Product Model

140DDO84300C

In Stock
Last updated: 2025/4/19
schneider 140DDO84300C

Selling Points

  • 116 Discrete Outputs: Control multiple devices with 16 discrete outputs.
  • 2Negative Logic (Sink): Compatible with systems requiring negative logic.
  • 3Robust Isolation: Ensures safe operation with 2500 Vrms DC isolation between channels and bus.
  • 4Fast Response Time: Achieve quick transitions with ≤1 ms response time.
  • 5High Load Capacity: Handle up to 12 A per module and 6 A per group.
Product Details
140DDO84300C
schneider

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Range of Product
Modicon Quantum automation platform
Product or Component Type
Dc discrete output module
Discrete output number
16
Group of channels
2 groups of 8
Discrete output logic
Positive logic (source)
Addressing requirement
1 output word
Discrete output voltage
10...60 V DC
Output voltage limits
10.2...72 V
Absolute maximum output
72 V permanent
Maximum voltage drop
<1 V 2 A
Maximum load current
12 A per module<br />6 A per group
Surge current
7.5 A 50 s
Response Time
<= 1 ms at state 0 to state 1<br /><= 1 ms at state 1 to state 0
Maximum leakage current
1 mA 60 V
Load inductance
Inductance(H) = 0.5/((current(A))² x (switching frequency(Hz)))
Associated fuse rating
2 A each point<br />8 A per group
Isolation between channels and bus
2500 Vrms DC for 1 minute
Isolation between group
700 Vrms DC for 1 minute
Protection Type
Internal output protection by 8 A fuse per group
Power dissipation
1 W + (1 V x total module load current)
marking
CE
Local signalling
for bus communication is present (Active) 1 LED (green)<br /> for external fault detected (F) 1 LED (red)<br /> for input status 16 LEDs (green)
Bus current requirement
160 mA
Module format
Standard
Net Weight
0.99 lb(US) (0.45 kg)
Protective treatment
Conformal coating Humiseal 1A33
Product Certifications
C-tick<br />FM Class 1 Division 2<br />RMRS<br />GOST
Standards
CSA C22.2 No 142<br />UL 508
Resistance to electrostatic discharge
4 kV contact IEC 801-2<br />8 kV on air IEC 801-2
Resistance to electromagnetic fields
9.1 V/m (10 V/m) 80…2000 MHz IEC 801-3
Ambient Air Temperature for Operation
32…140 °F (0…60 °C)
Ambient Air Temperature for Storage
-40…185 °F (-40…85 °C)
Relative Humidity
95 % without condensation
Operating altitude
<= 16404.2 ft (5000 m)

Specifications may be subject to change without notice