Product Model

ATS48M12Y

In Stock
Last updated: 2025/4/27
schneider ATS48M12Y

Selling Points

  • 1Advanced Torque Control System: The Altistart 48 torque control system ensures smooth starting and stopping of asynchronous motors without mechanical stress.
  • 2High Power Rating: Suitable for motors up to 1200 HP (at 575V) / 800 kW (at 525V) for standard applications and 1000 HP (at 575V) / 900 kW (at 690V) for severe applications.
  • 3Multi-Protocol Connectivity: Integrates with Modbus, Ethernet, Fipio, Profibus DP, and DeviceNet networks for seamless communication.
  • 4Robust Protection Features: Includes thermal protection of the motor, underload and overload protection with adjustable thresholds, and locked rotor protection.
  • 5Easy Integration: Simplified customization of settings using the built-in display or PowerSuite software, making it easy to integrate into various control systems.
Product Details
ATS48M12Y
schneider

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Range of Product
Altistart 48
Product or Component Type
Soft starter
Product destination
Asynchronous motors
Product Specific Application
Heavy duty industry and pumps
Device short name
ATS48
Utilisation category
AC-53A
Ue power supply voltage
208...690 V - 15...10 %
power supply frequency
50...60 Hz - 5...5 %
Motor power kW
250 kW 230 V for severe applications<br />355 kW 230 V for standard applications<br />500 kW 400 V for severe applications<br />630 kW 400 V for standard applications<br />630 kW 440 V for severe applications<br />630 kW 500 V for severe applications<br />630 kW 525 V for severe applications<br />710 kW 440 V for standard applications<br />800 kW 500 V for standard applications<br />800 kW 525 V for standard applications<br />900 kW 660 V for severe applications<br />900 kW 690 V for severe applications
Maximum Horse Power Rating
1000 hp 460 V for standard applications<br />1000 hp 575 V for severe applications<br />1200 hp 575 V for standard applications<br />350 hp 208 V for severe applications<br />350 hp 230 V for severe applications<br />400 hp 208 V for standard applications<br />450 hp 230 V for standard applications<br />800 hp 460 V for severe applications
Device connection
In the motor supply line
Protection type
Phase failure line<br />Thermal protection motor<br />Thermal protection starter
Standards
IEC 60947-4-2
Product Certifications
GOST<br />CSA<br />C-tick<br />UL<br />TCF<br />NOM 117<br />DNV<br />CCC<br />SEPRO
marking
CE
Discrete input number
5
Discrete input type
PTC, 750 Ohm 77 °F (25 °C)<br />Stop, Run, LI3, LI4) logic, <= 8 mA 4300 Ohm
Discrete input logic
Positive logic Stop, Run, LI3, LI4 < 5 V <= 2 mA > 11 V, >= 5 mA
Minimum switching current
10 mA 6 V DC relay outputs
Discrete output number
2
Discrete output type
LO1) logic output 0 V common configurable<br />LO2) logic output 0 V common configurable<br />R1) relay outputs fault relay NO<br />R2) relay outputs end of starting relay NO<br />R3) relay outputs motor powered NO
Analogue output type
Current output AO 0-20 mA or 4-20 mA 500 Ohm
communication port protocol
Modbus
Connector Type
1 RJ45
Communication data link
Serial
Physical interface
RS485 multidrop
Transmission Rate
4800, 9600 or 19200 bps
Function Available
External bypass (optional)
Operating position
Vertical +/- 10 degree
Height
35.04 in (890 mm)
Width
30.3 in (770 mm)
Depth
12.4 in (315 mm)
Net Weight
253.5 lb(US) (115 kg)
Electromagnetic compatibility
Conducted and radiated emissions level A IEC 60947-4-2<br />Damped oscillating waves level 3 IEC 61000-4-12<br />Electrostatic discharge level 3 IEC 61000-4-2<br />Immunity to electrical transients level 4 IEC 61000-4-4<br />Immunity to radiated radio-electrical interference level 3 IEC 61000-4-3<br />Voltage/current impulse level 3 IEC 61000-4-5
Relative humidity
0…95 % without condensation or dripping water IEC 60068-2-3
Ambient air temperature for operation
104…140 °F (40…60 °C) with current derating of 2 % per °C)<br />14…104 °F (-10…40 °C) without derating)
Ambient Air Temperature for Storage
-13…158 °F (-25…70 °C)
Operating altitude
<= 3280.84 ft (1000 m) without derating<br />> 3280.84...6561.68 ft (> 1000...2000 m) with current derating of 2.2 % per additional 100 m

Specifications may be subject to change without notice