Product Model

140DVO85300

In Stock
Last updated: 2025/4/19
schneider 140DVO85300

Selling Points

  • 1The 140DVO85300 offers fast response times of 1 ms for state transitions, making it suitable for time-sensitive applications.
  • 2Equipped with negative logic (sink) and multiple protective mechanisms, including short-circuit and overvoltage protection, ensuring reliable operation.
  • 3Features local signaling indicators for easy monitoring, including green LEDs for active bus communication and red LEDs for external faults.
  • 4Supports up to 16 A of load current per module, with a maximum of 0.5 A per point and 4 A per group, handling high-current loads efficiently.
  • 5Operates with a bus current requirement of 500 mA, making it a power-efficient option for extensive control systems.
Product Details
140DVO85300
schneider

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Range of Product
Modicon Quantum automation platform
Product or Component Type
Dc discrete output module
Discrete output number
32
Group of channels
4 groups of 8
Discrete output logic
Negative logic (sink)
Addressing requirement
2 output words<br />2 input words
Discrete output voltage
10...30 V DC
Absolute maximum output
50 V 1 s decaying pulse
Maximum voltage drop
<0.4 V 0.5 A
Maximum load current
<= 0.5 A each point<br /><= 16 A per module<br /><= 4 A each group
Surge current
2.5 A 1 ms
Response Time
<= 2 ms at state 0 to state 1<br /><= 2 ms at state 1 to state 0<br />1 ms at state 0 to state 1<br />1 ms at state 1 to state 0
Short-circuit protection
With
Output overvoltage protection
With
Load inductance
Inductance(H) = 0.5/((current(A))² x (switching frequency(Hz))) 0.5...4 Hz
Maximum tungsten load
2.5 W 10 V<br />3 W 12 V<br />6 W 24 V
Fault indication
Incorrect output state<br />Loss of field power<br />Blown fuse
Protection Type
Internal output protection by 5 A fuse per group
Power dissipation
2.5 W + (0.1 x all points on) + (0.4 x total load current)
marking
CE
Local signalling
for bus communication is present (Active) 1 LED (green)<br /> for external fault detected (F) 1 LED (red)<br /> for input status 32 LEDs (green)
Bus current requirement
500 mA
Module format
Standard
Net Weight
0.7 lb(US) (0.3 kg)
Product Certifications
GOST<br />FM Class 1 Division 2<br />RMRS<br />C-tick
Standards
UL 508<br />CSA C22.2 No 142
Resistance to electrostatic discharge
4 kV contact IEC 801-2<br />8 kV on air IEC 801-2
Resistance to electromagnetic fields
9.1 V/m (10 V/m) 80…2000 MHz IEC 801-3
Ambient Air Temperature for Operation
32…140 °F (0…60 °C)
Ambient Air Temperature for Storage
-40…185 °F (-40…85 °C)
Relative Humidity
95 % without condensation
Operating altitude
<= 16404.2 ft (5000 m)

Specifications may be subject to change without notice