  • 11. Flexible Output Configuration: The 1756-OX8I offers a mixed output configuration, including both Normally Closed (NC) and Normally Open (NO) contacts, providing flexibility in handling different output devices.;
  • 22. Reliable Performance: Designed for the ControlLogix platform, this module ensures reliable performance in industrial automation applications, minimizing downtime and maximizing efficiency.;
  • 33. Wide Voltage Compatibility: The module operates within a wide voltage range of 10-265 Volts AC and 5-150 Volts DC, making it compatible with various industrial power supplies.;
  • 44. High Isolation Voltage: With an isolation voltage of 250V (continuous), the 1756-OX8I provides robust electrical isolation between outputs and the backplane, ensuring safe operation in harsh environments.;
  • 55. Efficient Contact Life: The module features an expected contact life of 300 kHz resistive and 100 kHz inductive, ensuring long-lasting performance and reducing the need for frequent replacements.
Product Details
1756-OX8I
Rockwell Automation

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Dimension Unit
CM
Weight Unit
KG
Weight
0.363
Stock Status
STOCKED
Dimension Length
22.2
Dimension Width
18.009
Lead Time
5
Dimension Height
5.41
Quick Turnaround
false
Preferred Availability
true
Repairable
REPAIRABLE
Enclosure type
None (open-style)
Operating voltage
5...125V DC @ 10...240V AC
Output delay time
OFF to ON: 13 ms maximum, ON to OFF: 13 ms maximum
Load current per point, min
10 mA
Off-state leakage current per point, max
0 mA
Oscillatory surge withstand
IEEE C37.90.1: 3kV
Nonoperating temperature
-40 °C
Radiated RF immunity
10 V/m with 1 kHz sine-wave 80% AM from 80...2000 MHz, 10 V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz, 10 V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz, 3 V/m with 1 kHz sine-wave 80% AM from 2000...2700 MHz
Surge transient immunity
±1 kV line-line (DM) and ±2 kV line-earth (CM) on signal ports
Operating temperature
0 to 60 °C
EFT/B immunity
±4kV @ 5kHz on signal ports
Conducted RF immunity
10V rms with 1 kHz sine-wave 80% AM from 150 kHz...80 MHz
Relative humidity
5...95% noncondensing
ESD immunity
6 kV contact discharges, 8 kV air discharges
Emissions
IEC 61000-6-4
North American temperature code
T4A
Surrounding air temperature, max
60 °C
Vibration
2 G @ 10...500 Hz
Shock
Operating: 30 G, Non operating: 50 G
RTB keying
User-defined mechanical
Slot width
1
States in program mode per point
Hold last state, On or Off (Off is default)
States in fault mode per point
Hold last state, On or Off (Off is default)
Switching frequency, max
1 ops/3 s (0.3 Hz at rated load)
Initial contact resistance, max
100 m? @ 6V @ 1A
Pilot duty
C300, R150
Short-circuit protection, outputs available
No
Redundancy
No
Fusing
Not protected. A fused IFM is recommended to help protect outputs
Wire category
Wire category: 1
Isolation voltage
250V (continuous), basic insulation type, outputs-to-backplane, and output-to-output
Contact current rating
1A @ 5...30V DC, 0.5A @ 48V DC, 0.22A @ 125V DC, 1.5A @ 120V AC, 50/60 Hz, 0.75A @ 240V AC, 50/60 Hz
Power dissipation, max
3.1 W @ 60 °C (140 °F)
Scheduled outputs
Synchronization within 16.7 s max, reference to the coordinated system time
Outputs
8 N.O., 8 N.C. individually isolated (two points per group)
Module keying
Electronic, software configurable
Expected contact life
300 kHz, resistive, 100 kHz, inductive
Current draw
100mA @ 5.1V, 100mA @ 24V
Thermal dissipation
10.57 btu/h
Total backplane power
2.9 W
Bounce time, mean
1.2 μs
Type of electric connection
Screw connection
Type of digital output
Relay
Type of voltage (input voltage)
DC
Voltage type of supply voltage
DC
Digital outputs configurable
No
Digital inputs configurable
No
Suitable for safety functions
No
Number Of Channels
8
Isolation
250 V continuous between outputs

Specifications may be subject to change without notice