Product Model
140ACO13000C

Selling Points
- 1High Accuracy: Offers exceptional accuracy with an absolute accuracy error of +/- 0.2% of full scale at 25°C.
- 2Versatile Voltage Range: Compatible with a wide range of devices and systems, operating within 6 to 30V DC.
- 3Comprehensive Fault Monitoring: Equipped with local signaling indicators for channel faults, activation, and bus communication status.
- 4Fast Update Time: Ensures rapid response to control signals with an update time of just 5 ms.
- 5Energy-Efficient Design: Features low power dissipation of 5 W, ensuring efficient power management in industrial automation systems.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Range of Product | Modicon Quantum automation platform | Product or Component Type | Analogue output module |
Analogue output number | 8 | Addressing requirement | 8 output words |
Loop voltage | 6…30 V DC | Maximum voltage drop | <30 V 25 mA |
Analogue output range | 0...20 mA 0...20000 counts<br />0...25 mA 0...25000 counts<br />4...20 mA 0...16000 counts<br />4...20 mA 0...4095 counts | Absolute accuracy error | +/- 0.2 % of full scale 77 °F (25 °C) |
Linearity | +/- 12 µA 4...20 mA 0...4095 counts<br />+/- 4 µA 0...20 mA 0...20000 counts<br />+/- 4 µA 0...25 mA 0...25000 counts<br />+/- 4 µA 4...20 mA 0...16000 counts | Accuracy drift according to temperature | 0.004 % of full scale/°C typical<br />0.007 % of full scale/°C maximum |
Isolation between channels and bus | 1780 V for 1 minute AC | Update time | 5 ms |
Setting time | 1.6 ms to 5% of the final value<br />3.2 ms to +/-0.1% of the final value | Fault type | Open circuit 4...20 mA |
Bus current requirement | 550 mA | Maximum power dissipation in W | 5 W |
External power requirement | 6...30 V | marking | CE |
Local signalling | for bus communication is present (Active) 1 LED (green)<br /> for external fault 1 LED (red)<br /> for channel is turned on 8 LEDs (green)<br /> for channel fault 8 LEDs (red) | Module format | Standard |
Net Weight | 0.7 lb(US) (0.3 kg) | Protective treatment | Conformal coating Humiseal 1A33 |
Product Certifications | cUL<br />FM Class 1 Division 2 | Standards | CSA C22.2 No 142<br />UL 508 |
Resistance to electromagnetic fields | 9.1 V/m (10 V/m) 80…2000 MHz IEC 801-3 | Ambient Air Temperature for Operation | 32…140 °F (0…60 °C) |
Ambient Air Temperature for Storage | -40…185 °F (-40…85 °C) | Relative Humidity | 95 % without condensation |
Operating altitude | <= 16404.2 ft (5000 m) |
Specifications may be subject to change without notice