Product Model

140DDO35310

In Stock
Last updated: 2025/4/19
schneider 140DDO35310

Selling Points

  • 1Provides 1780 Vrms DC isolation between channels and the bus, ensuring robust protection against electrical interference.
  • 2Offers 32 discrete DC outputs grouped into four clusters of eight channels each, simplifying wiring and improving organizational efficiency.
  • 3Supports a maximum load current of 4 A per group and a total of 16 A across the module, handling substantial current loads.
  • 4Features rapid response time of less than or equal to 1 ms, ensuring timely output switching for high-speed operations.
  • 5Includes comprehensive protective features such as transient voltage suppression and internal fuses to prevent overcurrent damage and voltage surges.
Product Details
140DDO35310
schneider

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Range of Product
Modicon Quantum automation platform
Product or Component Type
Dc discrete output module
Discrete output number
32
Group of channels
4 groups of 8
Discrete output logic
Negative logic (sink)
Addressing requirement
2 output words
Discrete output voltage
24 V DC
Output voltage limits
19.2...30 V
Absolute maximum output
50 V 1 s decaying pulse
Maximum voltage drop
<0.4 V 0.5 A
Maximum load current
16 A per module<br />4 A per group
Surge current
5 A 1 ms
Response Time
<= 1 ms at state 0 to state 1<br /><= 1 ms at state 1 to state 0
Maximum leakage current
0.4 mA 30 V
Load inductance
Inductance(H) = 0.5/((current(A))² x (switching frequency(Hz)))
Maximum tungsten load
12 W 24 V
Fault indication
Loss of field power<br />Blown fuse
Associated fuse rating
3 A each point<br />5 A per group
Isolation between channels and bus
1780 Vrms DC for 1 minute
Isolation between group
500 Vrms DC for 1 minute
Protection Type
Internal output protection by 5 A fuse per group
Power dissipation
2.0 W + (0.4 V x total load current)
marking
CE
Local signalling
for bus communication is present (Active) 1 LED (green)<br /> for external fault detected (F) 1 LED (red)<br /> for input status 32 LEDs (green)
Bus current requirement
330 mA
Module format
Standard
Net Weight
0.99 lb(US) (0.45 kg)
Product Certifications
FM Class 1 Division 2<br />RINA<br />GOST<br />C-tick<br />RMRS
Standards
UL 508<br />CSA C22.2 No 142
Resistance to electrostatic discharge
4 kV contact IEC 801-2<br />8 kV on air IEC 801-2
Resistance to electromagnetic fields
9.1 V/m (10 V/m) 80…2000 MHz IEC 801-3
Ambient Air Temperature for Operation
32…140 °F (0…60 °C)
Ambient Air Temperature for Storage
-40…185 °F (-40…85 °C)
Relative Humidity
95 % without condensation
Operating altitude
<= 16404.2 ft (5000 m)

Specifications may be subject to change without notice