Product Model

140DAI75300

In Stock
Last updated: 2025/4/26
schneider 140DAI75300

Selling Points

  • 1High-Performance Discrete Input Module: The Schneider Electric 140DAI75300 offers 32 discrete input channels, ensuring high-performance signal processing in industrial automation systems.
  • 2230V AC Input Compatibility: Designed to handle 230V AC inputs, this module is compatible with a wide range of industrial equipment, making it versatile for various applications.
  • 3Robust Isolation and Safety: With 1780 Vrms of isolation, the module provides enhanced safety and protection against electrical faults, ensuring reliable operation in harsh environments.
  • 4Efficient Power Dissipation: The module dissipates ≤ 5 W of power, maintaining energy efficiency while ensuring high operational standards.
  • 5Seamless Integration with Automation Platforms: Compatible with Unity Pro, ProWORX 32, and Concept software platforms, the 140DAI75300 integrates seamlessly into various automation architectures.
Product Details
140DAI75300
schneider

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Range of Product
Modicon Quantum automation platform
Product or Component Type
VAC discrete input modules
Software name
Concept<br />Unity Pro<br />ProWORX 32
Discrete input number
32
Group of channels
4
Addressing requirement
2 input words
Discrete input voltage
230 V AC
Input current
11.5 mA 57...63 Hz<br />9.7 mA 47...53 Hz
Voltage state 1 guaranteed
165...264 V AC 57...63 Hz<br />175...264 V AC 47...53 Hz
Voltage state 0 guaranteed
0...40 V AC 57...63 Hz<br />0...40 V AC 47...53 Hz
Input impedance
26500 Ohm capacitive 57...63 Hz<br />31800 Ohm capacitive 47...53 Hz
Network frequency limits
47…63 Hz
Maximum leakage current
2.6 mA
Absolute maximum input
264 V continuous<br />312 V 10 s<br />400 V 1 cycle
Response Time
4.9...0.75 ms x line cycle Off-On<br />7.3...12.3 ms On-Off
Isolation between group
1780 Vrms for 1 minute
Isolation between group and bus
1780 Vrms for 1 minute
Bus current requirement
250 mA
Maximum power dissipation in W
5 W
Local signalling
for bus communication is present (Active) 1 LED (green)<br /> for external fault detected (F) 1 LED (red)<br /> for input status 32 LEDs (green)
Marking
CE
Module format
Standard
Net Weight
0.7 lb(US) (0.3 kg)
Standards
CSA C22.2 No 142<br />UL 508
Product Certifications
FM Class 1 Division 2<br />cUL
Resistance to electrostatic discharge
4 kV contact IEC 801-2<br />8 kV on air IEC 801-2
Resistance to electromagnetic fields
9.1 V/m (10 V/m) 80…2000 MHz IEC 801-3
Ambient Air Temperature for Operation
32…140 °F (0…60 °C)
Ambient Air Temperature for Storage
-40…185 °F (-40…85 °C)
Relative Humidity
95 % without condensation
Operating altitude
<= 16404.2 ft (5000 m)

Specifications may be subject to change without notice