Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Range of Product | Modicon Quantum automation platform | Product or Component Type | VAC discrete input modules |
Software name | ProWORX 32<br />Unity Pro<br />Concept | Discrete input number | 16 |
Group of channels | 2 | Addressing requirement | 1 input word |
Discrete input voltage | 115 V AC | Input current | 11.1 mA 57...63 Hz<br />13.2 mA 47...53 Hz |
Voltage state 1 guaranteed | 79...132 V AC 57...63 Hz<br />85...132 V AC 47...53 Hz | Voltage state 0 guaranteed | 0...20 V AC 57...63 Hz<br />0...20 V AC 47...53 Hz |
Input impedance | 12000 Ohm capacitive 57...63 Hz<br />14400 Ohm capacitive 47...53 Hz | Network frequency limits | 47…63 Hz |
Maximum leakage current | 2.1 mA | Absolute maximum input | 132 V continuous<br />156 V 10 s<br />200 V 1 cycle |
Response Time | 4.9...0.75 ms x line cycle Off-On<br />7.3...12.3 ms On-Off | Isolation between group | 1780 Vrms for 1 minute |
Isolation between group and bus | 1780 Vrms for 1 minute | Bus current requirement | 180 mA |
Maximum power dissipation in W | 5.5 W | Local signalling | for bus communication is present (Active) 1 LED (green)<br /> for external fault detected (F) 1 LED (red)<br /> for input status 16 LEDs (green) |
marking | CE | Module format | Standard |
Net Weight | 0.7 lb(US) (0.3 kg) | Protective treatment | Conformal coating Humiseal 1A33 |
Standards | UL 508<br />CSA C22.2 No 142 | Product Certifications | cUL<br />FM Class 1 Division 2 |
Resistance to electrostatic discharge | 4 kV contact IEC 801-2<br />8 kV on air IEC 801-2 | Resistance to electromagnetic fields | 9.1 V/m (10 V/m) 80…2000 MHz IEC 801-3 |
Ambient Air Temperature for Operation | 32…140 °F (0…60 °C) | Ambient Air Temperature for Storage | -40…185 °F (-40…85 °C) |
Relative Humidity | 95 % without condensation | Operating altitude | <= 16404.2 ft (5000 m) |