Product Model
ATV61WD37N4U

Selling Points
- 1Equipped with a 37 kW motor power rating, suitable for demanding applications.
- 2Includes a Level 3 EMC filter to minimize electromagnetic interference and ensure stable operation.
- 3Integrated heat sink assembly for efficient thermal management and prolonged component lifespan.
- 4Supports CANopen and Modbus communication protocols for easy integration into industrial networks.
- 5Designed for pumping and ventilation systems, with the ability to handle various industrial applications requiring precise motor control and speed regulation.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Range of Product | Altivar 61 | Product or Component Type | Variable speed drive |
Product Specific Application | Pumping and ventilation machine | Component name | ATV61 |
Motor power kW | 37 kW, 3 phase 380...480 V | Maximum Horse Power Rating | 50 hp, 3 phase 380...480 V |
power supply voltage | 380...480 V - 15...10 % | supply number of phases | 3 phase |
Line current | 56.8 A 480 V 3 phase 37 kW / 50 hp<br />69.5 A 380 V 3 phase 37 kW / 50 hp | EMC filter | Class C2 EMC filter integrated |
Variant | With EMC plate conforming to NEMA type 12 standard | Assembly style | Enclosed |
Apparent power | 45.7 kVA 380 V 3 phase 37 kW / 50 hp | maximum prospective line Isc | 22 kA 3 phase |
Maximum transient current | 78.6 A 60 s, 3 phase | Nominal switching frequency | 4 kHz |
Switching frequency | 2...16 kHz adjustable<br />8...16 kHz with derating factor | asynchronous motor control | Voltage/frequency ratio, 2 points<br />Voltage/frequency ratio, 5 points<br />Voltage/frequency ratio - Energy Saving, quadratic U/f<br />Flux vector control without sensor, standard |
Synchronous motor control profile | Vector control without sensor, standard | communication port protocol | Modbus<br />CANopen |
Type of polarization | No impedance Modbus | Option card | Communication card APOGEE FLN<br />Communication card BACnet<br />Communication card CC-Link<br />Controller inside programmable card<br />Communication card DeviceNet<br />Communication card EtherNet/IP<br />Communication card Fipio<br />I/O extension card<br />Communication card Interbus-S<br />Communication card LonWorks<br />Communication card METASYS N2<br />Communication card Modbus Plus<br />Communication card Modbus TCP<br />Communication card Modbus/Uni-Telway<br />Multi-pump card<br />Communication card Profibus DP<br />Communication card Profibus DP V1 |
Product destination | Synchronous motors<br />Asynchronous motors | power supply voltage limits | 323…528 V |
power supply frequency | 50...60 Hz - 5...5 % | power supply frequency limits | 47.5...63 Hz |
Continuous output current | 65 A 4 kHz, 460 V - 3 phase<br />71.5 A 4 kHz, 380 V - 3 phase | Output frequency | 0.1…599 Hz |
Speed range | 1…100 in open-loop mode, without speed feedback | Speed accuracy | +/- 10 % of nominal slip 0.2 Tn to Tn without speed feedback |
Torque accuracy | +/- 15 % in open-loop mode, without speed feedback | Transient overtorque | 130 % of nominal motor torque +/- 10 % 60 s |
Braking torque | <= 125 % with braking resistor<br />30 % without braking resistor | Regulation loop | Frequency PI regulator |
Motor slip compensation | Automatic whatever the load<br />Adjustable<br />Can be suppressed<br />Not available in voltage/frequency ratio (2 or 5 points) | diagnostic | for drive voltage 1 LED (red) |
Output voltage | <= power supply voltage | electrical isolation | Between power and control terminals |
type of cable for mounting in an enclosure | With an IP21 or an IP31 kit 3 IEC cable 104 °F (40 °C), copper 70 °C / PVC<br />With UL Type 1 kit 3 UL 508 cable 104 °F (40 °C), copper 75 °C / PVC<br />Without mounting kit 1 IEC cable 113 °F (45 °C), copper 70 °C / PVC<br />Without mounting kit 1 IEC cable 113 °F (45 °C), copper 90 °C / XLPE/EPR | Electrical connection | Terminal 2.5 mm² / AWG 14 AI1-/AI1+, AI2, AO1, R1A, R1B, R1C, R2A, R2B, LI1...LI6, PWR)<br />Terminal 50 mm² / AWG 1/0 L1/R, L2/S, L3/T, U/T1, V/T2, W/T3, PC/-, PO, PA/+, PA, PB) |
Tightening torque | 5.3 lbf.in (0.6 N.m) AI1-/AI1+, AI2, AO1, R1A, R1B, R1C, R2A, R2B, LI1...LI6, PWR)<br />106.2 lbf.in (12 N.m), 106.2 lb.in L1/R, L2/S, L3/T, U/T1, V/T2, W/T3, PC/-, PO, PA/+, PA, PB) | Supply | Internal supply for reference potentiometer (1 to 10 kOhm) 10.5 V DC, +/- 5 %, <10 mA overload and short-circuit protection<br />Internal supply 24 V DC 21…27 V), <200 mA overload and short-circuit protection<br />External supply 24 V DC 19…30 V) |
Analogue input number | 2 | Analogue input type | AI1-/Al1+ bipolar differential voltage +/- 10 V DC 24 V max 11 bits + sign<br />AI2 software-configurable current 0...20 mA 242 Ohm 11 bits<br />AI2 software-configurable voltage 0...10 V DC 24 V max 30000 Ohm 11 bits |
sampling time | 2 ms +/- 0.5 ms AI1-/Al1+) - analog input<br />2 ms +/- 0.5 ms Al2) - analog input<br />2 ms +/- 0.5 ms AO1) - analog output<br />2 ms +/- 0.5 ms LI1...LI5) - discrete input<br />2 ms +/- 0.5 ms LI6)if configured as logic input - discrete input | absolute accuracy precision | +/- 0.6 % AI1-/Al1+) for a temperature variation 60 °C<br />+/- 0.6 % AI2) for a temperature variation 60 °C<br />+/- 1 % AO1) for a temperature variation 60 °C |
Linearity error | +/- 0.15 % of maximum value AI1-/Al1+)<br />+/- 0.15 % of maximum value AI2)<br />+/- 0.2 % AO1) | Analogue output number | 1 |
Analogue output type | AO1 software-configurable current 0...20 mA 500 Ohm 10 bits<br />AO1 software-configurable voltage 0...10 V DC 470 Ohm 10 bits<br />AO1 software-configurable logic output 10 V, 20 mA | Discrete output number | 2 |
Discrete output type | Configurable relay logic R1A, R1B, R1C) NO/NC - 100000 cycles<br />Configurable relay logic R2A, R2B) NO - 100000 cycles | maximum response time | <= 100 ms in STO (Safe Torque Off)<br />R1A, R1B, R1C <= 7 ms +/- 0.5 ms<br />R2A, R2B <= 7 ms +/- 0.5 ms |
Minimum switching current | 3 mA 24 V DC configurable relay logic | Maximum switching current | R1, R2 2 A 250 V AC inductive, cos phi = 0.4 7 ms<br />R1, R2 2 A 30 V DC inductive, cos phi = 0.4 7 ms<br />R1, R2 5 A 250 V AC resistive, cos phi = 1 0 ms<br />R1, R2 5 A 30 V DC resistive, cos phi = 1 0 ms |
Discrete input number | 7 | Discrete input type | Programmable LI1...LI5) 24 V DC <= 30 V)level 1 PLC - 3500 Ohm<br />Switch-configurable LI6) 24 V DC <= 30 V)level 1 PLC - 3500 Ohm<br />Switch-configurable PTC probe LI6)0…6 - 1500 Ohm<br />Safety input PWR) 24 V DC <= 30 V) - 1500 Ohm |
Discrete input logic | Negative logic (sink) LI1...LI5), > 16 V, < 10 V<br />Positive logic (source) LI1...LI5), < 5 V, > 11 V<br />Negative logic (sink) LI6)if configured as logic input, > 16 V, < 10 V<br />Positive logic (source) LI6)if configured as logic input, < 5 V, > 11 V | Acceleration and deceleration ramps | Linear adjustable separately from 0.01 to 9000 s<br />S, U or customized<br />Automatic adaptation of ramp if braking capacity exceeded, by using resistor |
Braking to standstill | By DC injection | Protection type | Against exceeding limit speed drive<br />Against input phase loss drive<br />Break on the control circuit drive<br />Input phase breaks drive<br />Line supply overvoltage drive<br />Line supply undervoltage drive<br />Overcurrent between output phases and earth drive<br />Overheating protection drive<br />Overvoltages on the DC bus drive<br />Power removal drive<br />Short-circuit between motor phases drive<br />Thermal protection drive<br />Motor phase break motor<br />Power removal motor<br />Thermal protection motor |
Insulation resistance | > 1 mOhm 500 V DC for 1 minute to earth | Frequency resolution | Analog input 0.024/50 Hz<br />Display unit 0.1 Hz |
Connector type | 1 RJ45 on front face)Modbus<br />1 RJ45 on terminal)Modbus<br />Male SUB-D 9 on RJ45CANopen | Physical interface | 2-wire RS 485 Modbus |
Transmission frame | RTU Modbus | Transmission rate | 4800 bps, 9600 bps, 19200 bps, 38.4 Kbps Modbus on terminal<br />9600 bps, 19200 bps Modbus on front face<br />20 kbps, 50 kbps, 125 kbps, 250 kbps, 500 kbps, 1 Mbps CANopen |
Data format | 8 bits, 1 stop, even parity Modbus on front face<br />8 bits, odd even or no configurable parity Modbus on terminal | Number of addresses | 1…127 CANopen<br />1…247 Modbus |
Method of access | Slave CANopen | marking | CE |
Operating position | Vertical +/- 10 degree | Net Weight | 141.10 lb(US) (64 kg) |
Width | 11.2 in (285 mm) | Height | 34.6 in (880 mm) |
Depth | 13.5 in (343 mm) | Noise level | 64 dB 86/188/EEC |
Dielectric strength | 3535 V DC between earth and power terminals<br />5092 V DC between control and power terminals | Electromagnetic compatibility | Conducted radio-frequency immunity test level 3 IEC 61000-4-6<br />Electrical fast transient/burst immunity test level 4 IEC 61000-4-4<br />Electrostatic discharge immunity test level 3 IEC 61000-4-2<br />Radiated radio-frequency electromagnetic field immunity test level 3 IEC 61000-4-3<br />Voltage dips and interruptions immunity test IEC 61000-4-11 |
Standards | EN 61800-3 environments 1 category C2<br />IEC 60721-3-3 class 3C1<br />EN/IEC 61800-5-1<br />EN 55011 class A group 1<br />IEC 60721-3-3 class 3S2<br />UL Type 12<br />EN 61800-3 environments 2 category C2<br />EN/IEC 61800-3 | Product Certifications | NOM 117<br />DNV<br />C-tick<br />UL<br />CSA<br />GOST |
Pollution degree | 3 EN/IEC 61800-5-1<br />3 UL 840 | degree of proctection | IP54 EN/IEC 60529<br />IP54 EN/IEC 61800-5-1<br />IP54 UL Type 12 |
Vibration resistance | 1 gn 13…200 Hz)EN/IEC 60068-2-6<br />1.5 mm peak to peak 3…13 Hz)EN/IEC 60068-2-6 | Shock resistance | 15 gn 11 ms EN/IEC 60068-2-27 |
Relative humidity | 5…95 % without condensation IEC 60068-2-3<br />5…95 % without dripping water IEC 60068-2-3 | Ambient air temperature for operation | 14…104 °F (-10…40 °C) without derating)<br />14…122 °F (-10…50 °C) with derating factor) |
Ambient Air Temperature for Storage | -13…158 °F (-25…70 °C) | Operating altitude | <= 3280.84 ft (1000 m) without derating<br />3280.84...9842.52 ft (1000...3000 m) with current derating 1 % per 100 m |
Specifications may be subject to change without notice