Product Model
140AMM09000

Selling Points
- 14 channels support various input types, including unipolar voltage and current.
- 2500 V AC and 750 V DC isolation ensure secure signal transmission.
- 3Local signaling via LEDs provides real-time bus communication status and channel diagnostics.
- 4Operates between 32°F to 140°F (0°C to 60°C), suitable for diverse industrial environments.
- 5Meets FM Class 1 Division 2 and UL 508 standards for industrial safety compliance.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Range of Product | Modicon Quantum automation platform | Product or Component Type | Input/output analog module |
Type of filter | Single pole low pass - 3 dB at 21 Hz +/- 20 % input circuit | I/O modularity | 6 channels |
Addressing requirement | 2 output words<br />5 input words | Analogue input number | 4 |
Analogue input type | Bipolar current +/- 20 mA 15 bits DC<br />Bipolar voltage +/- 10 V 16 bits DC<br />Bipolar voltage +/- 5 V 15 bits DC<br />Unipolar current 0...20 mA 15 bits DC<br />Unipolar offset current 4...20 mA 14 bits DC<br />Unipolar offset voltage 1...5 V 14 bits DC<br />Unipolar voltage 0...10 V 16 bits DC<br />Unipolar voltage 0...5 V 15 bits DC | Absolute maximum input | +/- 25 mA current<br />+/- 50 V voltage |
Input impedance | > 10 MOhm voltage<br />> 250 Ohm current | Offset | +/- 0.0014 % of full scale maximum/°C 0...60 °C input circuit |
Gain shift | +/- 0.002 of full scale maximum 0...60 °C input circuit | Common mode rejection | > 80 dB 50/60 Hz input circuit |
Analogue output number | 2 | Analogue output range | 4...20 mA |
Analogue output resolution | 12 bits | Loop voltage | 0…60 V DC with external resistance output circuit<br />7…30 V DC output circuit |
Maximum voltage drop | <30 V DC 20 mA | Setting time | 900 µs to +/- 0.1 % of the final value output circuit |
External power requirement | 7...30 V output circuit | Absolute accuracy error | +/- 0.004 % of full scale 32…140 °F (0…60 °C) output circuit<br />+/- 0.007 %/°C of full scale maximum 32…140 °F (0…60 °C) output circuit<br />+/- 0.03 % 77 °F (25 °C) input circuit<br />+/- 0.05 % of full scale maximum 77 °F (25 °C) input circuit<br />+/- 0.20 % of full scale 77 °F (25 °C) output circuit |
Linearity | 2.4 % over and under range voltage<br />2.4 % over range, and - 9.6 % under range current<br />Monotonic +/- 1 LSB input<br />Monotonic +/- 1 LSB output | Update time | 15 ms output circuit<br />320 ms input circuit |
Fault type | Open circuit input/output circuit<br />Overtacking scale (unipolar) input circuit<br />Status byte output circuit | Isolation between channels | 500 V AC for 1 minute<br />750 V DC for 1 minute |
Isolation between channels and bus | 500 V AC for 1 minute<br />750 V DC for 1 minute | Isolation between input channel and output channel | 500 V for 1 minute<br />750 V for 1 minute |
marking | CE | Local signalling | for bus communication is present (Active) 1 LED (green)<br /> for external fault 1 LED (red)<br /> for channel is turned on 6 LEDs (green)<br /> for channel fault 6 LEDs (red) |
Bus current requirement | 350 mA | Module format | Standard |
Net Weight | 0.7 lb(US) (0.3 kg) | Product Certifications | FM Class 1 Division 2<br />C-Tick.1 |
Standards | UL 508<br />CSA C22.2 No 142 | Resistance to electromagnetic fields | 9.1 V/m (10 V/m) 80…2000 MHz IEC 801-3 |
Ambient Air Temperature for Operation | 32…140 °F (0…60 °C) | Ambient Air Temperature for Storage | -40…185 °F (-40…85 °C) |
Relative Humidity | 95 % without condensation | Operating altitude | <= 16404.2 ft (5000 m) |
Specifications may be subject to change without notice