Product Model

140CPU53414BC

In Stock
Last updated: 2025/4/27
schneider 140CPU53414BC

Selling Points

  • 1Advanced Processing: Equipped with an 80486 processor running at 100 MHz for rapid execution of control algorithms and data processing.
  • 2Efficient Memory Management: Offers 2972 kB of internal RAM for storing program code, data, and configuration settings.
  • 3Precise Timing and Monitoring: Includes a watchdog timer of 250 ms and clock drift of +/-8 s/day at 0...60 °C for accurate control and system integrity.
  • 4Robust Connectivity: Supports flexible I/O configurations with 64 I/64 O remote and 64 I/64 O max local, ensuring seamless communication across networks.
  • 5Reliable Operation: Features a battery backup system with a lithium battery type, providing long-term reliability and uninterrupted operation during power loss.
Product Details
140CPU53414BC
schneider

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Range of Product
Modicon Quantum automation platform
Product or Component Type
Processor
Software name
ProWORX 32<br />Concept
Processor name
80486
Mathematical coprocessor
With
Clock frequency
100 MHz
Memory description
Internal RAM 2972 kB
Exact time for 1 Kinstruction
0.1...0.5 ms LL984
Watchdog timer
250 ms
Clock drift
+/-8 s/day 32…140 °F (0…60 °C)
I/O words
30 I/32 O distributed<br />64 I/64 O max local<br />64 I/64 O remote
I/O words/network
500 I/500 O distributed
Drops/network
63 distributed
Number of drops
31 remote
Number of network
2 remote<br />3 distributed
Battery type
Lithium 10 µA 420 µA
Battery Capacity
1.2 Ah
Battery Life
10 year(s)
Switch Function
Key switch
marking
CE
Bus current requirement
1250 mA
Module format
Standard
Net Weight
1.87 lb(US) (0.85 kg)
Protective treatment
Conformal coating Humiseal 1A33
Product Certifications
FM Class 1 Division 2<br />cUL
Standards
UL 508<br />CSA C22.2 No 142
Resistance to electrostatic discharge
4 kV contact IEC 801-2<br />8 kV on air IEC 801-2
Resistance to electromagnetic fields
9.1 V/m (10 V/m) 80…2000 MHz IEC 801-3
Ambient Air Temperature for Operation
32…140 °F (0…60 °C)
Ambient Air Temperature for Storage
-40…185 °F (-40…85 °C)
Relative Humidity
95 % without condensation
Operating altitude
<= 16404.2 ft (5000 m)

Specifications may be subject to change without notice