Product Model

140DII33000

In Stock
Last updated: 2025/4/19
schneider 140DII33000

Selling Points

  • 1Ensures safe operation in hazardous environments, meeting CE II1 G/D-EEx ia IIC standards.
  • 2Switching frequency of 100 Hz for real-time monitoring and control of discrete input signals.
  • 3Internal resistance of 2.5 kOhm for optimal signal quality and reliability.
  • 4Compatible with ProWORX, Concept, and Unity Pro software for seamless integration.
  • 5Designed for industrial applications, including process control, machine automation, and safety monitoring in hazardous environments.
Product Details
140DII33000
schneider

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Range of Product
Modicon Quantum automation platform
Product or Component Type
Intrinsically safe discrete input module
Software Designation
ProWORX<br />Concept<br />Unity Pro
Software Version
V2.2 and above
Product destination
In conjunction with products for zone 20, 21 or 22
Discrete input number
8
No load voltage
8 V
Short-circuit current
8 mA
Switching hysteresis
0.2 mA
Current state 0 guaranteed
<= 1.2 mA
Current state 1 guaranteed
>= 2.1 mA
Switching frequency
100 Hz
Response time
1 ms resistive at state 0 to state 1<br />1 ms resistive at state 1 to state 0
Internal resistance
2.5 kOhm
Protection Type
Resistor limited<br />Internal by fuse
Isolation between channels and bus
2500 V for 1 minute DC<br />1780 V 47...63 Hz AC
Fault type
Resistor limited
Hot swapping fallback
Not allowed per intrinsic safety standards
Power dissipation in W
2 W
marking
CE<br />II1 G/D-EEx ia IIC
Bus current requirement
0.4 A
Module format
Standard
Net Weight
0.7 lb(US) (0.3 kg)
Standards
EN 50039<br />EN 50020<br />UL 508<br />CSA C22.2 No 142<br />EN 50014<br />EN 50284<br />Directive ATEX 94/9/EC<br />EN 50281-1-1
Dust zone
Outside zone
Product Certifications
FM Class 1 Division 2
Resistance to electrostatic discharge
4 kV contact IEC 801-2<br />8 kV on air IEC 801-2
Resistance to electromagnetic fields
9.1 V/m (10 V/m) 80...1000 MHz IEC 801-3
Ambient Air Temperature for Operation
32…140 °F (0…60 °C)
Ambient Air Temperature for Storage
-40…185 °F (-40…85 °C)
Relative Humidity
95 % without condensation
Operating altitude
<= 16404.2 ft (5000 m)

Specifications may be subject to change without notice