Product Model

140CPS52400C

In Stock
Last updated: 2025/4/27
schneider 140CPS52400C

Selling Points

  • 1Ensures continuous operation even if one power source fails.
  • 2Operates on 100-150 V DC, providing flexibility in varying power conditions.
  • 3Includes overvoltage and overload protection to safeguard against power surges.
  • 4Calculated using 6 + (1.5 x Iout), minimizing energy loss and reducing operational costs.
  • 5Meets European safety and environmental standards, ensuring high-quality performance in industrial applications.
Product Details
140CPS52400C
schneider

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Range of Product
Modicon Quantum automation platform
Product or Component Type
Power supply module
power supply type
Redundant
Input voltage
125 V 100...150 V) DC
Input current
500 mA 125 V
Inrush current
28 A 125 V
Maximum input power interruption
1 ms
Associated fuse rating
2 A, slow-blow
Output voltage
5.1 V DC
Power supply output current
8 A redundant
Output overvoltage protection
Internal
Output overload protection
Internal
Power dissipation
6 + (1.5 x Iout) where Iout is in A
Local signalling
for power (PWR OK) 1 LED (green)
marking
CE
Module format
Standard
Net Weight
1.43 lb(US) (0.65 kg)
Protective treatment
Conformal coating Humiseal 1A33
Standards
CSA C22.2 No 142<br />UL 508
Product Certifications
cUL<br />FM Class 1 Division 2
Resistance to electrostatic discharge
4 kV contact IEC 801-2<br />8 kV on air IEC 801-2
Resistance to electromagnetic fields
9.1 V/m (10 V/m) 80…2000 MHz IEC 801-3
Ambient Air Temperature for Operation
32…140 °F (0…60 °C)
Ambient Air Temperature for Storage
-40…185 °F (-40…85 °C)
Relative Humidity
95 % without condensation
Operating altitude
<= 16404.2 ft (5000 m)

Specifications may be subject to change without notice