  • 1Flexible I/O Configuration: The module features 16 discrete inputs and 8 discrete outputs, organized into two groups each, for efficient signal monitoring and control.
  • 2High Voltage Tolerance: It can handle input voltage surges of up to 200 V for one cycle and up to 156 V for 10 seconds, ensuring reliability in transient overvoltage conditions.
  • 3Advanced Protection Features: Equipped with RC filters and internal fuses rated at 5 A per group, the module provides robust protection against electrical faults and short circuits.
  • 4Strong Isolation Capabilities: Offers 1000 Vrms isolation between groups and 1780 Vrms between channels and the bus, safeguarding against electrical faults and interference.
  • 5Energy-Efficient Design: With a power dissipation rated at 5.5 W plus 1.1 times the total module load current, it ensures energy efficiency in industrial applications.
Product Details
140DAM59000
schneider

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Range of Product
Modicon Quantum automation platform
Product or Component Type
Mixed discrete I/O module
Discrete I/O number
24
Discrete input number
16 2 groups of 8
Addressing requirement
1 input word<br />0.5 output word
Network frequency limits
47…63 Hz
Discrete input voltage
115 V AC
input voltage limits
156 V during 10 s<br />200 V during one cycle<br />132 V typical
Voltage state 0 guaranteed
0...20 V
Voltage state 1 guaranteed
79...132 V 60 Hz<br />85...132 V 50 Hz
Current state 0 guaranteed
<= 0.5 mA
Current state 1 guaranteed
<= 11 mA 50 Hz<br /><= 13.2 mA 60 Hz
Input impedance
14400 Ohm capacitive
Response time
4.9...0.75 ms at state 0 to state 1<br />7.3...12.3 ms at state 1 to state 0
Discrete output number
8 2 groups of 4
Discrete output type
Solid state
Discrete output voltage
115 V
Output voltage limits
156 V AC during 10 s<br />200 V AC during 1 cycle<br />85...132 V typical AC typical
Minimum load
5 mA
Maximum load current
<= 4 A per point<br /><= 8 A per group<br /><= 8 A per module
Maximum voltage drop
<1.5 V
Absolute maximum output
20 A 2 cycles per point<br />26 A 3 cycles per group<br />30 A 1 cycle per point<br />30 A 2 cycles per group<br />45 A 1 cycle per group<br />10 A 3 cycles per point
DV/dt
400 V/µs
Maximum leakage current
2.1 mA 115 V AC input circuit<br />2 mA output circuit
Response time on output
<= 0.5 ms at state 0 to state 1<br /><= 0.5 ms at state 1 to state 0
Protection Type
On output by RC filter<br />Internal output protection by 5 A fuse per group
Isolation between group
1000 Vrms for 1 minute
Isolation between channels and bus
1780 Vrms for 1 minute
Fault indication
Loss of field power on output<br />Blown fuse on output
Power dissipation
5.5 W + (1.1 x total module load current)
External power requirement
85...132 V AC for output circuit
Local signalling
for bus communication is present (Active) 1 LED (green)<br /> for no voltage in output and input (F) 1 LED (red)<br /> for output is turned on 2 LEDs (green)<br /> for fault detected on the input point 2 LEDs (red)<br /> for fault detected on the output point 2 LEDs (red)
marking
CE
Bus current requirement
250 mA
Net Weight
0.99 lb(US) (0.45 kg)
Resistance to electrostatic discharge
4 kV contact IEC 801-2<br />8 kV on air IEC 801-2
Resistance to electromagnetic fields
9.1 V/m (10 V/m) 80…1000 MHz IEC 801-3
Ambient Air Temperature for Operation
32…140 °F (0…60 °C)
Ambient Air Temperature for Storage
-40…185 °F (-40…85 °C)
Relative Humidity
95 % without condensation
Operating altitude
<= 16404.2 ft (5000 m)
Standards
FM Class 1 Division 2<br />UL 508<br />CSA C22.2 No 142
Product Certifications
cUL