Product Model
140ACO02000

Selling Points
- 1The module offers an absolute accuracy error of +/- 0.20% of full scale at 25°C, ensuring precise output signals.
- 2It provides 750 V DC isolation between channels and 500 V AC isolation at 47 to 63 Hz frequency, ensuring signal integrity and safety.
- 3The module updates in just 3 ms and achieves +/- 0.1% precision in under a millisecond, making it ideal for real-time applications.
- 4Compatible with external power sources ranging from 12 to 30 V, offering flexibility in installation and power management.
- 5With a maximum power dissipation of <= 5.3 W, it ensures efficient energy utilization within the system.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Range of Product | Modicon Quantum automation platform | Product or Component Type | Analogue output module |
Analogue output number | 4 | Addressing requirement | 4 output words |
Loop voltage | 12…30 V DC | Maximum voltage drop | <30 V 20 mA |
Analogue output range | 4...20 mA 0...4096 counts, 12 bits bipolar current | Absolute accuracy error | +/- 0.20 % of full scale 77 °F (25 °C) |
Linearity | +/- 1 LSB | Accuracy drift according to temperature | +/- 0.004 % of full scale/°C<br />+/- 0.007 % of full scale/°C maximum |
Isolation between channels | 500 V 47...63 Hz AC<br />750 V for 1 minute DC | Update time | 3 ms |
Setting time | 900 µs to +/- 0.1 % of the final value | Fault type | Open circuit 4...20 mA |
Bus current requirement | 480 mA | Maximum power dissipation in W | 5.3 W |
External power requirement | 12...30 V | marking | CE |
Local signalling | for bus communication is present (Active) 1 LED (green)<br /> for external fault 1 LED (red)<br /> for channel is turned on 4 LEDs (green)<br /> for channel fault 4 LEDs (red) | Module format | Standard |
Net Weight | 0.7 lb(US) (0.3 kg) | Product Certifications | FM Class 1 Division 2<br />cUL |
Standards | CSA C22.2 No 142<br />UL 508 | Resistance to electromagnetic fields | 9.1 V/m (10 V/m) 80…2000 MHz IEC 801-3 |
Ambient Air Temperature for Operation | 32…140 °F (0…60 °C) | Ambient Air Temperature for Storage | -40…185 °F (-40…85 °C) |
Relative Humidity | 95 % without condensation | Operating altitude | <= 16404.2 ft (5000 m) |
Specifications may be subject to change without notice