Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Range of Product | Altivar Solar | Product or Component Type | Variable speed drive |
Product Specific Application | Pumping applications | Variant | Standard version |
Format of the drive | Compact | Mounting Mode | Wall mount |
communication port protocol | Modbus serial<br />CANopen | Option card | communication module, Ethernet IP/Modbus TCP |
[Us] rated supply voltage | 200...240 V - 15...10 % | Nominal output current | 66.0 A |
Motor power kW | 15.0 kW heavy duty | EMC filter | Without EMC filter |
IP degree of protection | IP20 | Discrete input number | 7 |
Discrete input type | STO safe torque off, 24 V DC1.5 kOhm<br />DI1...DI6 logic inputs, 24 V DC 30 V)<br />DI5 programmable as pulse input 0…30 kHz, 24 V DC 30 V) | Discrete input logic | Positive logic (source)<br />Negative logic (sink) |
Discrete output number | 3 | Discrete output type | Open collector DQ+ 0…1 kHz 30 V DC 100 mA<br />Open collector DQ- 0…1 kHz 30 V DC 100 mA |
Analogue input number | 3 | Analogue input type | AI1 voltage 0...10 V DC 30 kOhm 10 bits<br />AI2 bipolar differential voltage +/- 10 V DC 30 kOhm 10 bits<br />AI3 current 0...20 mA (or 4-20 mA, x-20 mA, 20-x mA or other patterns by configuration) 250 Ohm 10 bits |
Analogue output number | 1 | Analogue output type | Software-configurable current AQ1 0...20 mA 800 Ohm 10 bits<br />Software-configurable voltage AQ1 0...10 V DC 470 Ohm 10 bits |
Relay output number | 2 | Relay output type | Configurable relay logic R1A 1 NO 100000 cycles<br />Configurable relay logic R1B 1 NC 100000 cycles<br />Configurable relay logic R1C<br />Configurable relay logic R2A 1 NO 100000 cycles<br />Configurable relay logic R2C |
Maximum switching current | Relay output R1A, R1B, R1C resistive, cos phi = 1 3 A 250 V AC<br />Relay output R1A, R1B, R1C resistive, cos phi = 1 3 A 30 V DC<br />Relay output R1A, R1B, R1C, R2A, R2C inductive, cos phi = 0.4 7 ms 2 A 250 V AC<br />Relay output R1A, R1B, R1C, R2A, R2C inductive, cos phi = 0.4 7 ms 2 A 30 V DC<br />Relay output R2A, R2C resistive, cos phi = 1 5 A 250 V AC<br />Relay output R2A, R2C resistive, cos phi = 1 5 A 30 V DC | Minimum switching current | Relay output R1A, R1B, R1C, R2A, R2C 5 mA 24 V DC |
Method of access | Slave CANopen | Number of addresses | 1…247<br />1…127 |
Data format | 8 bits, configurable odd, even or no parity | Type of polarization | No impedance |
4 quadrant operation possible | True | Asynchronous motor control profile | Voltage/frequency ratio, 5 points<br />Flux vector control without sensor, standard<br />Voltage/frequency ratio - Energy Saving, quadratic U/f<br />Flux vector control without sensor - Energy Saving<br />Voltage/frequency ratio, 2 points |
Synchronous motor control profile | Vector control without sensor | Transient overtorque | 170…200 % of nominal motor torque |
Maximum output frequency | 0.599 kHz | Acceleration and deceleration ramps | Linear<br />U<br />S<br />CUS<br />Ramp switching<br />Acceleration/deceleration ramp adaptation<br />Acceleration/deceleration automatic stop with DC injection<br />Automatic adaptation of ramp if braking capacity exceeded, by using resistor<br />Linear adjustable separately from 0.01 to 6000 s |
Motor slip compensation | Automatic whatever the load<br />Adjustable 0...300 %<br />Not available in voltage/frequency ratio (2 or 5 points) | Switching frequency | 2...16 kHz adjustable<br />4...16 kHz with derating factor |
Nominal switching frequency | 4 kHz | Braking to standstill | By DC injection |
Brake chopper integrated | True | Line current | 79.7 A 200 V heavy duty)<br />67.1 A 240 V heavy duty) |
Maximum Input Current per Phase | 79.7 A | Maximum output voltage | 240 V |
Apparent power | 27.9 kVA 240 V heavy duty) | Maximum transient current | 99.0 A 60 s |
Short-circuit protection | thermal protection | Network Frequency | 50-60 Hz |
Relative symmetric network frequency tolerance | 5 % | Prospective line Isc | 22 kA |
Base load current at high overload | 8.0 A | Power dissipation in W | Fan 551 W 200 V 4 kHz |
Electrical connection | Screw terminal 0.5...1.5 mm² analog input<br />Screw terminal analog output<br />Screw terminal | With safety function Safely Limited Speed (SLS) | True |
With safety function Safe brake management (SBC/SBT) | False | With safety function Safe Operating Stop (SOS) | False |
With safety function Safe Position (SP) | False | With safety function Safe programmable logic | False |
With safety function Safe Speed Monitor (SSM) | False | With safety function Safe Stop 1 (SS1) | True |
With sft fct Safe Stop 2 (SS2) | False | With safety function Safe torque off (STO) | True |
With safety function Safely Limited Position (SLP) | False | With safety function Safe Direction (SDI) | False |
Protection type | Input phase breaks drive<br />Overcurrent between output phases and earth drive<br />Overheating protection drive<br />Short-circuit between motor phases drive<br />Thermal protection drive | Width | 7.09 in (180 mm) |
Height | 13.0 in (330 mm) | Depth | 7.8 in (198.0 mm) |
Net Weight | 15.2 lb(US) (6.9 kg) | Power factor | 0.618 at 230 V |
Braking torque | 170 % with braking resistor | Local signalling | for drive fault 1 LED (red)<br /> for CANopen error 1 LED (red)<br /> for CANopen run 1 LED (green) |
Operating altitude | 3280.84...6561.68 ft (1000...2000 m) with current derating 1 % per 100 m<br /><= 3280.84 ft (1000 m) without derating | Operating position | Vertical +/- 10 degree |
Product Certifications | CE<br />UR<br />UKCA<br />RCM | Marking | CE<br />UR<br />UKCA<br />RCM |
Standards | IEC 61800-5-1 | Assembly style | With heat sink |
Electromagnetic compatibility | Electrostatic discharge immunity test level 3 IEC 61000-4-2<br />Radiated radio-frequency electromagnetic field immunity test level 3 IEC 61000-4-3<br />Electrical fast transient/burst immunity test level 4 IEC 61000-4-4<br />1.2/50 µs - 8/20 µs surge immunity test level 3 IEC 61000-4-5<br />Conducted radio-frequency immunity test level 3 IEC 61000-4-6<br />Voltage dips and interruptions immunity test IEC 61000-4-11 | Environmental class (during operation) | Class 3C3 according to IEC 60721-3-3<br />Class 3S2 according to IEC 60721-3-3 |
Maximum acceleration under shock impact (during operation) | 150 m/s² at 11 ms | Maximum acceleration under vibrational stress (during operation) | 10 m/s² at 13...200 Hz |
Maximum deflection under vibratory load (during operation) | 1.5 mm at 2...13 Hz | Permitted relative humidity (during operation) | Class 3K5 according to EN 60721-3 |
Volume of cooling air | 41211.6 Gal/hr(US) (156.0 m3/h) | Overvoltage category | II |
Regulation loop | Adjustable PID regulator | Speed accuracy | +/- 10 % of nominal slip 0.2 Tn to Tn |
Noise level | 58 dB | Pollution degree | 2 |
Ambient air transport temperature | -13…158 °F (-25…70 °C) | Ambient air temperature for operation | 14…122 °F (-10…50 °C) without derating<br />122…140 °F (50…60 °C) with derating factor |
Ambient Air Temperature for Storage | -13…158 °F (-25…70 °C) |