Product Model
ATS48C59Y

Selling Points
- 1Supports motor power from 132 kW to 560 kW.
- 2Operates on 208-690 V with ±15% tolerance.
- 3Features start with torque control and current limited to 5 In.
- 4Includes phase failure, thermal protection for motor and starter.
- 5Supports Modbus protocol via RS485 multidrop connection.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Range of Product | Altistart 48 | Product or Component Type | Soft starter |
Product destination | Asynchronous motors | Product Specific Application | Heavy duty industry and pumps |
Device short name | ATS48 | Utilisation category | AC-53A |
Ue power supply voltage | 208...690 V - 15...10 % | power supply frequency | 50...60 Hz - 5...5 % |
Motor power kW | 132 kW 230 V for severe applications<br />160 kW 230 V for standard applications<br />250 kW 400 V for severe applications<br />250 kW 440 V for severe applications<br />315 kW 400 V for standard applications<br />315 kW 500 V for severe applications<br />315 kW 525 V for severe applications<br />355 kW 440 V for standard applications<br />400 kW 500 V for standard applications<br />400 kW 525 V for standard applications<br />400 kW 660 V for severe applications<br />500 kW 690 V for severe applications<br />560 kW 660 V for standard applications<br />560 kW 690 V for standard applications | Maximum Horse Power Rating | 150 hp 208 V for severe applications<br />200 hp 230 V for standard applications<br />350 hp 460 V for severe applications<br />400 hp 460 V for standard applications<br />400 hp 575 V for severe applications<br />500 hp 575 V for standard applications |
Device connection | In the motor supply line | Protection type | Phase failure line<br />Thermal protection motor<br />Thermal protection starter |
Standards | IEC 60947-4-2 | Product Certifications | NOM 117<br />CSA<br />GOST<br />DNV<br />CCC<br />C-tick<br />TCF<br />UL<br />SEPRO |
marking | CE | Discrete input number | 5 |
Discrete input type | PTC, 750 Ohm 77 °F (25 °C)<br />Stop, Run, LI3, LI4) logic, <= 8 mA 4300 Ohm | Discrete input logic | Positive logic Stop, Run, LI3, LI4 < 5 V <= 2 mA > 11 V, >= 5 mA |
Minimum switching current | 10 mA 6 V DC relay outputs | Discrete output number | 2 |
Discrete output type | LO1) logic output 0 V common configurable<br />LO2) logic output 0 V common configurable<br />R1) relay outputs fault relay NO<br />R2) relay outputs end of starting relay NO<br />R3) relay outputs motor powered NO | Analogue output type | Current output AO 0-20 mA or 4-20 mA 500 Ohm |
communication port protocol | Modbus | Connector Type | 1 RJ45 |
Communication data link | Serial | Physical interface | RS485 multidrop |
Transmission Rate | 4800, 9600 or 19200 bps | Function Available | External bypass (optional) |
Operating position | Vertical +/- 10 degree | Height | 26.4 in (670 mm) |
Width | 15.7 in (400 mm) | Depth | 11.8 in (300 mm) |
Net Weight | 113.3 lb(US) (51.4 kg) | Electromagnetic compatibility | Conducted and radiated emissions level A IEC 60947-4-2<br />Damped oscillating waves level 3 IEC 61000-4-12<br />Electrostatic discharge level 3 IEC 61000-4-2<br />Immunity to electrical transients level 4 IEC 61000-4-4<br />Immunity to radiated radio-electrical interference level 3 IEC 61000-4-3<br />Voltage/current impulse level 3 IEC 61000-4-5 |
Relative humidity | 0…95 % without condensation or dripping water IEC 60068-2-3 | Ambient air temperature for operation | 104…140 °F (40…60 °C) with current derating of 2 % per °C)<br />14…104 °F (-10…40 °C) without derating) |
Ambient Air Temperature for Storage | -13…158 °F (-25…70 °C) | Operating altitude | <= 3280.84 ft (1000 m) without derating<br />> 3280.84...6561.68 ft (> 1000...2000 m) with current derating of 2.2 % per additional 100 m |
Specifications may be subject to change without notice