Selling Points

  • 1The 140DAI45300C module offers 32 discrete inputs, perfect for complex automation systems.
  • 2Designed to work with 48V AC, ensuring reliable operation in various industrial environments.
  • 3Seamlessly integrates with Modicon Quantum PLC systems, enhancing system performance and efficiency.
  • 4Enjoy peace of mind with a 3-year warranty, covering any potential issues or defects.
  • 5We ship via global express services like DHL, FedEx, and Swiss Post, ensuring quick delivery worldwide.
Product Details
140DAI45300C
schneider

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Range of Product
Modicon Quantum automation platform
Product or Component Type
VAC discrete input modules
Software name
ProWORX 32<br />Unity Pro<br />Concept
Discrete input number
32
Group of channels
4
Addressing requirement
2 input words
Discrete input voltage
48 V AC
Input current
11.7 mA 57...63 Hz<br />9.8 mA 47...53 Hz
Voltage state 1 guaranteed
29...56 V AC 57...63 Hz<br />34...56 V AC 47...53 Hz
Voltage state 0 guaranteed
0...10 V AC 57...63 Hz<br />0...10 V AC 47...53 Hz
Input impedance
5600 Ohm capacitive 57...63 Hz<br />6800 Ohm capacitive 47...53 Hz
Network frequency limits
47…63 Hz
Maximum leakage current
1.7 mA
Absolute maximum input
100 V 1 cycle<br />56 V continuous<br />63 V 10 s
Response Time
4.9...0.75 ms x line cycle Off-On<br />7.3...12.3 ms On-Off
Isolation between group
1780 Vrms for 1 minute
Isolation between group and bus
1780 Vrms for 1 minute
Bus current requirement
250 mA
Maximum power dissipation in W
10.9 W
Local signalling
for bus communication is present (Active) 1 LED (green)<br /> for external fault detected (F) 1 LED (red)<br /> for input status 32 LEDs (green)
marking
CE
Module format
Standard
Net Weight
0.7 lb(US) (0.3 kg)
Protective treatment
Conformal coating Humiseal 1A33
Standards
CSA C22.2 No 142<br />UL 508
Product Certifications
cUL<br />FM Class 1 Division 2
Resistance to electrostatic discharge
4 kV contact IEC 801-2<br />8 kV on air IEC 801-2
Resistance to electromagnetic fields
9.1 V/m (10 V/m) 80…2000 MHz IEC 801-3
Ambient Air Temperature for Operation
32…140 °F (0…60 °C)
Ambient Air Temperature for Storage
-40…185 °F (-40…85 °C)
Relative Humidity
95 % without condensation
Operating altitude
<= 16404.2 ft (5000 m)