Selling Points
- 18 Discrete Output Channels: Precise control and monitoring of connected devices.
- 2Robust Isolation: 1780 Vrms AC and 2500 V DC isolation between channels and bus.
- 3CE Certification: Meets stringent quality and safety standards.
- 4Versatile Voltage Support: Handles 20-250 V AC, 30-150 V DC, and 5-30 V DC.
- 5Efficient Power Dissipation: 2.75 W plus 0.5 times the number of points on.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Range of Product | Modicon Quantum automation platform | Product or Component Type | Relay discrete output module |
Discrete output number | 8 | Contacts type and composition | 1 NO/NC |
Contact form | Form C | Discrete output voltage | 20...250 V AC<br />30...150 V DC<br />5...30 V DC |
Addressing requirement | 0.5 output word | Maximum load current | 100 mA 30...50 V DC L/R = 10 ms<br />2 A 250/30 V AC/DC tungsten 1/4 hp cos phi = 0.4<br />3 A 250/30 V AC/DC<br />300 mA 30...50 V DC resistive<br />5 A 250/30 V AC/DC resistive 140 °F (60 °C) |
Surge current | 20 A 10 ms capacitive | Switching frequency | 30 Hz resistive<br />F = 0.5/I²L inductive |
Switching capacity in VA | 1250 VA resistive | Maximum response time on input open | 10 ms at state 0 to state 1<br />20 ms at state 1 to state 0 |
Mechanical durability | 10000000 cycles | Electrical durability | 100000 cycles 100 mA 30...150 V DC L/R = 10 ms<br />100000 cycles 30...150 V DC interposing relay<br />100000 cycles 300 mA 30...150 V DC resistive<br />100000 cycles 5 A 30 V DC resistive<br />200000 cycles 5 A 250 V AC resistive<br />50000 cycles 500 mA 30...150 V DC resistive |
Output overvoltage protection | Internal by varistor, 275 V | Isolation between channels | 1780 Vrms AC for 1 minute<br />2500 V DC |
Isolation between channels and bus | 1780 Vrms AC for 1 minute<br />2500 V DC for 1 minute | Power dissipation | 2.75 W + (0.5 x the number of points on) |
marking | CE | Local signalling | for bus communication is present (Active) 1 LED (green)<br /> for external fault detected (F) 1 LED (red)<br /> for input status 8 LEDs (green) |
Bus current requirement | 560 mA | Module format | Standard |
Net Weight | 0.7 lb(US) (0.3 kg) | Product Certifications | C-tick<br />GOST<br />GL<br />RMRS<br />FM Class 1 Division 2<br />ABS<br />DNV<br />RINA |
Standards | UL 508<br />CSA C22.2 No 142 | Resistance to electrostatic discharge | 4 kV contact IEC 801-2<br />8 kV on air IEC 801-2 |
Resistance to electromagnetic fields | 9.1 V/m (10 V/m) 80…2000 MHz IEC 801-3 | Ambient Air Temperature for Operation | 32…140 °F (0…60 °C) |
Ambient Air Temperature for Storage | -40…185 °F (-40…85 °C) | Relative Humidity | 95 % without condensation |
Operating altitude | <= 16404.2 ft (5000 m) |