Product Model

140DDI36400C

In Stock
Last updated: 2025/4/26
schneider 140DDI36400C

Selling Points

  • 196 discrete input points organized into 6 channel groups for efficient signal processing.
  • 2Positive (sink) logic ensures accurate input detection, reducing noise and interference.
  • 3Transitions from state 1 to state 0 in ≤3 ms and state 0 to state 1 in ≤2 ms for real-time monitoring.
  • 4Power dissipation calculated at 1.35 W base rate + 0.13 W per active input point, optimizing power management.
  • 5Isolated at 500 VRMS for up to one minute, protecting against electrical interference across groups.
Product Details
140DDI36400C
schneider

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Range of Product
Modicon Quantum automation platform
Product or Component Type
Low voltage dc discrete input modules
Discrete input number
96
Group of channels
6
Logic input
Positive (sink)
Discrete input voltage
24 V DC
input voltage limits
19.2...30 V
Voltage state 1 guaranteed
15...30 V DC
Voltage state 0 guaranteed
5 V DC
Current state 1 guaranteed
>= 2.5 mA
Current state 0 guaranteed
>= 0.7 mA
Addressing requirement
6 words
input impedance
6700 Ohm
Absolute maximum input
30 V continuous<br />50 V decaying pulse
Response Time
<= 2 ms from state 0 to state 1<br /><= 3 ms from state 1 to state 0
Power dissipation
1.35 W + (0.13 x number of points on)
Isolation between group
500 Vrms for 1 minute
Local signalling
for bus communication is present (Active) 1 LED (green)<br /> for external fault detected (F) 1 LED (red)<br /> for input status 96 LEDs (green)
marking
CE
Bus current requirement
270 mA
Module format
Standard
Net Weight
0.7 lb(US) (0.3 kg)
Protective treatment
Conformal coating Humiseal 1A33
Standards
CSA C22.2 No 142<br />UL 508
Product Certifications
C-tick<br />FM Class 1 Division 2
Resistance to electrostatic discharge
4 kV contact IEC 801-2<br />8 kV on air IEC 801-2
Resistance to electromagnetic fields
9.1 V/m (10 V/m) 80…2000 MHz IEC 801-3
Ambient Air Temperature for Operation
32…140 °F (0…60 °C)
Ambient Air Temperature for Storage
-40…185 °F (-40…85 °C)
Relative Humidity
95 % without condensation
Operating altitude
<= 16404.2 ft (5000 m)

Specifications may be subject to change without notice