Product Model

140CPS11420C

In Stock
Last updated: 2025/4/27
schneider 140CPS11420C

Selling Points

  • 1The 140CPS11420C power supply module provides stable power output with internal overvoltage and overload protections.
  • 2Available in both summable and standalone configurations, it adapts to various industrial control system needs.
  • 3Supports input voltages of 115 V AC (93-132 V) and 230 V AC (170-276 V), ensuring compatibility with different power systems.
  • 4Features low harmonic distortion (<= 10% of fundamental RMS value) for clean power delivery and reduced interference.
  • 5Meets CE standards and offers resistance to electrostatic discharge and electromagnetic fields, ensuring safety and reliability in industrial applications.
Product Details
140CPS11420C
schneider

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Range of Product
Modicon Quantum automation platform
Product or Component Type
Power supply module
power supply type
Summable or standalone
Input voltage
115 V 93...132 V) AC 47…63 Hz<br />230 V 170...276 V) AC
Input current
1300 mA 115 V<br />750 mA 230 V
Inrush current
19 A 230 V<br />38 A 115 V
Rated power in VA
130 VA
Associated fuse rating
2 A, slow-blow
Harmonic distortion
<= 10 % of fundamental rms value
Output voltage
5.1 V DC
Power supply output current
11 A 140 °F (60 °C) standalone<br />20 A 140 °F (60 °C) summable
Output overvoltage protection
Internal
Output overload protection
Internal
Power dissipation
6 + (1.5 x Iout) where Iout is in A
Alarm output
1 NC 6 A 220 V power supply fault
Local signalling
for power (PWR OK) 1 LED (green)
marking
CE
Module format
Standard
Net Weight
1.43 lb(US) (0.65 kg)
Protective treatment
Conformal coating Humiseal 1A33
Standards
CSA C22.2 No 142<br />UL 508
Product Certifications
cUL
Resistance to electrostatic discharge
4 kV contact IEC 801-2<br />8 kV on air IEC 801-2
Resistance to electromagnetic fields
9.1 V/m (10 V/m) 80…2000 MHz IEC 801-3
Ambient Air Temperature for Operation
32…140 °F (0…60 °C)
Ambient Air Temperature for Storage
-40…185 °F (-40…85 °C)
Relative Humidity
95 % without condensation
Operating altitude
<= 16404.2 ft (5000 m)

Specifications may be subject to change without notice