Product Details
ATV6000D790A2424ND
schneider

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Range of Product
Altivar Process ATV6000
Product or Component Type
Medium voltage variable speed drive
Device short name
ATV6000
Product Specific Application
Process and utilities
Assembly style
In floor-standing enclosure
Provided Equipment
Cooling fans<br />Human machine interface<br />Plinth<br />Medium voltage arrestors<br />Power cells<br />Enclosure<br />Phase-shifting transformer
Colour of enclosure
Light grey RAL 7035)
IP degree of protection
IP31 conforming to IEC 60529
Type of cooling
Forced convection
input type
54 pulse diode rectifier bridge
Output type
IGBT inverter cells multilevel PWM
[Us] rated supply voltage
2.4 kV +/- 10 %
Supply frequency
50 Hz +/- 5 %
Phase
3 phase
Output voltage
<= power supply voltage
Permissible temporary current boost
1.2 x In 60 s normal duty)<br />1.5 x In 3 s normal duty)<br />1.5 x In 60 s heavy duty)<br />1.8 x In 3 s heavy duty)
Speed drive output frequency
0.1…120 Hz
Frequency resolution
0.01 Hz
Product destination
Synchronous motors<br />Asynchronous motors<br />Permanent magnet motors
Asynchronous motor control profile
Closed loop vector control<br />U/F vector control<br />Energy saving control<br />Vector control with slip compensation in open loop
Synchronous motor control profile
Permanent magnet control in open loop<br />Permanent magnet control in close loop<br />Line start permanent magnet motor
Apparent power
790 kVA
Maximum THDI
<3 % IEEE 519-1992
Power factor
96
Motor power kW
550.0 kW heavy duty<br />630.0 kW normal duty
Maximum Horse Power Rating
737.0 hp heavy duty<br />844.0 hp normal duty
Continuous output current
160.0 A heavy duty<br />181.3 A normal duty
Maximum transient current
240.0 A 3 s heavy duty)<br />217.5 A 3 s normal duty)
Line current
165.0 A heavy duty<br />217.5 A normal duty
Energy efficiency ratio
0.985 inverter<br />0.965 total drive including transformer
Cable entry
Bottom
Noise level
90.3 dB
EMC filter
Integrated IEC 61800-3 category C3 control<br />Integrated IEC 61800-3 category C4 Power
Display type
10 inch LCD touch screen multi-language
Protection type
Line supply overvoltage drive<br />Line supply undervoltage drive<br />Line supply phase loss drive<br />Overvoltages on the DC bus drive<br />Thermal overload for transformer drive<br />Cabinet overheating drive<br />Overcurrent drive<br />Overload drive<br />Short-circuit protection drive<br />IGBT for each cell drive<br />Thermal protection motor<br />Motor phase break motor<br />Motor earth fault motor<br />Break on the control circuit drive<br />Fan monitoring drive
Option card
Slot A communication module Profibus DP V1<br />Slot A communication module PROFINET<br />Slot A communication module DeviceNet<br />Slot A communication module CANopen daisy chain RJ45<br />Slot A communication module CANopen SUB-D 9<br />Slot A communication module CANopen screw terminals<br />Slot A communication module EtherCAT<br />Slot B 5/12 V digital encoder interface module<br />Slot B analog encoder interface module<br />Slot B resolver encoder interface module<br />Slot B HTL encoder interface module<br />Slot A/slot B digital and analog I/O extension module<br />Slot A/slot B output relay extension module
Connector type
2 RJ45 on the control block)Ethernet IP/Modbus TCP<br />1 RJ45 on the control block)Modbus serial
communication port protocol
Ethernet IP/Modbus TCP
Supply
Internal supply for digital inputs and PoE 24 V DC 21…27 V, <200 mA overload and short-circuit protection<br />Internal supply for reference potentiometer (1 to 10 kOhm) 10.5 V DC +/- 5 %, <10 mA overload and short-circuit protection<br />External supply for digital inputs 24 V DC 19…30 V<br />External supply for control circuit 100...240 V AC 47...63 Hz<br />External supply for control circuit 120...370 V DC +/- 10 % 1 kVA<br />Auxiliary power supply 230 V AC +/- 10 %<br />External supply for cooling fan 400 V AC +/- 10 %
Analogue input type
configurable voltage 0...10 V DC 30 kOhm 12 bits<br /> configurable current 0...20 mA 250 Ohm 12 bits
Discrete input number
10
Discrete input type
DI1...DI8 programmable, 24 V DC <= 30 V)3.5 kOhm<br />DI7, DI8 programmable as pulse input 0…30 kHz, 24 V DC <= 30 V)<br />POEA, POEB PWM output enable, 24 V DC <= 30 V)> 2.2 kOhm
Analogue output number
2
Analogue output type
Configurable voltage 0...10 V DC 470 Ohm 10 bits<br />Configurable current 0...20 mA 500 Ohm 10 bits
Discrete output number
2
Discrete output type
Logic output <= 30 V DC 100 mA
Relay output number
3
Relay output type
Configurable relay logic R1 fault relay NO/NC<br />Configurable relay logic R2 sequence relay NO<br />Configurable relay logic R3 sequence relay NO
Isolation
Electrical between power and control
Overvoltage category
II IEC 61800-5-1 motor side<br />III IEC 61800-5-1 line side<br />III IEC 61800-5-1 low voltage connections
Electromagnetic compatibility
Electrostatic discharge immunity test level 3 IEC 61000-4-2<br />Radiated radio-frequency electromagnetic field immunity test level 3 IEC 61000-4-3<br />Electrical fast transient/burst immunity test level 4 IEC 61000-4-4<br />1.2/50 µs - 8/20 µs surge immunity test level 3 IEC 61000-4-5<br />Conducted radio-frequency immunity test level 3 IEC 61000-4-6
Pollution degree
2 IEC 61800-5-1
Environmental characteristic
3K3 IEC 60721-3-3<br />3B1 IEC 60721-3-3<br />3C2 IEC 60721-3-3<br />3S1 IEC 60721-3-3<br />3M1 IEC 60721-3-3
Relative humidity
5…95 % without condensation IEC 60068-2-3
Ambient air temperature for operation
32.0000000000…104.0000000000 °F (0…40 °C)<br />104.0000000000…122.0000000000 °F (40…50 °C) with derating factor<br />-13.0000000000…158.0000000000 °F (-25…70 °C) during transport
Ambient Air Temperature for Storage
32…122 °F (0…50 °C)
Operating altitude
<= 3280.84 ft (1000 m) without derating<br />3280.84...6561.68 ft (1000...2000 m) with derating factor
Standards
IEC 61800-3<br />EN/IEC 61800-4<br />IEC 61800-5-1<br />IEC 60529<br />IEEE 519:1992<br />EN/IEC 60076<br />UL 347A
marking
CULus<br />CE<br />UKCA

Specifications may be subject to change without notice