Product Model
140DAI75300

Selling Points
- 1High-Performance Discrete Input Module: The Schneider Electric 140DAI75300 offers 32 discrete input channels, ensuring high-performance signal processing in industrial automation systems.
- 2230V AC Input Compatibility: Designed to handle 230V AC inputs, this module is compatible with a wide range of industrial equipment, making it versatile for various applications.
- 3Robust Isolation and Safety: With 1780 Vrms of isolation, the module provides enhanced safety and protection against electrical faults, ensuring reliable operation in harsh environments.
- 4Efficient Power Dissipation: The module dissipates ≤ 5 W of power, maintaining energy efficiency while ensuring high operational standards.
- 5Seamless Integration with Automation Platforms: Compatible with Unity Pro, ProWORX 32, and Concept software platforms, the 140DAI75300 integrates seamlessly into various automation architectures.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Range of Product | Modicon Quantum automation platform | Product or Component Type | VAC discrete input modules |
Software name | Concept<br />Unity Pro<br />ProWORX 32 | Discrete input number | 32 |
Group of channels | 4 | Addressing requirement | 2 input words |
Discrete input voltage | 230 V AC | Input current | 11.5 mA 57...63 Hz<br />9.7 mA 47...53 Hz |
Voltage state 1 guaranteed | 165...264 V AC 57...63 Hz<br />175...264 V AC 47...53 Hz | Voltage state 0 guaranteed | 0...40 V AC 57...63 Hz<br />0...40 V AC 47...53 Hz |
Input impedance | 26500 Ohm capacitive 57...63 Hz<br />31800 Ohm capacitive 47...53 Hz | Network frequency limits | 47…63 Hz |
Maximum leakage current | 2.6 mA | Absolute maximum input | 264 V continuous<br />312 V 10 s<br />400 V 1 cycle |
Response Time | 4.9...0.75 ms x line cycle Off-On<br />7.3...12.3 ms On-Off | Isolation between group | 1780 Vrms for 1 minute |
Isolation between group and bus | 1780 Vrms for 1 minute | Bus current requirement | 250 mA |
Maximum power dissipation in W | 5 W | Local signalling | for bus communication is present (Active) 1 LED (green)<br /> for external fault detected (F) 1 LED (red)<br /> for input status 32 LEDs (green) |
Marking | CE | Module format | Standard |
Net Weight | 0.7 lb(US) (0.3 kg) | Standards | CSA C22.2 No 142<br />UL 508 |
Product Certifications | FM Class 1 Division 2<br />cUL | Resistance to electrostatic discharge | 4 kV contact IEC 801-2<br />8 kV on air IEC 801-2 |
Resistance to electromagnetic fields | 9.1 V/m (10 V/m) 80…2000 MHz IEC 801-3 | Ambient Air Temperature for Operation | 32…140 °F (0…60 °C) |
Ambient Air Temperature for Storage | -40…185 °F (-40…85 °C) | Relative Humidity | 95 % without condensation |
Operating altitude | <= 16404.2 ft (5000 m) |
Specifications may be subject to change without notice