Product Model
140DAI35300C

Selling Points
- 1High-Performance VAC Discrete Input Module: The 140DAI35300C is designed for 24 V AC inputs and operates efficiently within a frequency range of 47 to 63 Hz.
- 2Robust Isolation and Safety Features: The module features isolation of up to 1780 Vrms for one minute between groups and between groups and the bus, ensuring robust protection against electrical faults.
- 3Advanced Software Compatibility: Compatible with ProWORX 32, Concept, and Unity Pro software solutions, providing seamless integration into various automation architectures.
- 4Detailed Input Status Monitoring: Equipped with 32 green LEDs indicating the status of each individual input channel, simplifying monitoring and troubleshooting.
- 5Quick Response Time and Low Power Consumption: The module offers quick response times ranging from 4.9 to 0.75 ms per line cycle for Off-On signals and 7.3 to 12.3 ms for On-Off transitions, while dissipating up to 10.9 W of power.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Range of Product | Modicon Quantum automation platform | Product or Component Type | VAC discrete input modules |
Software name | ProWORX 32<br />Unity Pro<br />Concept | Discrete input number | 32 |
Group of channels | 4 | Addressing requirement | 2 input words |
Discrete input voltage | 24 V AC | Input current | 11.1 mA 57...63 Hz<br />13.2 mA 47...53 Hz |
Voltage state 1 guaranteed | 12...30 V AC 57...63 Hz<br />14...30 V AC 47...53 Hz | Voltage state 0 guaranteed | 0...5 V 57...63 Hz<br />0...5 V 47...53 Hz |
Input impedance | 2600 Ohm capacitive 57...63 Hz<br />3100 Ohm capacitive 47...53 Hz | Network frequency limits | 47…63 Hz |
Maximum leakage current | 1.9 mA | Absolute maximum input | 30 V continuous<br />32 V 10 s<br />50 V 1 cycle |
Response Time | 4.9...0.75 ms x line cycle Off-On<br />7.3...12.3 ms On-Off | Isolation between group | 1780 Vrms for 1 minute |
Isolation between group and bus | 1780 Vrms for 1 minute | Bus current requirement | 250 mA |
Maximum power dissipation in W | 10.9 W | Local signalling | for bus communication is present (Active) 1 LED (green)<br /> for external fault detected (F) 1 LED (red)<br /> for input status 32 LEDs (green) |
marking | CE | Module format | Standard |
Net Weight | 0.75 lb(US) (0.34 kg) | Protective treatment | Conformal coating Humiseal 1A33 |
Standards | CSA C22.2 No 142<br />UL 508 | Product Certifications | FM Class 1 Division 2<br />cUL |
Resistance to electrostatic discharge | 4 kV contact IEC 801-2<br />8 kV on air IEC 801-2 | Resistance to electromagnetic fields | 9.1 V/m (10 V/m) 80…2000 MHz IEC 801-3 |
Ambient Air Temperature for Operation | 32…140 °F (0…60 °C) | Ambient Air Temperature for Storage | -40…185 °F (-40…85 °C) |
Relative Humidity | 95 % without condensation | Operating altitude | <= 16404.2 ft (5000 m) |
Specifications may be subject to change without notice