Product Model

140DAI74000C

In Stock
Last updated: 2025/4/26
schneider 140DAI74000C

Selling Points

  • 1Efficiently handles 16 discrete inputs at 230 V AC.
  • 2Built to withstand harsh industrial environments with high isolation capabilities.
  • 3Compatible with Schneider Electric software platforms like Concept, ProWORX 32, and Unity Pro.
  • 4Ensures safe data transmission with 1780 Vrms isolation between channels and bus.
  • 5Handles absolute maximum input conditions of up to 264 V continuously and 400 V for one cycle.
Product Details
140DAI74000C
schneider

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Range of Product
Modicon Quantum automation platform
Product or Component Type
VAC discrete input modules
Software name
Concept<br />Unity Pro<br />ProWORX 32
Discrete input number
16
Group of channels
16
Addressing requirement
1 input word
Discrete input voltage
230 V AC
Input current
11.5 mA 57...63 Hz<br />9.7 mA 47...53 Hz
Voltage state 1 guaranteed
165...264 V AC 57...63 Hz<br />175...264 V AC 47...53 Hz
Voltage state 0 guaranteed
0...40 V AC 57...63 Hz<br />0...40 V AC 47...53 Hz
Input impedance
26500 Ohm capacitive 57...63 Hz<br />31800 Ohm capacitive 47...53 Hz
Network frequency limits
47…63 Hz
Maximum leakage current
2.6 mA
Absolute maximum input
264 V continuous<br />300 V 10 s<br />400 V 1 cycle
Response Time
4.9...0.75 ms x line cycle Off-On<br />7.3...12.3 ms On-Off
Isolation between channels
1780 Vrms for 1 minute
Isolation between channels and bus
1780 Vrms for 1 minute
Bus current requirement
180 mA
Maximum power dissipation in W
5.5 W
Local signalling
for bus communication is present (Active) 1 LED (green)<br /> for external fault detected (F) 1 LED (red)<br /> for input status 16 LEDs (green)
marking
CE
Module format
Standard
Net Weight
0.77 lb(US) (0.35 kg)
Protective treatment
Conformal coating Humiseal 1A33
Standards
CSA C22.2 No 142<br />UL 508
Product Certifications
FM Class 1 Division 2<br />cUL
Resistance to electrostatic discharge
4 kV contact IEC 801-2<br />8 kV on air IEC 801-2
Resistance to electromagnetic fields
9.1 V/m (10 V/m) 80…2000 MHz IEC 801-3
Ambient Air Temperature for Operation
32…140 °F (0…60 °C)
Ambient Air Temperature for Storage
-40…185 °F (-40…85 °C)
Relative Humidity
95 % without condensation
Operating altitude
<= 16404.2 ft (5000 m)

Specifications may be subject to change without notice