  • 1Prevents motor restarts if temperature rise is too high.
  • 2Configurable for high torque on starting and lower torque at the end for gradual loading.
  • 3Integrated PTC probes for motor thermal protection and analog thermal probe for starter protection.
  • 4Suitable for constant and variable torque applications, including centrifugal pumps and machines with high resistive torque.
  • 5Meets international standards including EN/IEC 60947-4-2, CSA, UL, and more.
Product Details
ATS48D22Y
schneider

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Range of Product
Altistart 48
Product or Component Type
Soft starter
Product destination
Asynchronous motors
Product Specific Application
Heavy duty industry and pumps
Device short name
ATS48
Utilisation category
AC-53A
Ue power supply voltage
208...690 V - 15...10 %
power supply frequency
50...60 Hz - 5...5 %
Motor power kW
11 kW 400 V for standard applications<br />11 kW 440 V for standard applications<br />11 kW 500 V for standard applications<br />11 kW 525 V for standard applications<br />11 kW 660 V for severe applications<br />15 kW 660 V for standard applications<br />15 kW 690 V for severe applications<br />4 kW 230 V for severe applications<br />9 kW 500 V for severe applications<br />9 kW 525 V for severe applications<br />7.5 kW 400 V for severe applications<br />7.5 kW 440 V for severe applications<br />18.5 kW 690 V for standard applications<br />5.5 kW 230 V for standard applications
Maximum Horse Power Rating
10 hp 460 V for severe applications<br />15 hp 460 V for standard applications<br />15 hp 575 V for severe applications<br />20 hp 575 V for standard applications<br />3 hp 208 V for severe applications<br />5 hp 208 V for standard applications<br />5 hp 230 V for severe applications<br />7.5 hp 230 V for standard applications
Device connection
In the motor supply line
Protection type
Phase failure line<br />Thermal protection motor<br />Thermal protection starter
Standards
EN/IEC 60947-4-2
Product Certifications
CSA<br />SEPRO<br />UL<br />GOST<br />NOM 117<br />TCF<br />CCC<br />C-tick<br />DNV
marking
CE
Discrete input number
5
Discrete input type
PTC, 750 Ohm 77 °F (25 °C)<br />Stop, Run, LI3, LI4) logic, <= 8 mA 4300 Ohm
Discrete input logic
Positive logic Stop, Run, LI3, LI4 < 5 V <= 2 mA > 11 V, >= 5 mA
Minimum switching current
10 mA 6 V DC relay outputs
Discrete output number
2
Discrete output type
LO1) logic output 0 V common configurable<br />LO2) logic output 0 V common configurable<br />R1) relay outputs fault relay NO<br />R2) relay outputs end of starting relay NO<br />R3) relay outputs motor powered NO
Analogue output type
Current output AO 0-20 mA or 4-20 mA 500 Ohm
communication port protocol
Modbus
Connector Type
1 RJ45
Communication data link
Serial
Physical interface
RS485 multidrop
Transmission Rate
4800, 9600 or 19200 bps
Function Available
External bypass (optional)
Operating position
Vertical +/- 10 degree
Height
10.8 in (275 mm)
Width
6.3 in (160 mm)
Depth
7.5 in (190 mm)
Net Weight
10.8 lb(US) (4.9 kg)
Electromagnetic compatibility
Conducted and radiated emissions level A IEC 60947-4-2<br />Conducted and radiated emissions level B IEC 60947-4-2<br />Damped oscillating waves level 3 IEC 61000-4-12<br />Electrostatic discharge level 3 IEC 61000-4-2<br />Immunity to electrical transients level 4 IEC 61000-4-4<br />Immunity to radiated radio-electrical interference level 3 IEC 61000-4-3<br />Voltage/current impulse level 3 IEC 61000-4-5
Relative humidity
0…95 % without condensation or dripping water EN/IEC 60068-2-3
Ambient air temperature for operation
104…140 °F (40…60 °C) with current derating of 2 % per °C)<br />14…104 °F (-10…40 °C) without derating)
Ambient Air Temperature for Storage
-13…158 °F (-25…70 °C)
Operating altitude
<= 3280.84 ft (1000 m) without derating<br />> 3280.84...6561.68 ft (> 1000...2000 m) with current derating of 2.2 % per additional 100 m