Product Model
140ARI03010

Selling Points
- 1Supports various temperature probes including Pt 100, Pt 200, Ni 100, and Ni 200.
- 2Offers high-resolution analog input with 13-bit resolution for accurate data acquisition.
- 3Provides robust isolation capabilities up to 1780 V AC and 2500 V DC for signal integrity.
- 4Features local signaling indicators for quick fault detection and troubleshooting.
- 5Designed for seamless integration into industrial control systems with a standard module format.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Range of Product | Modicon Quantum automation platform | Product or Component Type | Analogue input module |
Analogue input number | 8 | input type | Differential |
Addressing requirement | 9 input words | Analogue input type | Temperature probe - 100...450 °C Pt 100, Pt 200, Pt 500, Pt 1000<br />Temperature probe - 200...850 °C Pt 100, Pt 200, Pt 500, Pt 1000<br />Temperature probe - 60...180 °C Ni 100, Ni 200, Ni 500, Ni 1000<br />Temperature probe 0.5 mA Ni 100, Ni 200, Ni 500, Ni 1000<br />Temperature probe 2.5 mA Pt 100, Pt 200, Ni 100, Ni 200 |
Analogue input resolution | 13 bits | Input impedance | >= 10 MOhm |
Absolute accuracy error | 0.1 °C | Linearity error | +/- 0.01 % full scale<br />+/- 0.5 °C |
Accuracy drift according to temperature | +/- 0.5 °C 77 °F (25 °C)<br />+/- 0.9 °C 32…140 °F (0…60 °C) | Isolation between channels and bus | 1780 V AC 47...63 Hz 60 s<br />2500 V DC 60 s |
Isolation between channels | 300 Vrms AC | Update time | 1200 ms 3 wires<br />640 ms 2 wires/4 wires |
Fault type | Broken wire<br />Overtacking scale | marking | CE |
Local signalling | for bus communication is present (Active) 1 LED (green)<br /> for external fault 1 LED (red)<br /> for channel is turned on 8 LEDs (green)<br /> for channel fault 8 LEDs (red) | Bus current requirement | 200 mA |
Power dissipation in W | 1 W | Module format | Standard |
Net Weight | 0.7 lb(US) (0.3 kg) | Standards | UL 508<br />CSA C22.2 No 142 |
Product Certifications | FM Class 1 Division 2<br />cUL | Resistance to electrostatic discharge | 4 kV contact IEC 801-2<br />8 kV on air IEC 801-2 |
Resistance to electromagnetic fields | 9.1 V/m (10 V/m) 80…1000 MHz IEC 801-3 | Ambient Air Temperature for Operation | 32…140 °F (0…60 °C) |
Ambient Air Temperature for Storage | -40…185 °F (-40…85 °C) | Relative Humidity | 95 % without condensation |
Operating altitude | <= 16404.2 ft (5000 m) |
Specifications may be subject to change without notice