Product Model

140AVI03000C

In Stock
Last updated: 2025/4/17
schneider 140AVI03000C

Selling Points

  • 1The 140AVI03000C boasts an impressive accuracy of +/- 0.03 percent and a linearity error of +/- 0.008%.
  • 2With a power consumption of 2.2 W, this module is effective and efficient for various industrial scenarios.
  • 3Supports unipolar voltage (0...5 V, 0...10 V), unipolar current (0...20 mA), and bipolar voltage (+/- 5 V, +/- 10 V) inputs.
  • 4Ensures reliable performance even in demanding environments with a low accuracy drift of just 0.0015 percent.
  • 5Equipped with 9 LEDs for quick diagnosis of potential issues, including bus communication and channel activation indicators.
Product Details
140AVI03000C
schneider

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Range of Product
Modicon Quantum automation platform
Product or Component Type
Analogue input module
Type of filter
Single pole low pass - 3 dB at 847 Hz +/- 20 %
Analogue input number
8
input type
Differential
Addressing requirement
9 input words
Analogue input type
Bipolar current 20 mA<br />Bipolar voltage +/- 10 V<br />Bipolar voltage +/- 5 V<br />Unipolar current 0...20 mA<br />Unipolar voltage 0...10 V<br />Unipolar voltage 0...5 V
Analogue input resolution
16 bits +/- 10 V<br />16 bits +/- 5 V<br />16 bits 0...10 V<br />16 bits 0...20 mA<br />16 bits 0...5 V<br />16 bits 20 mA
Linear measuring range
(input range) x 1.024 V<br />(input range) x 1.024 mA
Absolute maximum input
50 V DC<br />25 mA
Input impedance
> 20 Ohm voltage<br />250 MOhm +/- 0.03 %
Absolute accuracy error
+/- 0.03 %<br />+/- 0.05 % of full scale maximum
Linearity error
+/- 0.008 %
Accuracy drift according to temperature
+/- 0.0015 % of full scale/°C<br /><= 0.004 % of full scale /°C
Common mode rejection
> - 80 dB 60 Hz
Isolation between channels and bus
500 Vrms AC 60 s<br />750 V DC
Isolation between channels
135 Vrms AC<br />200 V DC
Update time
10 ms
Fault type
Broken wire 4...20 mA<br />Overtacking scale 1...5 V
marking
CE
Local signalling
for bus communication is present (Active) 1 LED (green)<br /> for external fault 1 LED (red)<br /> for channel is turned on 8 LEDs (green)<br /> for channel fault 8 LEDs (red)
Bus current requirement
280 mA
Power dissipation in W
2.2 W
Module format
Standard
Net Weight
0.7 lb(US) (0.3 kg)
Protective treatment
Conformal coating Humiseal 1A33
Standards
UL 508<br />CSA C22.2 No 142
Product Certifications
FM Class 1 Division 2<br />cUL
Resistance to electrostatic discharge
4 kV contact IEC 801-2<br />8 kV on air IEC 801-2
Resistance to electromagnetic fields
9.1 V/m (10 V/m) 80…1000 MHz IEC 801-3
Ambient Air Temperature for Operation
32…140 °F (0…60 °C)
Ambient Air Temperature for Storage
-40…185 °F (-40…85 °C)
Relative Humidity
95 % without condensation
Operating altitude
<= 16404.2 ft (5000 m)

Specifications may be subject to change without notice