately (unpowered), Current mode: 125 ? approximately
Slot width
1 None
Shock
Operating: 30 G, Non operating: 50 G
Vibration
2 G @ 10...500 Hz
RTB keying
User-defined mechanical
Nonoperating temperature
-40 °C
Radiated RF immunity
10 V/m with 1 kHz sine-wave 80% AM from 80...2000 MHz, 10 V/m with 200 Hz 50% pulse 100% AM @ 900 MHz, 10 V/m with 200 Hz 50% pulse 100% AM @ 1890 MHz, 3 V/m with 1 kHz sine-wave 80% AM from 2000...2700 MHz
Operating temperature
0 to 60 °C
Surge transient immunity
±2 kV line-earth (CM) on shielded signal ports
Conducted RF immunity
10V rms with 1 kHz sine wave 80% AM from 150 kHz...80 MHz on shielded signal ports
Relative humidity
5...95% noncondensing
EFT/B immunity
±4kV @ 5kHz on shielded signal ports
ESD immunity
6 kV contact discharges, 8 kV air discharges
Emissions
IEC 61000-6-4
North American temperature code
T4
Surrounding air temperature, max
60 °C
Sourcing current, max
Current limited <45 mA (IN_x/I/SRC to RTN_x)
Sourcing voltage, max
36V DC (open circuit)
Sourcing voltage, min
20V DC
Real-time channel sampling
True
Scaling to engineering units
True
Onboard data alarming
True
Suitable for safety functions
False
Open circuit detection time
5 s
Calibrated accuracy
0.05% @ 25°C (77 °F)
Wire size
0.33...2.1 mm2 (22...14 AWG) solid or stranded shielded copper wire rated at 90 °C (194 °F), or greater, 1.2 mm (3/64 in.) insulation maximum
Resolution
24 bit, ±10.5V (1.49 μV/count), 0...10.5V (1.49 μV/count), 0...5.25V (1.49 μV/count), 0...21 mA (2.99 nA/count)
Power dissipation
Voltage mode: 4.6 W (15.7 BTU/hr), Non-sourcing current mode: 5.1 W (17.4 BTU/hr), Sourcing current mode: 7.3 W (24.9 BTU/hr)
Inputs
Eight isolated channels - any combination of voltage or current mode
Current draw
200mA @ 5.1V, Voltage/Non-sourcing current mode: 150mA @ 24V, Sourcing current mode: 400mA @ 24V (In sourcing current mode, the channel provides loop power.)
Thermal dissipation
Voltage mode: 15.7 BTU/hr, Non-sourcing current mode: 17.4 BTU/hr, Sourcing current mode: 24.9 BTU/hr
Total backplane power
Voltage/Non-sourcing current mode: 4.6 W, Sourcing current mode: 10.6 W
Settling time
Notch Filter configuration dependent
Voltage and current ratings
Backplane: 5.1V DC 200mA @ 24V DC 400 mA, Input voltage: -10V to +10V @ 0V to 10V @ 0V to 5V, Input current: 0 mA to 20 mA, Output current: 0 mA to 20 mA
Module input scan time, min
1 ms
Normal mode noise rejection
80 dB @ 60 Hz
Common mode noise rejection
120 dB @ 50/60 Hz
Overvoltage protection
±30V DC maximum
Wire category
2 - on signal ports
Data format
IEEE 32-bit floating point
Input range
-10...10V, 0…10V @ 0...5V, 0...20 mA
Module conversion method
Sigma-Delta
Module error over full temperature range
0.1 %
Module keying
Electronic, software configurable
Channel bandwidth
Notch Filter configuration dependent
Type of electric connection
Screw-/spring clA connection
Analogue outputs configurable
False
Analogue inputs configurable
True
Output signal configurable
False
Output, voltage
False
Output, current
False
Input signal, configurable
True
Input, thermocouple
False
Input, resistance thermometer
False
Input, resistor
False
Input, voltage
True
Input, current
True

Specifications may be subject to change without notice