Product Model

140DRA84000C

In Stock
Last updated: 2025/4/19
schneider 140DRA84000C

Selling Points

  • 1High Reliability: 16-point relay discrete output module with 2-year warranty.
  • 2Versatile Voltage Range: Operates at 5-30 V DC, 30-150 V DC, and 20-250 V AC.
  • 3High Load Capacity: Maximum load current up to 2 A at 250/30 V AC/DC.
  • 4Advanced Durability: Mechanical durability of 10,000,000 cycles and electrical durability of up to 200,000 cycles.
  • 5Enhanced Safety Features: Internal overvoltage protection by varistor and isolation between channels up to 1780 Vrms AC.
Product Details
140DRA84000C
schneider

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Range of Product
Modicon Quantum automation platform
Product or Component Type
Relay discrete output module
Discrete output number
16
Contacts type and composition
1 NO
Contact form
Form A
Discrete output voltage
20...250 V AC<br />30...150 V DC<br />5...30 V DC
Addressing requirement
1 output word
Minimum load
50 mA 20...250 V AC<br />50 mA 5...30 V DC
Maximum load current
1 A 250/30 V AC/DC 1/8 hp cos phi = 0.4<br />1 A 250/30 V AC/DC tungsten<br />2 A 250/30 V AC/DC resistive 140 °F (60 °C)<br />300 mA 30...50 V DC resistive
Surge current
10 A 10 ms capacitive
Switching capacity in VA
500 VA resistive
Maximum response time on input open
10 ms at state 0 to state 1<br />20 ms at state 1 to state 0
Mechanical durability
10000000 cycles
Electrical durability
100000 cycles 100 mA 30...150 V DC L/R = 10 ms<br />100000 cycles 2 A 30 V DC resistive<br />100000 cycles 30...150 V DC interposing relay<br />100000 cycles 300 mA 30...150 V DC resistive<br />200000 cycles 2 A 250 V AC resistive<br />50000 cycles 500 mA 30...150 V DC resistive
Output overvoltage protection
Internal by varistor, 275 V
Isolation between channels
1780 Vrms AC for 1 minute
Isolation between channels and bus
1780 Vrms AC for 1 minute<br />2500 V DC for 1 minute
Power dissipation
5.5 W + (0.5 x the number of points on)
marking
CE
Local signalling
for bus communication is present (Active) 1 LED (green)<br /> for external fault detected (F) 1 LED (red)<br /> for input status 16 LEDs (green)
Bus current requirement
1100 mA
Module format
Standard
Net Weight
0.90 lb(US) (0.41 kg)
Protective treatment
Conformal coating Humiseal 1A33
Product Certifications
FM Class 1 Division 2<br />ABS<br />GOST<br />C-tick
Standards
UL 508<br />CSA C22.2 No 142
Resistance to electrostatic discharge
4 kV contact IEC 801-2<br />8 kV on air IEC 801-2
Resistance to electromagnetic fields
9.1 V/m (10 V/m) 80…2000 MHz IEC 801-3
Ambient Air Temperature for Operation
32…140 °F (0…60 °C)
Ambient Air Temperature for Storage
-40…185 °F (-40…85 °C)
Relative Humidity
95 % without condensation
Operating altitude
<= 16404.2 ft (5000 m)

Specifications may be subject to change without notice