Product Model
140DAI35300

Selling Points
- 1High-Performance VAC Discrete Input Module: Designed for industrial automation systems, this module offers advanced features and functionality.
- 232 Individual Inputs: Organized into four groups, each with high isolation (1780 Vrms for 1 minute), ensuring robust data handling.
- 3Seamless Integration: Compatible with Schneider Electric software solutions like ProWORX 32, Concept, and Unity Pro.
- 4Advanced Signaling Indicators: Includes 32 green LEDs for input status monitoring and a red LED for external fault detection.
- 5Reliable Operation: Withstands overvoltage conditions up to 32 V for 10 seconds and 50 V for one cycle, ensuring operational resilience.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Range of Product | Modicon Quantum automation platform | Product or Component Type | VAC discrete input modules |
Software name | ProWORX 32<br />Concept<br />Unity Pro | Discrete input number | 32 |
Group of channels | 4 | Addressing requirement | 2 input words |
Discrete input voltage | 24 V AC | Input current | 11.1 mA 57...63 Hz<br />13.2 mA 47...53 Hz |
Voltage state 1 guaranteed | 12...30 V AC 57...63 Hz<br />14...30 V AC 47...53 Hz | Voltage state 0 guaranteed | 0...5 V 57...63 Hz<br />0...5 V 47...53 Hz |
Input impedance | 2600 Ohm capacitive 57...63 Hz<br />3100 Ohm capacitive 47...53 Hz | Network frequency limits | 47…63 Hz |
Maximum leakage current | 1.9 mA | Absolute maximum input | 30 V continuous<br />32 V 10 s<br />50 V 1 cycle |
Response Time | 4.9...0.75 ms x line cycle Off-On<br />7.3...12.3 ms On-Off | Isolation between group | 1780 Vrms for 1 minute |
Isolation between group and bus | 1780 Vrms for 1 minute | Bus current requirement | 250 mA |
Maximum power dissipation in W | 10.9 W | Local signalling | for bus communication is present (Active) 1 LED (green)<br /> for external fault detected (F) 1 LED (red)<br /> for input status 32 LEDs (green) |
marking | CE | Module format | Standard |
Net Weight | 0.75 lb(US) (0.34 kg) | Standards | UL 508<br />CSA C22.2 No 142 |
Product Certifications | FM Class 1 Division 2<br />cUL | Resistance to electrostatic discharge | 4 kV contact IEC 801-2<br />8 kV on air IEC 801-2 |
Resistance to electromagnetic fields | 9.1 V/m (10 V/m) 80…2000 MHz IEC 801-3 | Ambient Air Temperature for Operation | 32…140 °F (0…60 °C) |
Ambient Air Temperature for Storage | -40…185 °F (-40…85 °C) | Relative Humidity | 95 % without condensation |
Operating altitude | <= 16404.2 ft (5000 m) |
Specifications may be subject to change without notice