Selling Points

  • 1High-Performance DC Discrete Output Module: The 140DVO85300C offers 32 discrete outputs, making it suitable for complex industrial automation tasks.
  • 2Robust Protection Features: Equipped with negative logic (sink) and internal output protection by a 5A fuse per group, ensuring reliable operation.
  • 3Standard Module Format: Compatible with various industrial setups, featuring a standard module format for easy integration.
  • 4Wide Voltage Range: Operates within a voltage range of 10-30V DC, with an absolute maximum output of 50V for 1s decaying pulse.
  • 5Fast Response Time: Delivers fast response times of 1ms at state 1 to state 0 and state 0 to state 1, ensuring quick control over outputs.
Product Details
140DVO85300C
schneider

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Range of Product
Modicon Quantum automation platform
Product or Component Type
Dc discrete output module
Discrete output number
32
Group of channels
4 groups of 8
Discrete output logic
Negative logic (sink)
Addressing requirement
2 output words<br />2 input words
Discrete output voltage
10...30 V DC
Absolute maximum output
50 V 1 s decaying pulse
Maximum voltage drop
<0.4 V 0.5 A
Maximum load current
<= 0.5 A each point<br /><= 16 A per module<br /><= 4 A each group
Surge current
2.5 A 1 ms
Response Time
<= 2 ms at state 0 to state 1<br /><= 2 ms at state 1 to state 0<br />1 ms at state 0 to state 1<br />1 ms at state 1 to state 0
Short-circuit protection
With
Output overvoltage protection
With
Load inductance
Inductance(H) = 0.5/((current(A))² x (switching frequency(Hz))) 0.5...4 Hz
Maximum tungsten load
2.5 W 10 V<br />3 W 12 V<br />6 W 24 V
Fault indication
Incorrect output state<br />Loss of field power<br />Blown fuse
Protection Type
Internal output protection by 5 A fuse per group
Power dissipation
2.5 W + (0.1 x all points on) + (0.4 x total load current)
marking
CE
Local signalling
for bus communication is present (Active) 1 LED (green)<br /> for external fault detected (F) 1 LED (red)<br /> for input status 32 LEDs (green)
Bus current requirement
500 mA
Module format
Standard
Net Weight
0.7 lb(US) (0.3 kg)
Protective treatment
Conformal coating Humiseal 1A33
Product Certifications
RMRS<br />FM Class 1 Division 2<br />C-tick<br />GOST
Standards
CSA C22.2 No 142<br />UL 508
Resistance to electrostatic discharge
4 kV contact IEC 801-2<br />8 kV on air IEC 801-2
Resistance to electromagnetic fields
9.1 V/m (10 V/m) 80…2000 MHz IEC 801-3
Ambient Air Temperature for Operation
32…140 °F (0…60 °C)
Ambient Air Temperature for Storage
-40…185 °F (-40…85 °C)
Relative Humidity
95 % without condensation
Operating altitude
<= 16404.2 ft (5000 m)

Specifications may be subject to change without notice