Product Model

ATV11HU41M2E

In Stock
Last updated: 2025/4/27
schneider ATV11HU41M2E

Selling Points

  • 1High Power Conversion: Converts 1-phase to 3-phase power with 2.2kW main power.
  • 2Advanced Control Modes: Features built-in PID regulator and vector control mode without encoder.
  • 3Efficient Operation: Operates at 150% maximum number for 1 minute, ensuring reliable performance.
  • 4Compact Design: Measures 117 x 142 x 156 mm, with a weight of 1.8 kg.
  • 5Comprehensive Warranty: Covered by a 24-month warranty with the possibility of extension.
Product Details
ATV11HU41M2E
schneider

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Range of Product
Altivar 11
Product or Component Type
Variable speed drive
Product Specific Application
Simple machine
Component name
ATV11
Application market
European
Assembly style
With heat sink
EMC filter
Integrated
Built-in fan
With
Phase
1 phase
[Us] rated supply voltage
200...240 V - 15...10 %
Supply frequency
50...60 Hz - 5...5 %
Motor power kW
2.2 kW
Line current
20.8 A 230 V, Isc = 1 kA
Nominal output current
9.6 A 230 V motor 4 kHz
Maximum transient current
14.4 A 60 s
Power dissipation in W
96 W at nominal load
Switching frequency
2...16 kHz adjustable<br />4...16 kHz with derating factor
Braking torque
150 % of nominal motor torque with braking resistor at high inertia<br />20 % of nominal motor torque without braking resistor at no load<br />80 % of nominal motor torque with braking resistor at no load
Asynchronous motor control profile
Sensorless flux vector control with PWM type motor control signal
Electrical connection
Terminal 1.5 mm², AWG 14 AI1, RA-RC, LI1...LI4, DO)<br />Terminal 1.5 mm², AWG 14 L1, L2, L3, U, V, W, PA, PC)
Supply
Internal supply for logic inputs 15 V +/- 15 %) 100 A overload and short-circuit protection<br />Internal supply for reference potentiometer (2.2 to 10 kOhm) 5...5.25 VDC 10 A overload and short-circuit protection
Analogue input type
Configurable current AI1 4...20 mA 250 Ohm without adding resistor<br />Configurable voltage AI1 0...5 V 40000 Ohm only with internal supply<br />Configurable current AI1 0...20 mA 250 Ohm<br />Configurable voltage AI1 0...10 V 40000 Ohm
Sampling duration
AI1 20 ms analog<br />LI1...LI4 20 ms discrete
Response time
20 ms DO
Linearity error
DO +/- 1 % output<br />AI +/- 5 % input
Discrete input type
Assignable Ll1 forward 5000 Ohm 15 V 24 V<br />Assignable Ll2 reverse 5000 Ohm 15 V 24 V<br />Assignable Ll3/Ll4 4 preset speeds 5000 Ohm 15 V 24 V
Discrete input logic
Positive logic (source) LI1...LI4), < 5 V, > 11 V
Discrete output type
Assignable as external voltage DO 30 V max, 30 mA<br />Assignable as open collector logic output DO 100 Ohm, 50 mA max<br />Factory set as PWM open collector output DO at 2 kHz 10 mA max<br />Protected relay logic RA-RC 1 NO<br />Assignable as internal voltage DO
Minimum switching current
RA-RC 10 mA 24 V DC
Maximum switching current
2 A 250 V AC inductive cos phi = 0.4 7 ms RA-RC<br />2 A 30 V DC inductive cos phi = 0.4 7 ms RA-RC<br />5 A 250 V AC resistive cos phi = 1 0 ms RA-RC<br />5 A 30 V DC resistive cos phi = 1 0 ms RA-RC
Protection type
Line supply overvoltage drive<br />Line supply undervoltage drive<br />Overheating protection drive<br />Short-circuit between motor phases drive<br />Thermal protection motor<br />Overcurrent between output phases and earth drive
Frequency resolution
Display unit 0.1 Hz<br />Analog input converter A/D, 10 bits
Electromagnetic compatibility
1.2/50 µs - 8/20 µs surge immunity test level 3 EN/IEC 61000-4-5<br />Electrical fast transient/burst immunity test level 4 EN/IEC 61000-4-4<br />Electrostatic discharge immunity test level 3 EN/IEC 61000-4-2<br />Radiated radio-frequency electromagnetic field immunity test level 3 EN/IEC 61000-4-3
Maximum motor cable length
32.8 ft (10 m) without additional EMC filter from 2 to 16 kHz EN 55011 class A group 1<br />32.8 ft (10 m) without additional EMC filter from 2 to 16 kHz EN 55022 class A group 1<br />65.6 ft (20 m) with additional EMC filter from 2 to 16 kHz EN 55011 class B<br />16.4 ft (5 m) without additional EMC filter from 2 to 12 kHz EN 55011 class B<br />16.4 ft (5 m) without additional EMC filter from 2 to 12 kHz EN 55022 class B<br />164.04 ft (50 m) with additional EMC filter from 2 to 16 kHz EN 55011 class A group 1
Vibration resistance
1 gn 13…200 Hz)EN/IEC 60068-2-6<br />1.5 mm peak to peak 3…13 Hz)EN/IEC 60068-2-6
Shock resistance
15 gn 11 ms EN/IEC 60068-2-27
Relative humidity
5…93 % without condensation IEC 60068-2-3<br />5…93 % without dripping water IEC 60068-2-3
Ambient air temperature for operation
14…104 °F (-10…40 °C) without derating<br />104…122 °F (40…50 °C) by removing the protective cover from the top of the drive<br />122…140 °F (50…60 °C) by removing the protective cover from the top of the drive with current derating of 2.2 % per °C
Operating altitude
<= 3280.84 ft (1000 m) without derating<br />> 3280.84 ft (1000 m) with current derating 1 % per 100 m
Product destination
Asynchronous motors
Supply voltage limits
170…264 V
Network frequency limits
47.5…63 Hz
Speed drive output frequency
0…200 Hz
Nominal switching frequency
4 kHz
Speed range
1…20
Transient overtorque
150...170 % of nominal motor torque
Regulation loop
Factory-set with the speed loop stability and gain<br />Adjustable frequency<br />Possible correction for machines with high resistive torque/inertia/fast cycles
Motor slip compensation
Preset in factory<br />Adjustable
Prospective line Isc
1 kA
Output voltage
<= power supply voltage
Insulation
Electrical between power and control
Analogue input number
1
Discrete input number
4
Discrete output number
2
Acceleration and deceleration ramps
Linear from 0 to 99.9 s
Braking to standstill
By DC injection
Insulation resistance
> 500 MOhm
marking
CE
Operating position
Vertical +/- 10 degree
CAD overall width
4.6 in (117 mm)
CAD overall height
5.6 in (142 mm)
CAD overall depth
6.1 in (156 mm)
Outer dimension
142 x 117 x 156 mm
Net Weight
4.0 lb(US) (1.8 kg)
Standards
EN 50178
Product Certifications
CSA<br />C-tick<br />UL<br />N998
IP Degree of Protection
IP20
Ambient Air Temperature for Storage
-13…149 °F (-25…65 °C)
Variable speed drive application selection
Packaging conveyor
Motor power range AC-3
2.2…3 kW 200…240 V 1 phase
Motor starter type
Variable speed drive

Specifications may be subject to change without notice