Product Model

ATV630D75S6

In Stock
Last updated: 2025/4/19
schneider ATV630D75S6

Selling Points

  • 1High Amperage Rating: 89.4 A at 600 V Normal Duty, 70.1 A at 600 V Heavy Duty.
  • 2Efficient Power Output: 100 HP at 600 V Normal Duty, 75 HP at 600 V Heavy Duty.
  • 3Durable Enclosure: IP20 rating for protection against solid particles.
  • 4Versatile Connectivity: Modbus serial, Modbus TCP, Ethernet connectivity options.
  • 5Reliable Performance: Suitable for material handling and hoisting applications.
Product Details
ATV630D75S6
schneider

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Range of Product
Altivar Process ATV600
Product or Component Type
Variable speed drive
Product Specific Application
Process and utilities
Device short name
ATV630
Variant
Standard version
Product destination
Asynchronous motors<br />Synchronous motors
EMC filter
Without EMC filter
IP degree of protection
IP20IEC 61800-5-1<br />IP20IEC 60529
[Us] rated supply voltage
600 V - 15...10 %
Degree of protection
UL type 1 UL 508C
Type of cooling
Forced convection
Supply frequency
50...60 Hz - 5...5 %
Maximum Horse Power Rating
100 hp 600 V normal duty<br />75 hp 600 V heavy duty
Line current
89.4 A 600 V normal duty)<br />70.1 A 600 V heavy duty)
Prospective line Isc
70 kA
Apparent power
92.9 kVA 600 V normal duty)<br />72.9 kVA 600 V heavy duty)
Continuous output current
100 A 2.5 kHz normal duty<br />83 A 2.5 kHz heavy duty
Asynchronous motor control profile
Variable torque standard<br />Constant torque standard<br />Optimized torque mode
Synchronous motor control profile
Permanent magnet motor<br />Synchronous reluctance motor
Speed drive output frequency
0.1…500 Hz
Nominal switching frequency
2.5 kHz
Switching frequency
1...4.9 kHz adjustable<br />2.5...4.9 kHz with derating factor
Safety function
STO (safe torque off) SIL 3
Discrete input logic
Positive logic (source) DI1...DI8), < 5 V, > 11 V<br />Negative logic (sink) DI1...DI8), > 16 V, < 10 V
communication port protocol
Modbus serial<br />Modbus TCP<br />Ethernet
Option card
Slot A communication module, Profibus DP V1<br />Slot A communication module, PROFINET<br />Slot A communication module, DeviceNet<br />Slot A communication module, Modbus TCP/EtherNet/IP<br />Slot A communication module, CANopen daisy chain RJ45<br />Slot A communication module, CANopen SUB-D 9<br />Slot A communication module, CANopen screw terminals<br />Slot A/slot B digital and analog I/O extension module<br />Slot A/slot B output relay extension module<br />Slot A communication module, Ethernet IP/Modbus TCP/MD-Link<br /> communication module, BACnet MS/TP<br /> communication module, Ethernet Powerlink
Mounting Mode
Wall mount
Maximum transient current
110 A 60 s normal duty)<br />124.5 A 60 s heavy duty)
Phase
3 phase
Discrete output number
0
Discrete output type
Relay outputs R1A, R1B, R1C 250 V AC 3000 mA<br />Relay outputs R1A, R1B, R1C 30 V DC 3000 mA<br />Relay outputs R2A, R2C 250 V AC 5000 mA<br />Relay outputs R2A, R2C 30 V DC 5000 mA<br />Relay outputs R3A, R3C 250 V AC 5000 mA<br />Relay outputs R3A, R3C 30 V DC 5000 mA
Output voltage
<= power supply voltage
Permissible temporary current boost
1.1 x In 60 s normal duty)<br />1.5 x In 60 s heavy duty)
Motor slip compensation
Automatic whatever the load<br />Not available in permanent magnet motor law<br />Adjustable<br />Can be suppressed
Acceleration and deceleration ramps
S, U or customized<br />Linear adjustable separately from 0.01...9999 s
Physical interface
Ethernet<br />2-wire RS 485
Braking to standstill
By DC injection
Protection type
Thermal protection motor<br />Safe torque off motor<br />Motor phase break motor<br />Thermal protection drive<br />Safe torque off drive<br />Overheating drive<br />Overcurrent between output phases and earth drive<br />Overload of output voltage drive<br />Short-circuit protection drive<br />Motor phase break drive<br />Overvoltages on the DC bus drive<br />Line supply overvoltage drive<br />Line supply undervoltage drive<br />Line supply phase loss drive<br />Overspeed drive<br />Break on the control circuit drive
Transmission Rate
10, 100 Mbits<br />4800 bps, 9600 bps, 19200 bps, 38.4 Kbps
Frequency resolution
Display unit 0.1 Hz<br />Analog input 0.012/50 Hz
Transmission frame
RTU
Electrical connection
Control removable screw terminals 0.5...1.5 mm² AWG 20...AWG 16<br />Motor screw terminal 50 mm² AWG 1<br />Line side screw terminal 50 mm² AWG 1
Connector type
RJ45 on the remote graphic terminal)Ethernet/Modbus TCP<br />RJ45 on the remote graphic terminal)Modbus serial
Data format
8 bits, configurable odd, even or no parity
Type of polarization
No impedance
Exchange mode
Half duplex, full duplex, autonegotiation Ethernet/Modbus TCP
Number of addresses
1…247 Modbus serial
Method of access
Slave Modbus TCP
Supply
External supply for digital inputs 24 V DC 19…30 V), <1.25 mA overload and short-circuit protection<br />Internal supply for reference potentiometer (1 to 10 kOhm) 10.5 V DC +/- 5 %, <10 mA overload and short-circuit protection<br />Internal supply for digital inputs and STO 24 V DC 21…27 V), <200 mA overload and short-circuit protection
Local signalling
for local diagnostic 3 LEDs<br /> for embedded communication status 3 LEDs (dual colour)<br /> for communication module status 4 LEDs (dual colour)<br /> for presence of voltage 1 LED (red)
Width
13.03 in (331 mm)
Height
32.4 in (822 mm)
Depth
11.7 in (297 mm)
Net Weight
121.3 lb(US) (55 kg)
Analogue input number
3
Analogue input type
AI1, AI2, AI3 software-configurable voltage 0...10 V DC 31.5 kOhm 12 bits<br />AI1, AI2, AI3 software-configurable current 0...20 mA 250 Ohm 12 bits<br />AI2 voltage analog input - 10...10 V DC 31.5 kOhm 12 bits
Discrete input number
8
Discrete input type
DI7, DI8 programmable as pulse input 0…30 kHz, 24 V DC <= 30 V)
Input compatibility
DI1...DI6 discrete input level 1 PLC IEC 61131-2<br />DI5, DI6 discrete input level 1 PLC IEC 65A-68<br />STOA, STOB discrete input level 1 PLC IEC 61131-2
Analogue output number
2
Analogue output type
Software-configurable voltage AQ1, AQ2 0...10 V DC 470 Ohm 10 bits<br />Software-configurable current AQ1, AQ2 0...20 mA 10 bits<br />Software-configurable current DQ-, DQ+ 30 V DC<br />Software-configurable current DQ-, DQ+ 100 mA
Sampling duration
2 ms +/- 0.5 ms DI1...DI4) - discrete input<br />5 ms +/- 1 ms DI5, DI6) - discrete input<br />5 ms +/- 0.1 ms AI1, AI2, AI3) - analog input<br />10 ms +/- 1 ms AO1) - analog output
Accuracy
+/- 0.6 % AI1, AI2, AI3 for a temperature variation 60 °C analog input<br />+/- 1 % AO1, AO2 for a temperature variation 60 °C analog output
Linearity error
AI1, AI2, AI3 +/- 0.15 % of maximum value analog input<br />AO1, AO2 +/- 0.2 % analog output
Relay output number
3
Relay output type
Configurable relay logic R1 fault relay NO/NC 100000 cycles<br />Configurable relay logic R2 sequence relay NO 100000 cycles<br />Configurable relay logic R3 sequence relay NO 100000 cycles
Refresh time
Relay output R1, R2, R3)5 ms +/- 0.5 ms)
Minimum switching current
Relay output R1, R2, R3 5 mA 24 V DC
Maximum switching current
Relay output R1, R2, R3 resistive, cos phi = 1 3 A 250 V AC<br />Relay output R1, R2, R3 resistive, cos phi = 1 3 A 30 V DC<br />Relay output R1, R2, R3 inductive, cos phi = 0.4 7 ms 2 A 250 V AC<br />Relay output R1, R2, R3 inductive, cos phi = 0.4 7 ms 2 A 30 V DC
Isolation
Between power and control terminals
Maximum output frequency
500 kHz
Maximum Input Current per Phase
89.4 A
Quantity per Set
1
enclosure mounting
Wall mounted
Insulation resistance
> 1 MOhm 500 V DC for 1 minute to earth
Noise level
56 dB
Power dissipation in W
Natural convection 287 W 600 V 2.5 kHz<br />Forced convection 1206 W 600 V 2.5 kHz
Volume of cooling air
107255.8 Gal/hr(US) (406 m3/h)
Operating position
Vertical +/- 10 degree
Maximum THDI
<48 % with external line choke IEC 61000-3-12
Electromagnetic compatibility
Electrostatic discharge immunity test level 3 IEC 61000-4-2<br />Radiated radio-frequency electromagnetic field immunity test level 3 IEC 61000-4-3<br />Electrical fast transient/burst immunity test level 4 IEC 61000-4-4<br />1.2/50 µs - 8/20 µs surge immunity test level 3 IEC 61000-4-5<br />Conducted radio-frequency immunity test level 3 IEC 61000-4-6
Pollution degree
2
Vibration resistance
1.5 mm peak to peak 2…13 Hz)IEC 60068-2-6<br />1 gn 13…200 Hz)IEC 60068-2-6
Shock resistance
15 gn 11 ms IEC 60068-2-27
Relative humidity
5…95 % without condensation IEC 60068-2-3
Ambient air temperature for operation
5…122 °F (-15…50 °C) without derating)<br />122…140 °F (50…60 °C) with derating factor)
Ambient Air Temperature for Storage
-40…158 °F (-40…70 °C)
Operating altitude
<= 3280.84 ft (1000 m) without derating<br />1000...4800 m with current derating 1 % per 100 m
Product Certifications
TÜV<br />CSA<br />UL
marking
CE
Standards
UL 508C<br />IEC 61800-3<br />IEC 61800-5-1<br />IEC 61000-3-12<br />IEC 60721-3<br />IEC 61508<br />IEC 13849-1
Overvoltage category
III
Regulation loop
Adjustable PID regulator

Specifications may be subject to change without notice