Product Model

140ACO02000C

In Stock
Last updated: 2025/4/16
schneider 140ACO02000C

Selling Points

  • 1High Precision Output: Offers an absolute accuracy error of +/- 0.20% of full scale at 25°C.
  • 2Safety Features: Provides 750 V DC isolation between channels and 500 V AC isolation for enhanced safety.
  • 3Fast Response Time: Updates in just 3 ms and achieves +/- 0.1% precision in under a millisecond.
  • 4Versatile Power Supply: Operates within a loop voltage range of 12 to 30 V DC, ensuring compatibility with various power sources.
  • 5Efficient Energy Use: Consumes a maximum power dissipation of <= 5.3 W, making it energy-efficient for industrial use.
Product Details
140ACO02000C
schneider

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Range of Product
Modicon Quantum automation platform
Product or Component Type
Analogue output module
Analogue output number
4
Addressing requirement
4 output words
Loop voltage
12…30 V DC
Maximum voltage drop
<30 V 20 mA
Analogue output range
4...20 mA 0...4096 counts, 12 bits bipolar current
Absolute accuracy error
+/- 0.20 % of full scale 77 °F (25 °C)
Linearity
+/- 1 LSB
Accuracy drift according to temperature
+/- 0.004 % of full scale/°C<br />+/- 0.007 % of full scale/°C maximum
Isolation between channels
500 V 47...63 Hz AC<br />750 V for 1 minute DC
Update time
3 ms
Setting time
900 µs to +/- 0.1 % of the final value
Fault type
Open circuit 4...20 mA
Bus current requirement
480 mA
Maximum power dissipation in W
5.3 W
External power requirement
12...30 V
marking
CE
Local signalling
for bus communication is present (Active) 1 LED (green)<br /> for external fault 1 LED (red)<br /> for channel is turned on 4 LEDs (green)<br /> for channel fault 4 LEDs (red)
Module format
Standard
Net Weight
0.7 lb(US) (0.3 kg)
Protective treatment
Conformal coating Humiseal 1A33
Product Certifications
cUL<br />FM Class 1 Division 2
Standards
CSA C22.2 No 142<br />UL 508
Resistance to electromagnetic fields
9.1 V/m (10 V/m) 80…2000 MHz IEC 801-3
Ambient Air Temperature for Operation
32…140 °F (0…60 °C)
Ambient Air Temperature for Storage
-40…185 °F (-40…85 °C)
Relative Humidity
95 % without condensation
Operating altitude
<= 16404.2 ft (5000 m)

Specifications may be subject to change without notice