Product Model

140DAI35300C

In Stock
Last updated: 2025/4/26
schneider 140DAI35300C

Selling Points

  • 1High-Performance VAC Discrete Input Module: The 140DAI35300C is designed for 24 V AC inputs and operates efficiently within a frequency range of 47 to 63 Hz.
  • 2Robust Isolation and Safety Features: The module features isolation of up to 1780 Vrms for one minute between groups and between groups and the bus, ensuring robust protection against electrical faults.
  • 3Advanced Software Compatibility: Compatible with ProWORX 32, Concept, and Unity Pro software solutions, providing seamless integration into various automation architectures.
  • 4Detailed Input Status Monitoring: Equipped with 32 green LEDs indicating the status of each individual input channel, simplifying monitoring and troubleshooting.
  • 5Quick Response Time and Low Power Consumption: The module offers quick response times ranging from 4.9 to 0.75 ms per line cycle for Off-On signals and 7.3 to 12.3 ms for On-Off transitions, while dissipating up to 10.9 W of power.
Product Details
140DAI35300C
schneider

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Range of Product
Modicon Quantum automation platform
Product or Component Type
VAC discrete input modules
Software name
ProWORX 32<br />Unity Pro<br />Concept
Discrete input number
32
Group of channels
4
Addressing requirement
2 input words
Discrete input voltage
24 V AC
Input current
11.1 mA 57...63 Hz<br />13.2 mA 47...53 Hz
Voltage state 1 guaranteed
12...30 V AC 57...63 Hz<br />14...30 V AC 47...53 Hz
Voltage state 0 guaranteed
0...5 V 57...63 Hz<br />0...5 V 47...53 Hz
Input impedance
2600 Ohm capacitive 57...63 Hz<br />3100 Ohm capacitive 47...53 Hz
Network frequency limits
47…63 Hz
Maximum leakage current
1.9 mA
Absolute maximum input
30 V continuous<br />32 V 10 s<br />50 V 1 cycle
Response Time
4.9...0.75 ms x line cycle Off-On<br />7.3...12.3 ms On-Off
Isolation between group
1780 Vrms for 1 minute
Isolation between group and bus
1780 Vrms for 1 minute
Bus current requirement
250 mA
Maximum power dissipation in W
10.9 W
Local signalling
for bus communication is present (Active) 1 LED (green)<br /> for external fault detected (F) 1 LED (red)<br /> for input status 32 LEDs (green)
marking
CE
Module format
Standard
Net Weight
0.75 lb(US) (0.34 kg)
Protective treatment
Conformal coating Humiseal 1A33
Standards
CSA C22.2 No 142<br />UL 508
Product Certifications
FM Class 1 Division 2<br />cUL
Resistance to electrostatic discharge
4 kV contact IEC 801-2<br />8 kV on air IEC 801-2
Resistance to electromagnetic fields
9.1 V/m (10 V/m) 80…2000 MHz IEC 801-3
Ambient Air Temperature for Operation
32…140 °F (0…60 °C)
Ambient Air Temperature for Storage
-40…185 °F (-40…85 °C)
Relative Humidity
95 % without condensation
Operating altitude
<= 16404.2 ft (5000 m)

Specifications may be subject to change without notice