Selling Points

  • 1Handles motor powers from 45 kW to 200 kW, suitable for various industrial scenarios.
  • 2Features torque-controlled start for smooth and controlled acceleration, ensuring reliability in diverse environments.
  • 3Operates with a power supply voltage spanning from 208 to 690 V, accommodating different industrial settings.
  • 4Equipped with an IP00 degree of protection, making it robust against solid objects and water-resistant.
  • 5Supports Modbus protocol and RS485 multidrop physical interface for seamless communication and control precision.
Product Details
ATS48C21Y
schneider

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Range of Product
Altistart 48
Product or Component Type
Soft starter
Product destination
Asynchronous motors
Product Specific Application
Heavy duty industry and pumps
Device short name
ATS48
Utilisation category
AC-53A
Ue power supply voltage
208...690 V - 15...10 %
power supply frequency
50...60 Hz - 5...5 %
Motor power kW
110 kW 400 V for standard applications<br />110 kW 440 V for standard applications<br />110 kW 500 V for severe applications<br />110 kW 525 V for severe applications<br />132 kW 500 V for standard applications<br />132 kW 525 V for standard applications<br />132 kW 660 V for severe applications<br />160 kW 660 V for standard applications<br />160 kW 690 V for severe applications<br />200 kW 690 V for standard applications<br />45 kW 230 V for severe applications<br />55 kW 230 V for standard applications<br />90 kW 400 V for severe applications<br />90 kW 440 V for severe applications
Maximum Horse Power Rating
125 hp 460 V for severe applications<br />150 hp 460 V for standard applications<br />150 hp 575 V for severe applications<br />200 hp 575 V for standard applications<br />50 hp 208 V for severe applications<br />60 hp 208 V for standard applications<br />60 hp 230 V for severe applications<br />75 hp 230 V for standard applications
Device connection
In the motor supply line
Protection type
Phase failure line<br />Thermal protection motor<br />Thermal protection starter
Standards
IEC 60947-4-2
Product Certifications
DNV<br />GOST<br />SEPRO<br />TCF<br />UL<br />CCC<br />NOM 117<br />C-tick<br />CSA
marking
CE
Discrete input number
5
Discrete input type
PTC, 750 Ohm 77 °F (25 °C)<br />Stop, Run, LI3, LI4) logic, <= 8 mA 4300 Ohm
Discrete input logic
Positive logic Stop, Run, LI3, LI4 < 5 V <= 2 mA > 11 V, >= 5 mA
Minimum switching current
10 mA 6 V DC relay outputs
Discrete output number
2
Discrete output type
LO1) logic output 0 V common configurable<br />LO2) logic output 0 V common configurable<br />R1) relay outputs fault relay NO<br />R2) relay outputs end of starting relay NO<br />R3) relay outputs motor powered NO
Analogue output type
Current output AO 0-20 mA or 4-20 mA 500 Ohm
communication port protocol
Modbus
Connector Type
1 RJ45
Communication data link
Serial
Physical interface
RS485 multidrop
Transmission Rate
4800, 9600 or 19200 bps
Function Available
External bypass (optional)
Operating position
Vertical +/- 10 degree
Height
15.0 in (380 mm)
Width
12.6 in (320 mm)
Depth
10.4 in (265 mm)
Net Weight
40.1 lb(US) (18.2 kg)
Electromagnetic compatibility
Conducted and radiated emissions level A IEC 60947-4-2<br />Damped oscillating waves level 3 IEC 61000-4-12<br />Electrostatic discharge level 3 IEC 61000-4-2<br />Immunity to electrical transients level 4 IEC 61000-4-4<br />Immunity to radiated radio-electrical interference level 3 IEC 61000-4-3<br />Voltage/current impulse level 3 IEC 61000-4-5
Relative humidity
0…95 % without condensation or dripping water IEC 60068-2-3
Ambient air temperature for operation
104…140 °F (40…60 °C) with current derating of 2 % per °C)<br />14…104 °F (-10…40 °C) without derating)
Ambient Air Temperature for Storage
-13…158 °F (-25…70 °C)
Operating altitude
<= 3280.84 ft (1000 m) without derating<br />> 3280.84...6561.68 ft (> 1000...2000 m) with current derating of 2.2 % per additional 100 m