Product Model

140EHC20200

In Stock
Last updated: 2025/4/19
schneider 140EHC20200

Selling Points

  • 1Handles frequencies up to 500,000 Hz for precise and efficient counting operations.
  • 2Suitable for a range of industrial applications including material handling, packaging, and textile machines.
  • 3Compliant with European safety and environmental standards, ensuring quality and reliability.
  • 4Equipped with 4 discrete output channels using Field Effect Transistor (FET) for efficient switching.
  • 5Includes a 36 V transorb for discrete output protection, ensuring the safety of the module and connected devices.
Product Details
140EHC20200
schneider

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Range of Product
Modicon Quantum automation platform
Product or Component Type
High-speed counter module
Number of Channels
2
Addressing requirement
6 output words<br />6 input words
Data format
2147483647 dec 32 bits<br />65535 dec 16 bits
Counting input type
Incremental or quadrature
Counting frequency
500000 Hz
Discrete input voltage
< 30 V
Operating mode
Incremental or quadrature discrete input
Input resistance
10 kOhm discrete input
Operating threshold
0...11 V single ended mode 24 V DC at state off<br />0...2 V single ended mode 5 V DC at state on<br />0 V single ended mode 12 V DC at state on<br />13...24 V single ended mode 24 V DC at state on<br />2...7 V single ended mode 12 V DC at state off<br />>= 1.8 V differential mode<br />3.5...5 V single ended mode 5 V DC at state off
Discrete output number
4
Discrete output type
Field Effect Transistor (FET)
Discrete output voltage
0 V switch off DC<br />0.4 V switch on DC
Load current
0.5 A
Maximum leakage current
0.4 mA state off
Maximum voltage drop
<0.4 V state on
Protection type
36 V transorb discrete output
Isolation between channels and bus
1780 Vrms 60 s
Fault type
Loss of output field power
Output short-circuit protection
Blown fuse 2.5 A
Power dissipation
4 + (0.4 x total module load current)
Bus current requirement
650 mA
External power requirement
19.2...30 V
Rack type
Local<br />Remote<br />Distributed
Local signalling
for channel status 2 LEDs
marking
CE
Current consumption
<= 1050 mA 24 V DC external power supply
Module format
Standard
Resistance to electrostatic discharge
4 kV contact IEC 801-2<br />8 kV on air IEC 801-2
Resistance to electromagnetic fields
9.1 V/m (10 V/m) 80…1000 MHz IEC 801-3
Ambient Air Temperature for Operation
32…140 °F (0…60 °C)
Ambient Air Temperature for Storage
-40…185 °F (-40…85 °C)
Relative Humidity
95 % without condensation
Operating altitude
<= 16404.2 ft (5000 m)
Standards
UL 508
Product Certifications
C-Tick.1<br />CSA No 142<br />FM Class 1 Division 2<br />UL

Specifications may be subject to change without notice