Product Model
ATV630D18N4

Selling Points
- 118.5 kW (25 HP) for heavy-duty applications.
- 2Operates on 380-480V, suitable for various electrical environments.
- 3IP21 rating for protection against vertical falling water and hazardous parts.
- 4Supports Modbus TCP, Modbus serial, and Ethernet communication protocols.
- 5Forced convection cooling and robust NEMA 1 enclosure ensure long-lasting performance.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Range of Product | Altivar Process ATV600 | Product or Component Type | Variable speed drive |
Product Specific Application | Process and utilities | Device short name | ATV630 |
Variant | Standard version | Product destination | Asynchronous motors<br />Synchronous motors |
EMC filter | Integrated 164.04 ft (50 m) IEC 61800-3 category C2<br />Integrated 492.1 ft (150 m) IEC 61800-3 category C3 | IP degree of protection | IP21IEC 61800-5-1<br />IP21IEC 60529 |
[Us] rated supply voltage | 380...480 V - 15...10 % | Degree of protection | UL type 1 UL 508C |
Type of cooling | Forced convection | Supply frequency | 50...60 Hz - 5...5 % |
Motor power kW | 18.5 kW normal duty)<br />15 kW heavy duty) | Maximum Horse Power Rating | 25 hp normal duty<br />20 hp heavy duty |
Line current | 33.4 A 380 V normal duty)<br />28.9 A 480 V normal duty)<br />27.7 A 380 V heavy duty)<br />24.4 A 480 V heavy duty) | Prospective line Isc | 50 kA |
Apparent power | 24 kVA 480 V normal duty)<br />20.3 kVA 480 V heavy duty) | Continuous output current | 39.2 A 4 kHz normal duty<br />31.7 A 4 kHz heavy duty |
Asynchronous motor control profile | Optimized torque mode<br />Variable torque standard<br />Constant torque standard | Synchronous motor control profile | Permanent magnet motor<br />Synchronous reluctance motor |
Speed drive output frequency | 0.1…500 Hz | Nominal switching frequency | 4 kHz |
Switching frequency | 2...12 kHz adjustable<br />4...12 kHz with derating factor | Safety function | STO (safe torque off) SIL 3 |
Discrete input logic | Positive logic (source) DI1...DI8), < 5 V, > 11 V<br />Negative logic (sink) DI1...DI8), > 16 V, < 10 V | communication port protocol | Modbus TCP<br />Modbus serial<br />Ethernet |
Option card | Slot A communication module, Profibus DP V1<br />Slot A communication module, PROFINET<br />Slot A communication module, DeviceNet<br />Slot A communication module, Modbus TCP/EtherNet/IP<br />Slot A communication module, CANopen daisy chain RJ45<br />Slot A communication module, CANopen SUB-D 9<br />Slot A communication module, CANopen screw terminals<br />Slot A/slot B digital and analog I/O extension module<br />Slot A/slot B output relay extension module<br />Slot A communication module, Ethernet IP/Modbus TCP/MD-Link<br /> communication module, BACnet MS/TP<br /> communication module, Ethernet Powerlink | Mounting Mode | Wall mount |
Maximum transient current | 43.1 A 60 s normal duty)<br />47.6 A 60 s heavy duty) | Phase | 3 phase |
Discrete output number | 0 | Discrete output type | Relay outputs R1A, R1B, R1C 250 V AC 3000 mA<br />Relay outputs R1A, R1B, R1C 30 V DC 3000 mA<br />Relay outputs R2A, R2C 250 V AC 5000 mA<br />Relay outputs R2A, R2C 30 V DC 5000 mA<br />Relay outputs R3A, R3C 250 V AC 5000 mA<br />Relay outputs R3A, R3C 30 V DC 5000 mA |
Output voltage | <= power supply voltage | Permissible temporary current boost | 1.1 x In 60 s normal duty)<br />1.5 x In 60 s heavy duty) |
Motor slip compensation | Automatic whatever the load<br />Adjustable<br />Not available in permanent magnet motor law<br />Can be suppressed | Acceleration and deceleration ramps | Linear adjustable separately from 0.01...9999 s |
Physical interface | Ethernet<br />2-wire RS 485 | Braking to standstill | By DC injection |
Protection type | Thermal protection motor<br />Safe torque off motor<br />Motor phase break motor<br />Thermal protection drive<br />Safe torque off drive<br />Overheating drive<br />Overcurrent between output phases and earth drive<br />Overload of output voltage drive<br />Short-circuit protection drive<br />Motor phase break drive<br />Overvoltages on the DC bus drive<br />Line supply overvoltage drive<br />Line supply undervoltage drive<br />Line supply phase loss drive<br />Overspeed drive<br />Break on the control circuit drive | Transmission Rate | 10, 100 Mbits<br />4800 bps, 9600 bps, 19200 bps, 38.4 Kbps |
Frequency resolution | Display unit 0.1 Hz<br />Analog input 0.012/50 Hz | Transmission frame | RTU |
Electrical connection | Control removable screw terminals 0.5...1.5 mm² AWG 20...AWG 16<br />Line side screw terminal 10...16 mm² AWG 8...AWG 6<br />Motor screw terminal 10...16 mm² AWG 8...AWG 6 | Connector type | RJ45 on the remote graphic terminal)Ethernet/Modbus TCP<br />RJ45 on the remote graphic terminal)Modbus serial |
Data format | 8 bits, configurable odd, even or no parity | Type of polarization | No impedance |
Exchange mode | Half duplex, full duplex, autonegotiation Ethernet/Modbus TCP | Number of addresses | 1…247 Modbus serial |
Method of access | Slave Modbus TCP | Supply | External supply for digital inputs 24 V DC 19…30 V), <1.25 mA overload and short-circuit protection<br />Internal supply for reference potentiometer (1 to 10 kOhm) 10.5 V DC +/- 5 %, <10 mA overload and short-circuit protection<br />Internal supply for digital inputs and STO 24 V DC 21…27 V), <200 mA overload and short-circuit protection |
Local signalling | for local diagnostic 3 LEDs<br /> for embedded communication status 3 LEDs (dual colour)<br /> for communication module status 4 LEDs (dual colour)<br /> for presence of voltage 1 LED (red) | Width | 8.3 in (211 mm) |
Height | 21.5 in (546 mm) | Depth | 9.1 in (232 mm) |
Net Weight | 31.3 lb(US) (14.2 kg) | Analogue input number | 3 |
Analogue input type | AI1, AI2, AI3 software-configurable voltage 0...10 V DC 31.5 kOhm 12 bits<br />AI1, AI2, AI3 software-configurable current 0...20 mA 250 Ohm 12 bits<br />AI2 voltage analog input - 10...10 V DC 31.5 kOhm 12 bits | Discrete input number | 8 |
Discrete input type | DI7, DI8 programmable as pulse input 0…30 kHz, 24 V DC <= 30 V) | Input compatibility | DI1...DI6 discrete input level 1 PLC IEC 61131-2<br />DI5, DI6 discrete input level 1 PLC IEC 65A-68<br />STOA, STOB discrete input level 1 PLC IEC 61131-2 |
Analogue output number | 2 | Analogue output type | Software-configurable voltage AQ1, AQ2 0...10 V DC 470 Ohm 10 bits<br />Software-configurable current AQ1, AQ2 0...20 mA 10 bits<br />Software-configurable current DQ-, DQ+ 30 V DC<br />Software-configurable current DQ-, DQ+ 100 mA |
Sampling duration | 2 ms +/- 0.5 ms DI1...DI4) - discrete input<br />5 ms +/- 1 ms DI5, DI6) - discrete input<br />5 ms +/- 0.1 ms AI1, AI2, AI3) - analog input<br />10 ms +/- 1 ms AO1) - analog output | Accuracy | +/- 0.6 % AI1, AI2, AI3 for a temperature variation 60 °C analog input<br />+/- 1 % AO1, AO2 for a temperature variation 60 °C analog output |
Linearity error | AI1, AI2, AI3 +/- 0.15 % of maximum value analog input<br />AO1, AO2 +/- 0.2 % analog output | Relay output number | 3 |
Relay output type | Configurable relay logic R1 fault relay NO/NC 100000 cycles<br />Configurable relay logic R2 sequence relay NO 100000 cycles<br />Configurable relay logic R3 sequence relay NO 100000 cycles | Refresh time | Relay output R1, R2, R3)5 ms +/- 0.5 ms) |
Minimum switching current | Relay output R1, R2, R3 5 mA 24 V DC | Maximum switching current | Relay output R1, R2, R3 resistive, cos phi = 1 3 A 250 V AC<br />Relay output R1, R2, R3 resistive, cos phi = 1 3 A 30 V DC<br />Relay output R1, R2, R3 inductive, cos phi = 0.4 7 ms 2 A 250 V AC<br />Relay output R1, R2, R3 inductive, cos phi = 0.4 7 ms 2 A 30 V DC |
Isolation | Between power and control terminals | Maximum output frequency | 500 kHz |
Maximum Input Current per Phase | 33.4 A | Variable speed drive application selection | Building - HVAC compressor centrifugal<br />Food and beverage processing other application<br />Mining mineral and metal fan<br />Mining mineral and metal pump<br />Oil and gas fan<br />Water and waste water other application<br />Building - HVAC screw compressor<br />Food and beverage processing pump<br />Food and beverage processing fan<br />Food and beverage processing atomization<br />Oil and gas electro submersible pump (ESP)<br />Oil and gas water injection pump<br />Oil and gas jet fuel pump<br />Oil and gas compressor for refinery<br />Water and waste water centrifuge pump<br />Water and waste water positive displacement pump<br />Water and waste water electro submersible pump (ESP)<br />Water and waste water screw pump<br />Water and waste water lobe compressor<br />Water and waste water screw compressor<br />Water and waste water compressor centrifugal<br />Water and waste water fan<br />Water and waste water conveyor<br />Water and waste water mixer |
Motor power range AC-3 | 15…25 kW 380…440 V 3 phase<br />15…25 kW 480…500 V 3 phase | Quantity per Set | 1 |
enclosure mounting | Wall mounted | Insulation resistance | > 1 MOhm 500 V DC for 1 minute to earth |
Noise level | 59.5 dB | Power dissipation in W | Natural convection 67 W 380 V 4 kHz<br />Forced convection 460 W 380 V 4 kHz |
Volume of cooling air | 56798.008 Gal/hr(US) (215 m3/h) | Operating position | Vertical +/- 10 degree |
Maximum THDI | <48 % from 80...100 % of load IEC 61000-3-12 | Electromagnetic compatibility | Electrostatic discharge immunity test level 3 IEC 61000-4-2<br />Radiated radio-frequency electromagnetic field immunity test level 3 IEC 61000-4-3<br />Electrical fast transient/burst immunity test level 4 IEC 61000-4-4<br />1.2/50 µs - 8/20 µs surge immunity test level 3 IEC 61000-4-5<br />Conducted radio-frequency immunity test level 3 IEC 61000-4-6 |
Pollution degree | 2 | Vibration resistance | 1.5 mm peak to peak 2…13 Hz)IEC 60068-2-6<br />1 gn 13…200 Hz)IEC 60068-2-6 |
Shock resistance | 15 gn 11 ms IEC 60068-2-27 | Relative humidity | 5…95 % without condensation IEC 60068-2-3 |
Ambient air temperature for operation | 5…122 °F (-15…50 °C) without derating)<br />122…140 °F (50…60 °C) with derating factor) | Ambient Air Temperature for Storage | -40…158 °F (-40…70 °C) |
Operating altitude | <= 3280.84 ft (1000 m) without derating<br />1000...4800 m with current derating 1 % per 100 m | Product Certifications | CSA<br />ATEX zone 2/22<br />ATEX INERIS<br />DNV-GL<br />UL<br />TÜV |
Marking | CE | Standards | UL 508C<br />IEC 61800-3<br />IEC 61800-3 environment 1 category C2<br />EN/IEC 61800-3 environment 2 category C3<br />IEC 61800-5-1<br />IEC 61000-3-12<br />IEC 60721-3<br />IEC 61508<br />IEC 13849-1 |
Overvoltage category | III | Regulation loop | Adjustable PID regulator |
Specifications may be subject to change without notice