Product Model

140AII33010

In Stock
Last updated: 2025/4/16
schneider 140AII33010

Selling Points

  • 1Robust Noise Elimination: Equipped with a single low-pass input filter, this module effectively eliminates noise for accurate analog signal acquisition.
  • 2Flexible Installation: Compatible with Zone 20, 21, or 22 hazardous areas, offering flexibility in installation while maintaining safety compliance.
  • 3Comprehensive Data Acquisition: Features eight analog input channels for simultaneous monitoring of multiple signals, enhancing data acquisition capabilities.
  • 4Multiple Input Ranges: Supports various input ranges including 0-20 mA, 0-25 mA, and 4-20 mA with tailored input resolutions for precise measurement.
  • 5Fault Detection and Protection: Includes fault detection for broken wire conditions in 4-20 mA circuits and internal overcurrent protection up to 25 mA for robust system reliability.
Product Details
140AII33010
schneider

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Range of Product
Modicon Quantum automation platform
Product or Component Type
Intrinsically safe current input module
Software designation
Concept V2.2 and above<br />ProWORX<br />Unity Pro
Type of filter
Single low pass input filter -3 dB 15 Hz +/- 20 %
Product destination
In conjunction with products for zone 20, 21 or 22
Analogue input number
8
Analogue input range
0...20 mA<br />0...25 mA<br />4...20 mA
Analogue input resolution
0...16000 counts 4...20 mA<br />0...20000 counts 0...20 mA<br />0...25000 counts 0...25 mA<br />0...4095 counts 4...20 mA
Absolute maximum input
25 mA internally limited
Input impedance
100 Ohm +/- 0.1 %
Absolute accuracy error
+/- 0.05 % typical of full scale 77 °F (25 °C)<br />+/- 0.1 % of full scale maximum 77 °F (25 °C)
Accuracy drift according to temperature
+/- 0.0025 % typical of full scale/°C<br />0.005 % maximum of full scale/°C
Linearity error
0.003 % of full scale
Common mode rejection
> 100 dB 50/60 Hz
Update time
750 ms
Isolation between channels and bus
2500 V for 1 minute DC<br />1780 V 47...63 Hz AC
Fault type
Broken wire 4...20 mA
Power dissipation in W
7.5 W
Hot swapping fallback
Not allowed per intrinsic safety standards
Protection Type
Internal fuse
marking
CE<br />II1 G/D-EEx ia IIC
Bus current requirement
1500 mA
Module format
Standard
Net Weight
0.7 lb(US) (0.3 kg)
Standards
Directive ATEX 94/9/EC<br />EN 50039<br />CSA C22.2 No 142<br />EN 50014<br />EN 50020<br />EN 50284<br />EN 50281-1-1<br />UL 508
Dust zone
Outside zone
Product Certifications
GOST<br />C-tick<br />FM Class 1 Division 2<br />SIRA 02ATEX2345X
Resistance to electrostatic discharge
4 kV contact IEC 801-2<br />8 kV on air IEC 801-2
Resistance to electromagnetic fields
9.1 V/m (10 V/m) 80…2000 MHz IEC 801-3
Ambient Air Temperature for Operation
32…140 °F (0…60 °C)
Ambient Air Temperature for Storage
-40…185 °F (-40…85 °C)
Relative Humidity
95 % without condensation
Operating altitude
<= 16404.2 ft (5000 m)

Specifications may be subject to change without notice