Product Model

140ESI06210C

In Stock
Last updated: 2025/4/18
schneider 140ESI06210C

Selling Points

  • 1Seamless Integration: The 140ESI06210C integrates effortlessly into industrial automation systems, ensuring optimal performance across diverse settings.
  • 2Advanced Communication: Equipped with two RS232C non-isolated ports, this module facilitates reliable ASCII serial link communication, supporting up to 8 levels of message nesting.
  • 3Efficient Data Exchange: With a transmission rate of 19.2 kbit/s and a cable length of 20 meters, it ensures efficient data exchange and processing.
  • 4Software Compatibility: Compatible with Unity Pro, ProWORX NxT, ProWORX 32, and Concept software platforms, enhancing seamless integration into existing control systems.
  • 5Energy Efficiency: Maintaining a power dissipation of less than or equal to 2 watts, it ensures minimal energy usage without compromising performance.
Product Details
140ESI06210C
schneider

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Range of Product
Modicon Quantum automation platform
Product or Component Type
ASCII serial link module
Software name
Concept > V2<br />ProWORX 32 > V2<br />ProWORX NxT > V2<br />Unity Pro > V2
Product Compatibility
All Quantum CPU
Product Specific Application
For severe environments
Mode of Transmission
ASCII
Number of port
2 RS232C non isolated DIN 66020
Electrical connection
2 connectors SUB-D 9
Transmission Rate
19.2 kbit/s
Maximum cable distance between devices
<65.6 ft (20 m)
Message nesting
8 levels
Buffer size
255 I bytes/255 O bytes
Number of messages
255
Message length
127 characters + 1 checksum maximum
Clock
With calendar clock
Memory capacity
128 kB flash<br />32 kB RAM
Maximum power dissipation in W
2 W
Addressing requirement
12 input words<br />12 output words
Bus current requirement
300 mA
Module format
Standard
Net Weight
0.7 lb(US) (0.3 kg)
Resistance to electromagnetic fields
9.1 V/m (10 V/m) 80...1000 MHz IEC 801-3
Ambient Air Temperature for Operation
32…140 °F (0…60 °C)
Ambient Air Temperature for Storage
-40…185 °F (-40…85 °C)
Relative Humidity
95 % without condensation
Operating altitude
<= 16404.2 ft (5000 m)

Specifications may be subject to change without notice