Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Range of Product | Modicon Quantum automation platform | Product or Component Type | Dc discrete output module |
Discrete output number | 32 | Group of channels | 4 groups of 8 |
Discrete output logic | Negative logic (sink) | Addressing requirement | 2 output words<br />2 input words |
Discrete output voltage | 10...30 V DC | Absolute maximum output | 50 V 1 s decaying pulse |
Maximum voltage drop | <0.4 V 0.5 A | Maximum load current | <= 0.5 A each point<br /><= 16 A per module<br /><= 4 A each group |
Surge current | 2.5 A 1 ms | Response Time | <= 2 ms at state 0 to state 1<br /><= 2 ms at state 1 to state 0<br />1 ms at state 0 to state 1<br />1 ms at state 1 to state 0 |
Short-circuit protection | With | Output overvoltage protection | With |
Load inductance | Inductance(H) = 0.5/((current(A))² x (switching frequency(Hz))) 0.5...4 Hz | Maximum tungsten load | 2.5 W 10 V<br />3 W 12 V<br />6 W 24 V |
Fault indication | Incorrect output state<br />Loss of field power<br />Blown fuse | Protection Type | Internal output protection by 5 A fuse per group |
Power dissipation | 2.5 W + (0.1 x all points on) + (0.4 x total load current) | marking | CE |
Local signalling | for bus communication is present (Active) 1 LED (green)<br /> for external fault detected (F) 1 LED (red)<br /> for input status 32 LEDs (green) | Bus current requirement | 500 mA |
Module format | Standard | Net Weight | 0.7 lb(US) (0.3 kg) |
Product Certifications | GOST<br />FM Class 1 Division 2<br />RMRS<br />C-tick | Standards | UL 508<br />CSA C22.2 No 142 |
Resistance to electrostatic discharge | 4 kV contact IEC 801-2<br />8 kV on air IEC 801-2 | Resistance to electromagnetic fields | 9.1 V/m (10 V/m) 80…2000 MHz IEC 801-3 |
Ambient Air Temperature for Operation | 32…140 °F (0…60 °C) | Ambient Air Temperature for Storage | -40…185 °F (-40…85 °C) |
Relative Humidity | 95 % without condensation | Operating altitude | <= 16404.2 ft (5000 m) |