Product Model

ATV630U75Y6

In Stock
Last updated: 2025/4/20
schneider ATV630U75Y6

Selling Points

  • 1High Performance: Designed for industrial applications, delivering reliable and efficient motor control.
  • 2Versatile Voltage Range: Operates at 500-690VAC, suitable for various industrial settings.
  • 3Integrated EMC Filter: Ensures electromagnetic compatibility with a 25m cable conforming to category C3.
  • 4Advanced Control Options: Supports Modbus TCP, Modbus serial, Ethernet, and other communication protocols.
  • 5Safety Features: Includes STO (Safe Torque Off) SIL 3 for enhanced safety in process and utility applications.
Product Details
ATV630U75Y6
schneider

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Range of Product
Altivar Process ATV600
Product or Component Type
Variable speed drive
Product Specific Application
Process and utilities
Device short name
ATV630
Variant
Standard version
Product destination
Asynchronous motors<br />Synchronous motors
EMC filter
Integrated 82.02 ft (25 m) IEC 61800-3 category C3
IP degree of protection
IP21IEC 60529<br />IP00IEC 61800-5-1
[Us] rated supply voltage
500...690 V - 15...10 %
Type of cooling
Forced convection
Supply frequency
50...60 Hz - 5...5 %
Motor power kW
5.5 kW 500 V normal duty)
Maximum Horse Power Rating
7.5 hp 600 V heavy duty<br />7.5 hp 500 V normal duty
Line current
7.7 A 600 V heavy duty)<br />10.4 A 500 V normal duty)
Prospective line Isc
70 kA
Apparent power
8 kVA 600 V heavy duty)<br />12.5 kVA 690 V normal duty)
Continuous output current
9.5 A 4 kHz heavy duty<br />7.2 A 4 kHz heavy duty
Asynchronous motor control profile
Optimized torque mode<br />Constant torque standard<br />Constant torque standard
Synchronous motor control profile
Synchronous reluctance motor<br />Permanent magnet motor
Speed drive output frequency
0.1…500 Hz
Nominal switching frequency
4 kHz
Switching frequency
4...12 kHz with derating factor<br />2...8 kHz adjustable
Safety function
STO (safe torque off) SIL 3
Discrete input logic
Positive logic (source) DI1...DI8), < 5 V, > 11 V<br />Negative logic (sink) DI1...DI8), > 16 V, < 10 V
communication port protocol
Ethernet<br />Modbus serial<br />Modbus TCP
Option card
Slot A communication module, PROFINET<br />Slot A communication module, DeviceNet<br />Slot A communication module, Modbus TCP/EtherNet/IP<br />Slot A communication module, CANopen daisy chain RJ45<br />Slot A communication module, CANopen SUB-D 9<br />Slot A communication module, CANopen screw terminals<br />Slot A/slot B digital and analog I/O extension module<br />Slot A/slot B output relay extension module<br />Slot A communication module, Ethernet IP/Modbus TCP/MD-Link<br /> communication module, BACnet MS/TP<br /> communication module, Ethernet Powerlink<br />Slot A communication module, Profibus DP V1
Mounting Mode
Wall mount
Maximum transient current
14.3 A 60 s heavy duty)<br />10.8 A 60 s heavy duty)
Phase
3 phase
Discrete output number
0
Discrete output type
Relay outputs R1A, R1B, R1C 250 V AC 3000 mA<br />Relay outputs R1A, R1B, R1C 30 V DC 3000 mA<br />Relay outputs R2A, R2C 250 V AC 5000 mA<br />Relay outputs R2A, R2C 30 V DC 5000 mA<br />Relay outputs R3A, R3C 250 V AC 5000 mA<br />Relay outputs R3A, R3C 30 V DC 5000 mA
Output voltage
<= power supply voltage
Permissible temporary current boost
1.5 x In 60 s heavy duty)<br />1.1 x In 60 s normal duty)
Motor slip compensation
Not available in permanent magnet motor law<br />Can be suppressed<br />Adjustable<br />Automatic whatever the load
Acceleration and deceleration ramps
S, U or customized<br />Linear adjustable separately from 0.01...9999 s
Physical interface
Ethernet<br />2-wire RS 485
Braking to standstill
By DC injection
Protection type
Safe torque off motor<br />Motor phase break motor<br />Thermal protection drive<br />Safe torque off drive<br />Overheating drive<br />Overcurrent between output phases and earth drive<br />Overload of output voltage drive<br />Short-circuit protection drive<br />Motor phase break drive<br />Overvoltages on the DC bus drive<br />Line supply overvoltage drive<br />Line supply undervoltage drive<br />Line supply phase loss drive<br />Overspeed drive<br />Break on the control circuit drive<br />Thermal protection motor
Transmission Rate
10, 100 Mbits<br />4800 bps, 9600 bps, 19200 bps, 38.4 Kbps
Frequency resolution
Analog input 0.012/50 Hz<br />Display unit 0.1 Hz
Transmission frame
RTU
Electrical connection
Motor screw terminal 6...10 mm² AWG 10...AWG 8<br />Line side screw terminal 6...10 mm² AWG 10...AWG 8<br />Control removable screw terminals 0.5...1.5 mm² AWG 20...AWG 16
Connector type
RJ45 on the remote graphic terminal)Modbus serial<br />RJ45 on the remote graphic terminal)Ethernet/Modbus TCP
Data format
8 bits, configurable odd, even or no parity
Type of polarization
No impedance
Exchange mode
Half duplex, full duplex, autonegotiation Ethernet/Modbus TCP
Number of addresses
1…247 Modbus serial
Method of access
Slave Modbus TCP
Supply
Internal supply for reference potentiometer (1 to 10 kOhm) 10.5 V DC +/- 5 %, <10 mA overload and short-circuit protection<br />Internal supply for digital inputs and STO 24 V DC 21…27 V), <200 mA overload and short-circuit protection<br />External supply for digital inputs 24 V DC 19…30 V), <1.25 mA overload and short-circuit protection
Local signalling
for embedded communication status 3 LEDs (dual colour)<br /> for communication module status 4 LEDs (dual colour)<br /> for presence of voltage 1 LED (red)<br /> for local diagnostic 3 LEDs
Width
9.7 in (246 mm)
Height
16.5 in (420 mm)
Depth
9.5 in (242 mm)
Net Weight
48.5 lb(US) (22 kg)
Analogue input number
3
Analogue input type
AI1, AI2, AI3 software-configurable voltage 0...10 V DC 31.5 kOhm 12 bits<br />AI1, AI2, AI3 software-configurable current 0...20 mA 250 Ohm 12 bits<br />AI2 voltage analog input - 10...10 V DC 31.5 kOhm 12 bits
Discrete input number
8
Discrete input type
DI7, DI8 programmable as pulse input 0…30 kHz, 24 V DC <= 30 V)
Input compatibility
DI5, DI6 discrete input level 1 PLC IEC 65A-68<br />STOA, STOB discrete input level 1 PLC IEC 61131-2<br />DI1...DI6 discrete input level 1 PLC IEC 61131-2
Analogue output number
2
Analogue output type
Software-configurable voltage AQ1, AQ2 0...10 V DC 470 Ohm 10 bits<br />Software-configurable current AQ1, AQ2 0...20 mA 10 bits<br />Software-configurable current DQ-, DQ+ 30 V DC<br />Software-configurable current DQ-, DQ+ 100 mA
Sampling duration
5 ms +/- 1 ms DI5, DI6) - discrete input<br />5 ms +/- 0.1 ms AI1, AI2, AI3) - analog input<br />10 ms +/- 1 ms AO1) - analog output<br />2 ms +/- 0.5 ms DI1...DI4) - discrete input
Accuracy
+/- 1 % AO1, AO2 for a temperature variation 60 °C analog output<br />+/- 0.6 % AI1, AI2, AI3 for a temperature variation 60 °C analog input
Linearity error
AO1, AO2 +/- 0.2 % analog output<br />AI1, AI2, AI3 +/- 0.15 % of maximum value analog input
Relay output number
3
Relay output type
Configurable relay logic R2 sequence relay NO 100000 cycles<br />Configurable relay logic R3 sequence relay NO 100000 cycles<br />Configurable relay logic R1 fault relay NO/NC 100000 cycles
Refresh time
Relay output R1, R2, R3)5 ms +/- 0.5 ms)
Minimum switching current
Relay output R1, R2, R3 5 mA 24 V DC
Maximum switching current
Relay output R1, R2, R3 resistive, cos phi = 1 3 A 30 V DC<br />Relay output R1, R2, R3 inductive, cos phi = 0.4 7 ms 2 A 250 V AC<br />Relay output R1, R2, R3 inductive, cos phi = 0.4 7 ms 2 A 30 V DC<br />Relay output R1, R2, R3 resistive, cos phi = 1 3 A 250 V AC
Isolation
Between power and control terminals
Maximum output frequency
500 kHz
Maximum Input Current per Phase
10.5 A
Quantity per Set
1
enclosure mounting
Wall mounted
Insulation resistance
> 1 MOhm 500 V DC for 1 minute to earth
Noise level
58 dB
Power dissipation in W
Forced convection 110 W 600 V 4 kHz<br />Natural convection 88 W 500 V 4 kHz
Volume of cooling air
87178.3 Gal/hr(US) (330 m3/h)
Operating position
Vertical +/- 10 degree
Maximum THDI
<48 % with external line choke IEC 61000-3-12
Electromagnetic compatibility
Radiated radio-frequency electromagnetic field immunity test level 3 IEC 61000-4-3<br />Electrical fast transient/burst immunity test level 4 IEC 61000-4-4<br />1.2/50 µs - 8/20 µs surge immunity test level 3 IEC 61000-4-5<br />Conducted radio-frequency immunity test level 3 IEC 61000-4-6<br />Electrostatic discharge immunity test level 3 IEC 61000-4-2
Pollution degree
2
Vibration resistance
1 gn 13…200 Hz)IEC 60068-2-6<br />1.5 mm peak to peak 2…13 Hz)IEC 60068-2-6
Shock resistance
15 gn 11 ms IEC 60068-2-27
Relative humidity
5…95 % without condensation IEC 60068-2-3
Ambient air temperature for operation
122…140 °F (50…60 °C) with derating factor)<br />5…122 °F (-15…50 °C) without derating)
Ambient Air Temperature for Storage
-40…158 °F (-40…70 °C)
Operating altitude
1000...4800 m with current derating 1 % per 100 m<br /><= 3280.84 ft (1000 m) without derating
Product Certifications
TÜV<br />CSA<br />UL
marking
CE
Standards
IEC 61800-3<br />IEC 61800-5-1<br />IEC 61000-3-12<br />IEC 60721-3<br />IEC 61508<br />IEC 13849-1<br />UL 508C
Overvoltage category
III
Regulation loop
Adjustable PID regulator

Specifications may be subject to change without notice